Loading...
(Amended by Ord. 186,488, Eff. 12/27/19.)
Section 1703 of the CBC is adopted by reference, except Sections 1703.1, 1703.2, 1703.3, 1703.4, 1703.4.1, and 1703.4.2 of the CBC are not adopted; and, in lieu LAMC Subsections 91.1703.1, 91.1703.2, 91.1703.3, 91.1703.4, 91.1703.4.1, and 91.1703.4.2 are added.
91.1703.1. Approved Agency. (Amended by Ord. No. 185,587, Eff. 7/16/18.) Pursuant to LAMC Section 98.0503, a testing agency shall provide all information required by the Superintendent of Building to determine whether the agency shall become an approved testing agency.
91.1703.2. Written Approval. (Amended by Ord. No. 185,587, Eff. 7/16/18.) Any new material, appliance, equipment, system or method of construction meeting the requirements of this Code shall be approved in writing after satisfactory completion of the required tests and submission of required test reports pursuant to LAMC Sections 98.0501 and 98.0502.
91.1703.3. Approved Record. For any material, appliance, equipment, system or method of construction that has been approved, a record of that approval, including the conditions and limitations of the approval, shall be kept on file in the Department and shall be open to public inspection at appropriate times.
91.1703.4. Performance. Specific information consisting of test reports conducted by an approved testing agency in accordance with standards referenced in Division 35, Article 1, Chapter IX of the LAMC, or other information as necessary, shall be provided for the Superintendent of Building to determine that the material meets the applicable Code requirements, including LAMC Sections 98.0501 and 98.0502.
91.1703.4.1. Research and Investigation. (Amended by Ord. 186,488, Eff. 12/27/19.) Sufficient technical data shall be submitted to the Superintendent of Building to substantiate the proposed use of any product, material or assembly. If it is determined that the evidence submitted is satisfactory proof of performance for the use intended, the Superintendent of Building shall approve the use of the product, material or assembly subject to the requirements of this Code. The costs, reports and investigations required under these provisions shall be paid by the permit applicant as required by LAMC Sections 98.0501, 98.0502 and 98.0503.
91.1703.4.2. Research Reports. (Amended by Ord. 186,488, Eff. 12/27/19.) Supporting data, where necessary to assist in the approval of products, materials or assemblies not specifically provided for in this Code, shall consist of valid research reports from approved sources as required in LAMC Sections 98.0501 and 98.0502.
(Amended by Ord. No. 187,719, Eff. 1/23/23.)
Section 1704 of the CBC is adopted by reference, except that CBC Sections 1704.2, 1704.2.1, 1704.2.3, 1704.2.4, 1704.2.5, 1704.2.5.1, 1704.2.5.2, 1704.6, 1704.6.1, 1704.7, 1704.8, and 1704.9 are not adopted; and, in lieu, LAMC Subsections 91.1704.1.1, 91.1704.1.2, 91.1704.1.3, 91.1704.1.4, 91.1704.1.5, 91.1704.1.6, 91.1704.1.7, 91.1704.2, 91.1704.2.1, 91.1704.2.1.1, 91.1704.2.1.3, 91.1704.2.3, 91.1704.2.4, 91.1704.2.5, 91.1704.2.5.1, 91.1704.2.5.2, 91.1704.6, and 91.1704.6.1 are added or amended to read as follows:
91.1704.1.2. Registration. Application for registration as a certified licensed contractor shall be made to the Superintendent of Building on a form furnished by the Department and a separate application shall be made for each type of registration desired. Before the application can be accepted, the applicant must furnish proof satisfactory to the Department that the applicant holds a valid active California State Contractor's License in the same specialty as the certification requested.
1. Form. Application for a Certificate of Registration shall be made on a form furnished by the Department.
2. Information Necessary. The application shall bear the name and address of the applicant and, if the applicant is employed by a firm, partnership or corporation, the names of the principal officers should also be included. The application shall carry other information deemed necessary by the Department.
