Skip to code content (skip section selection)
Compare to:
Chicago Overview
Prior Chicago Building Code
BUILDING CODE AND RELATED EXCERPTS OF THE MUNICIPAL CODE OF CHICAGO
DIVISION 1 - ADMINISTRATION
DIVISION 2 - DEFINITIONS
DIVISION 3 - USE AND OCCUPANCY CLASSIFICATIONS
Subdivision 302 - Classification
Subdivision 303 - Assembly
CHAPTER 13-84 ASSEMBLY UNITS
13-84-010 General requirements.
13-84-020 Capacity of schools.
13-84-030 Frontage requirements.
13-84-040 Special height limitations.
13-84-050 Special enclosures and separations.
13-84-060 Special fire-resistive requirements.
13-84-070 Definitions.
13-84-080 Construction requirements - Type 1 stages.
13-84-090 Construction requirements - Type 2 stages.
13-84-100 Stage vents - Type 1 stages.
13-84-110 Proscenium opening - Type 1 stages.
13-84-120 Projection rooms.
13-84-130 Bowling alleys.
13-84-140 Planning requirements for Type I schools.
13-84-150 Planning requirements for Type III schools.
13-84-160 Special exit requirements.
13-84-170 Minimum number of exits.
13-84-180 Width of exits.
13-84-190 Location of exits.
13-84-200 Exit connections.
13-84-210 Exit courts and exit passageways.
13-84-220 Waiting spaces.
13-84-230 Aisles and seating.
13-84-240 Railings.
13-84-250 Ramps and steps.
13-84-260 Exits from stage block.
13-84-270 Fixed seating.
13-84-280 Schools for handicapped children - Elevator requirements.
13-84-290 Accessibility for handicapped.
13-84-300 Exhibition areas in excess of 10,000 square feet.
13-84-310 Automatic smoke and heat vents - Requirements for topmost occupied levels.
13-84-320 Noncombustible draft curtains - Where required.
13-84-330 Automatic smoke and heat vents - Requirements for lower floor levels.
13-84-331 Special requirement for nightclubs and restaurants.
13-84-340 Exhibition area minimum aisle width.
13-84-350 Smoke detectors.
13-84-351 Temporary display booths.
13-84-360 Storage of combustible containers.
13-84-370 Open plan schools - Individual plan floor areas.
13-84-380 Stair enclosures.
13-84-390 Fire guard requirements.
13-84-400 Floor plan diagram to be submitted to department of buildings.
13-84-410 Building capacity - Signs to be posted.
13-84-420 Building capacity - Approval required.
13-84-430 Exit and aisle regulations.
CHAPTER 13-88 OPEN AIR ASSEMBLY UNITS
Subdivision 304 - Business
Subdivision 306 - Factory
Subdivision 307 - High-Hazard
Subdivision 308 - Institutional
Subdivision 309 - Mercantile
Subdivision 310 - Residential
Subdivision 311 - Storage
Subdivision 312 - Utility and Miscellaneous
DIVISION 4 - SPECIAL DETAILED REQUIREMENTS BASED ON USE AND OCCUPANCY
DIVISION 5 - GENERAL BUILDING HEIGHTS AND AREAS
DIVISION 6 - TYPES OF CONSTRUCTION
DIVISION 7 - FIRE-RESISTANCE-RATED CONSTRUCTION
DIVISION 8 - INTERIOR FINISHES (NA)
DIVISION 9 - FIRE PROTECTION SYSTEMS
DIVISION 10 - MEANS OF EGRESS
DIVISION 11 - ACCESSIBILITY
DIVISION 12 - INTERIOR ENVIRONMENT
DIVISION 13 - ENERGY EFFICIENCY AND ENVIRONMENTAL PROTECTION
DIVISION 14 - EXTERIOR WALLS (NA)
DIVISION 15 - ROOF ASSEMBLIES AND ROOFTOP STRUCTURES (NA)
DIVISION 16 - STRUCTURAL DESIGN
DIVISION 17 - STRUCTURAL TESTS AND SPECIAL INSPECTIONS
DIVISION 18 - SOILS AND FOUNDATIONS
DIVISION 19 - CONCRETE
DIVISION 20 - ALUMINUM (NA)
DIVISION 21 - MASONRY
DIVISION 22 - STEEL
DIVISION 23 - WOOD
DIVISION 24 - GLASS AND GLAZING (NA)
DIVISION 25 - GYPSUM BOARD AND PLASTER (NA)
DIVISION 26 - PLASTIC (NA)
DIVISION 27 - ELECTRICAL
DIVISION 28 - MECHANICAL SYSTEMS
DIVISION 29 - PLUMBING SYSTEMS
DIVISION 30 - ELEVATORS AND CONVEYING SYSTEMS
DIVISION 31 - SPECIAL CONSTRUCTION (NA)
DIVISION 32 - ENCROACHMENTS INTO THE PUBLIC RIGHT-OF-WAY
DIVISION 33 - SAFEGUARDS DURING CONSTRUCTION
DIVISION 34 - EXISTING STRUCTURES
DIVISION 35 - REFERENCED STANDARDS

