180.21 SECTION 507.5.1.1 AMENDED - - HYDRANT FOR FIRE DEPARTMENT CONNECTIONS.
Section 507.5.1.1, Hydrant For Fire Department Connections, of the IFC, is hereby established by deleting said section and inserting in lieu thereof the following:
Section 507.5.1.1 Hydrant For Fire Department Connections Buildings equipped with a fire department connection installed in accordance with Section 912 shall have a fire hydrant located on a fire access road within 100 feet (30 m) of the fire department connection as measured by an approved route around the exterior of the building.
Exception: The distance shall be permitted to exceed 100 feet (30 m) where approved by the Code Official