3. Verification. The applicant shall declare that the information contained in the application is true and correct.
4. Fee. The application shall be accompanied by an examination fee of $188.
1. Examination Required. Before issuance of a Certificate of Registration, the applicant shall have successfully passed the examination required for the issuance of the Certificate of Registration within ninety (90) days preceding the date of the issuance. To be eligible for the examination for a Certificate of Registration, the applicant shall have a valid California State Contractor’s License in an appropriate specialty and a valid City Business Tax Certificate.
2. Board of Examiners. The Superintendent of Building and/or Board of Examiners composed of three qualified persons appointed by the Superintendent of Building shall conduct examinations. The results of every examination shall be subject to the approval of the Superintendent of Building. Each examiner shall serve at the pleasure of the Superintendent of Building and shall serve for a period of one year unless re-appointed by the Superintendent of Building. (Amended by Ord. No. 185,587, Eff. 7/16/18.)
3. Scope of Examination. The examination shall, in the judgment of the Superintendent of Building, fairly determine the ability of the applicant to perform properly the work, which the applicant would be authorized to do by the Certificate of Registration requested, and may include the following:
a. A written test.
b. Practical tests as may be required.
c. An oral interview as may be required.
d. Other tests as may be required by the Board of Examiners.
4. Time of Examination. The applicant shall be examined as soon as practicable after filing an application.
5. Rules and Regulations. The Department shall have the authority to establish rules and regulations for the conduct of examinations.
6. Fitness of Applicant. Any applicant may be required to submit satisfactory proof of the applicant’s fitness to carry out the intent of this Code.
7. Failure to Pass. An applicant who fails to pass an examination shall not be eligible for another examination until four (4) weeks after taking the previous examination.
1. The Superintendent of Building shall issue separate Certificates of Registration for each of the following categories:
a. FAU/AC units; evaporative coolers.
b. Domestic water piping/plumbing fixtures/hot water heaters/solar panels.
c. Reroofing and roof repair.
d. Electrical equipment/fixtures/smoke detectors.
e. Masonry and concrete fences.
f. Masonry chimney repairs.
g. Shower pan replacement.
Nothing here prohibits any person from being qualified for more than one type of certification, provided the person files an application, pays the required fees, takes the required examinations and is duly qualified by the Superintendent of Building for each type of certification. (Amended by Ord. No. 185,587, Eff. 7/16/18.)
2. Upon payment of a $45 fee, the Department may issue a Certificate of Registration to every applicant who passes the required examination for a Certified Licensed Contractor.
3. Each Certificate of Registration shall expire twelve (12) months from the date of issuance.
4. The Superintendent of Building shall keep on file a list, open to public inspection, of the names of all registered certified licensed contractors, showing the type of work each has been authorized to inspect.
5. Renewal of Certificates. Expired Certificates of Registration may be renewed at any time within thirty (30) days following the date of expiration. After a Certificate of Registration has been expired for thirty (30) days, it may not be renewed; rather, a new application for a new certificate must be submitted at that time.
1. Every person having a fixed place of business shall keep their Certificate of Registration posted in some conspicuous location at their place of business during the time the certificate is in force.
2. Every person not having a fixed place of business shall carry their Certificate of Registration with them at all times while doing any inspections or other work pursuant to this certificate.
91.1704.1.7. Revocation of Certificate. The Superintendent of Building may revoke, suspend or refuse to renew any Certificate of Registration upon a showing of incompetence, willful or negligent failure to observe or report violations of this Code, or failure to maintain a valid active California State Contractor's License in the same specialty as the certification. Prior to any action, the holder shall be given an opportunity to appear before the Superintendent of Building and be heard.
Suspension or revocation of any Certificate of Registration issued under this Section shall be in accordance with the provisions of Article 8, Chapter IX of the LAMC. (Amended by Ord. No. 185,587, Eff. 7/16/18.)
