13-84-190  Location of exits.
   (a)   Exits shall be located as remote from each other as is practicable. In rooms, spaces or seating levels having fixed seats and requiring more than two exits, the exits shall be so located as to serve both sides of the front half and both sides of the rear half of the seating level.
   (b)   All required stairs in Type I schools shall open directly to the outside air or to a public vestibule or lobby leading to the outside. The travel distance from the stairway to the outside exit door of such vestibule or lobby shall not exceed 20 feet.
(Prior code § 54-8.3)