407.4.4.4 Doors within care suites.
Doors in care suites serving habitable rooms shall be permitted to comply with one of the following:
1. Manually operated horizontal sliding doors permitted in accordance with Exception 9 to Section 1010.1.2.1.
2. Power-operated doors permitted in accordance with Exception 7 to Section 1010.1.2.1.
3. Means of egress doors complying with Section 1010.
407.4.4.5 Care suites containing sleeping room areas.
Sleeping rooms shall be permitted to be grouped into care suites where one of the following criteria is met:
1. The care suite is not used as an exit access for more than eight care recipient beds.
2. The arrangement of the care suite allows for direct and constant visual supervision into the sleeping rooms by care providers.
3. An automatic smoke detection system is provided in the sleeping rooms and installed in accordance with NFPA 72 as modified by Appendix Q of this code.
407.4.4.5.1 Area.
Care suites containing sleeping rooms shall be not greater than 7,500 square feet (696 m
2
) in area.
Exception: Care suites containing sleeping rooms shall be permitted to be not greater than 10,000 square feet (929 m
2
) in area where an automatic smoke detection system is provided throughout the care suite and installed in accordance with NFPA 72 as modified by Appendix Q of this code.
407.4.4.5.2 Exit access.
Any sleeping room, or any care suite that contains sleeping rooms, of more than 1,000 square feet (93 m
2
) shall have no fewer than two exit access doors from the care suite located in accordance with Section 1007.
407.4.4.6 Care suites not containing sleeping rooms.
Areas not containing sleeping rooms, but only treatment areas and the associated rooms, spaces or circulation space, shall be permitted to be grouped into care suites and shall conform to the limitations in Sections 407.4.4.6.1 and 407.4.4.6.2.
407.4.4.6.1 Area.
Care suites of rooms, other than sleeping rooms, shall have an area not greater than 12,500 square feet (1161 m
2
).
Exception: Care suites not containing sleeping rooms shall be permitted to be not greater than 15,000 square feet (1394 m
2
) in area where an automatic smoke detection system is provided throughout the care suite in accordance with Section 907.