You are viewing an archived code

Loading...
13-84-230  Aisles and seating.
   All aisles and seating in assembly units shall comply with the requirements of this section.
   (a)   Arrangement of Aisles. Every aisle shall lead to an exit door or to another aisle leading directly to an exit.
   (b)   Seating. No row of seats shall have more than 14 seats between aisles and not more than seven seats abutting an aisle at one end only, with the following exceptions:
      (1)   In assembly units of Type I-A or I-B construction, other than theaters, there may be not more than 20 seats between aisles and not more than ten seats abutting an aisle at one end only.
      (2)   When the distance between rows of seats is increased above that required by Section 13-84-230(e), the number of seats between aisles may be increased by one seat for each inch that such distance is increased; provided, however, that in no case shall there be more than ten seats in a row abutting an aisle on one end only.
      (3)   When the distance between rows of seats is increased above that required in Section 13-84-230(e), by an amount of eight inches, rows not exceeding 48 seats between aisles shall be permitted.
   (c)   Transverse Aisles.
      (1)   Transverse aisles leading to exits shall be provided at the rear of every seating level unless there are exits at the end of each longitudinal aisles.
      (2)   Transverse aisles shall be provided in all seating levels so that in no case shall there be a difference of level exceeding 12 feet between intermediate transverse aisles nor six feet from the lowest seat platform and a transverse aisle; provided, however, that in lieu of such transverse aisles there may be vomitories or other direct exits from each longitudinal aisle located at the same maximum difference of level.
   (d)   Width of Aisles.
      (1)   No aisle shall be less than 36 inches in width except that aisles with seats on one side only, and aisles serving not more than 60 seats, may have a minimum width of 30 inches.
      (2)   Transverse aisles shall have a minimum width of 44 inches.
      (3)   Aisles shall be increased in width where necessary to provide a clear width at every point equal to 18 inches for each 100 persons served. Such increase shall be cumulative in the direction of normal exit.
   (e)   Spacing of Rows.
      (1)   Rows of seats without backs shall be not less than 28 inches apart measured from corresponding points of adjacent rows. Telescoping bleachers without backs shall be not less than 24 inches apart measured from corresponding points of adjacent rows.
      (2)   Rows of seats with backs shall be spaced not less than 34 inches apart, measured back to back except that such distance may be reduced to 32 inches when the thickness of the back does not exceed three- fourths inch.
(Prior code § 54-8.7)
13-84-240  Railings.
   (a)   The facias of boxes, balconies, galleries and at the end of the aisles shall have substantial metal protective railings not less than 30 inches high above the floor. The railings at the foot of steps shall be not less than 36 inches high for the width of the steps.
   (b)   Cross-aisles, except where the backs of seats on the front of the aisles project 24 inches or more above the floor of the aisles, shall be provided with railings not less than 26 inches high.
   (c)   In balconies, galleries or other locations where seats are arranged on platforms or successive tiers, and the height of the rise from one platform to another below and in front of it exceeds 21 inches, a substantial railing not less than 26 inches high shall be placed at the edge of the platform along the entire rows of seats.
(Prior code § 54-8.8)
13-84-250  Ramps and steps.
   Steps shall not be used in aisles where differences of level can be overcome by ramps having a grade of not more than one in eight. Where steps are used in aisles, such steps shall extend across the full width of aisles and shall be illuminated. Treads and risers shall be as required in Chapter 13-160 of this Code for exit stairs.
(Prior code § 54-8.9)
13-84-260  Exits from stage block.
   (a)   There shall be not less than two exits from every part of a stage block.
   (b)   Exits from the stage floor level shall be located at opposite sides of the stage.
   (c)   One of the required exits from every gridiron shall extend to the roof of the stage block or to a doorway through the wall.
   (d)   Every stairway located within a stage block shall be constructed of noncombustible materials.
(Prior code § 54-8.10)
13-84-270  Fixed seating.
   In places of public assembly where more than 200 seats are arranged in rows, the seats shall be securely fastened to the floor except as follows:
   (a)   Seats in boxes and railed-in enclosures having not more than 14 seats.
   (b)   Temporary seating in a place of assembly secured together in units of not less than five seats.
(Prior code § 54-8.11)
13-84-280  Schools for handicapped children – Elevator requirements.
   Every floor above the second floor in a school for crippled children shall be served by an elevator or elevators with a floor area of at least four square feet per person, computed on the basis of a carrying capacity of all elevators sufficient to empty the school above the second floor in 20 minutes.
(Prior code § 54-8.12)
13-84-290  Accessibility for handicapped.
   Places of assembly shall conform to the following requirements in addition to requirements set forth in other sections of this Code:
   (a)   Such places of assembly shall provide a clear space in the assembly units for individuals in wheelchairs;
   (b)   These spaces shall be located so as not to interfere with egress from any row of seats;
   (c)   Places of assembly with fixed seating arrangements shall provide viewing positions for individuals in wheelchairs in accordance with the following schedule:
 
Capacity of Assembly Space:
Number of Viewing Spaces:
Up to 50 seats:
2 spaces
51 to 400 seats:
4 spaces
401 or more seats:
An even number of spaces not less than 1% of total seats.
 
(Prior code § 54-8.13)
13-84-300  Exhibition areas in excess of 10,000 square feet.
   Every new exhibition area in excess of 10,000 square feet shall comply with all applicable provisions of this Code and with the provisions of Sections 13-84-310 through 13-84-350 of this Code.
(Prior code § 54-9)
13-84-310  Automatic smoke and heat vents – Requirements for topmost occupied levels.
   Automatic smoke and heat vents shall be installed on the topmost occupied level of every exhibition area at a vent ratio of one square foot of vent area for each 100 square feet of floor area. Vents shall be spaced no greater than 100 feet apart (on centers).
(Prior code § 54-9.1)