13-84-310  Automatic smoke and heat vents – Requirements for topmost occupied levels.
   Automatic smoke and heat vents shall be installed on the topmost occupied level of every exhibition area at a vent ratio of one square foot of vent area for each 100 square feet of floor area. Vents shall be spaced no greater than 100 feet apart (on centers).