Loading...
407.4.4.1 Exit access through care suites.
Exit access from all other portions of a building not classified as a care suite shall not pass through a care suite. In a care suite required to have more than one exit, one exit access is permitted to pass through an adjacent care suite provided all of the other requirements of Sections 407.4 and 1016.2 are satisfied.
407.4.4.2 Separation.
Care suites shall be separated from other portions of the building, including other care suites, by a smoke partition complying with Section 710.
407.4.4.3 Access to corridor.
Movement from habitable rooms shall not require passage through more than three doors and 100 feet (30 480 mm) distance of travel within the suite.
Exception: The distance of travel shall be permitted to be increased to 125 feet (38 100 mm) where an automatic smoke detection system is provided throughout the care suite and installed in accordance with NFPA 72 as modified by Appendix Q of this code.
(Am. L.L. 2023/077, 6/11/2023, eff. 6/11/2023)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2023/077.
407.4.4.4 Doors within care suites.
Doors in care suites serving habitable rooms shall be permitted to comply with one of the following:
1. Manually operated horizontal sliding doors permitted in accordance with Exception 9 to Section 1010.1.2.1.
2. Power-operated doors permitted in accordance with Exception 7 to Section 1010.1.2.1.
3. Means of egress doors complying with Section 1010.
407.4.4.5 Care suites containing sleeping room areas.
Sleeping rooms shall be permitted to be grouped into care suites where one of the following criteria is met:
1. The care suite is not used as an exit access for more than eight care recipient beds.
2. The arrangement of the care suite allows for direct and constant visual supervision into the sleeping rooms by care providers.
3. An automatic smoke detection system is provided in the sleeping rooms and installed in accordance with NFPA 72 as modified by Appendix Q of this code.
Loading...