Loading...
Section 1031.2.1, Operational Constraints, of the IFC, is hereby amended by adding the following:
Section 1031.2.1 Operational constraints The net clear opening dimensions required by this section shall be obtained by the normal operation of the emergency escape and rescue opening from the inside and shall not require the removal of a sash or other component of the emergency escape and rescue opening.
Section 1103.5.3, Group I-2, Condition 2, of the IFC is hereby modified by inserting the following:
Section 1103.5.3 Group I-2, Condition 2 (insert date by which sprinkler system must be installed): At such time as mandated by the Iowa State Fire Marshal, Iowa Department of Inspections and Appeals, Iowa Department of Public Safety.
Section1107 is hereby established with the inclusion of the following sections:
Section 1107.1 Existing CSST - Bonding In Rental Units All rental dwellings shall be bonded in accordance with the Ankeny Fuel Gas Code, unless deemed technically infeasible by the Code Official.
Section 1107.2 Existing CSST - Bonding In Other Than Rental Units For other than rental dwelling units, where alterations, repairs or additions requiring a permit occur, CSST shall be bonded in accordance with sections 310.2.1 through 310.2.5 of the Ankeny Fuel Gas Code, unless deemed technically infeasible by the Code Official.
Section 1203.7, Shutdown of Emergency and Standby Power Systems, of the IFC, is hereby established by adding the following section:
Section 1203.7 Shutdown of Emergency and Standby Power Systems In addition to the requirements of NFPA 110 for a remote manual stop, a switch of an approved type shall be provided to shut down the generator. The switch shall be provided at an approved location.
Section 1203.8, Emergency Generator Signs, of the IFC, is hereby established by adding the following section:
Section 1203.8 Emergency Generator Signs Main electrical disconnects and main breaker panels supplied by the generator shall be provided with approved signs. Additionally, doors accessing emergency and standby power systems shall be provided with approved signs. When approved switches for emergency power shut-down are located remote from the fire alarm annunciator, an approved sign shall be provided at fire alarm annunciator. Approved signs shall contain the word CAUTION in black letters at least 2 inches (50 mm) high on a yellow background. Such warning signs shall be placed so as to be readily discernible.
Section 3301.2, Purpose, of the IFC, is hereby amended by deleting said section and inserting in lieu thereof the following:
Section 3301.2 Purpose This chapter prescribes minimum safeguards for construction, alteration and demolition operations to provide reasonable safety to life and property from fire and other emergencies during such operations.
Loading...