Automatic smoke and heat vents shall be installed on the topmost occupied level of every exhibition area at a vent ratio of one square foot of vent area for each 100 square feet of floor area. Vents shall be spaced no greater than 100 feet apart (on centers).
(Prior code § 54-9.1)
Exhibition areas on lower floor levels shall be provided with automatic smoke and heat venting at a rate of two cfm per square foot measured at 70 degrees Fahrenheit. Fans for this purpose are to be wired to an emergency power supply and operated by smoke detectors. All smoke detectors shall be approved by Underwriters Laboratories and the fire commissioner.
(Prior code § 54-9.3; Amend Coun. J. 5-18-16, p. 24131, § 41)
Every newly constructed, reconstructed or substantially rehabilitated nightclub or restaurant with an occupancy of more than 100 persons and located in whole or in part more than four feet below street grade shall be equipped with an approved automatic sprinkler system. Every existing nightclub or restaurant with an occupancy of more than 100 persons and located in whole or in part more than four feet below street grade shall be equipped with an approved automatic sprinkler system within six months after the effective date of this section.
(Added Coun. J. 11-1-00, p. 43076, § 2)
All mechanical equipment used in supplying or recirculating air in an exhibition area shall be automatically stopped by smoke detectors. Smoke detectors shall be approved as required in Section 13-84-330 of this Code.
(Prior code § 54-9.5)
All temporary booths erected within assembly units shall comply with the following minimum requirements:
a. One approved battery-operated smoke alarm for each 1,000 square feet of enclosed area; and
b. One approved fire extinguisher for each 1,000 square feet of enclosed area.
(Added Coun. J. 9-15-93, p. 37767; Amend Coun. J. 9-6-17, p. 55278, Art. VI, § 23)
Areas used for storage of combustible containers in new and existing buildings with exhibition areas shall be enclosed with two-hour fire-resistive construction and shall have a standard sprinkler system as defined in Chapter 15-16 of this Code.
(Prior code § 54-10)