91.1704.2. Special Inspections. Where application is made for construction as described in this section, the owner or the registered design professional in responsible charge acting as the owner's agent shall employ one or more Registered Deputy Inspectors to perform inspections during construction on the types of work listed under CBC Section 1705. The Registered Deputy Inspector shall be a qualified person as set forth in LAMC Subsection 91.1704.2.1 and shall demonstrate competence to the satisfaction of the Superintendent of Building for inspection of the particular type of construction or operation requiring special inspection.
The special inspections shall be in addition to the inspections made by the employees of the Department as set forth in LAMC Section 91.108.
All special inspections shall be made by a Registered Deputy Inspector. Whenever the term "Special Inspector" is used in this Code, it shall mean "Registered Deputy Inspector" as described in LAMC Subdivision 91.1704.2.1.
EXCEPTIONS:
1. Special inspections are not required for construction of a minor nature or as warranted by conditions in the jurisdiction as approved by the Superintendent of Building.
2. Unless otherwise required by the Superintendent of Building, special inspections are not required for Group U occupancies that are accessory to a residential occupancy including, but not limited to, those listed in CBC Section 312.1.
3. Special inspections are not required for portions of structures designed and constructed in accordance with the cold-formed steel light-frame construction provisions of CBC Section 2211.7 or the conventional light-frame construction provisions of CBC Section 2308.
4. The contractor is permitted to employ the approved agencies where the contractor is also the owner.
91.1704.2.1. Registered Deputy Inspector Qualifications. An applicant for Deputy Inspector shall provide written documentation to the Superintendent of Building demonstrating the applicant’s competence and relevant experience or training. Experience or training shall be considered relevant when the documented experience or training is related in complexity to the same type of special inspection activities for projects of similar complexity and material qualities. These qualifications are in addition to qualifications specified in other sections of this Code.
Application for registration as a Registered Deputy Inspector shall be made to the Superintendent of Building on a form furnished by the Department. A separate application shall be made for each type of registration desired. Registration is available for the following types of inspections: Reinforced Concrete (RC), Structural Masonry (SM), Structural Steel/Welding (SSW), Grading (GD), Sprayed Fire resistant Materials (SFRM), Methane Barrier (MB) and Wood (WD).
A committee appointed by the Superintendent of Building shall examine each applicant as to the applicant’s experience and training for performing the duties of an inspector of the type for which application has been made. Additionally, the applicant will be examined on the applicant’s knowledge of the LAMC and Registered Deputy Inspector duties, responsibilities and procedures. When satisfied as to the fitness of the applicant, the Superintendent of Building shall issue a Certificate of Registration. Upon application for renewal of a Certificate of Registration, the applicant shall be re-examined to ascertain the applicant’s fitness to perform the duties of inspector of the type for which application has been made.
EXCEPTION: If the Department determines that the initial examination (which includes general knowledge, code requirements and plan comprehension) for the special inspector program under the International Code Council (ICC) is equivalent to the above-described initial or renewal examination, then the Department may accept the results of the ICC examination in lieu of the Department’s examination in that category; however, the Department will be examining the applicant’s knowledge of the LAMC and Registered Deputy Inspector duties, responsibilities and procedures.
The Superintendent of Building shall issue a separate Certificate of Registration for each type of registration requiring special inspection in accordance with LAMC Section 91.1704 and as determined by the Superintendent of Building for any construction requiring either continuous or periodic special inspection.
Nothing here shall be deemed to prohibit any one person from being qualified for more than one type of special inspection, provided the person applies, pays the required fees, takes the required examinations and is duly qualified by the Superintendent of Building for each type.
Each Certificate of Registration shall expire three (3) years from the date of issuance, but may be renewed by the Superintendent of Building within a grace period of thirty (30) days thereafter.
The Department shall maintain a list of the names of all Registered Deputy Inspectors, showing the type of work each has been authorized to inspect. This list shall be available to the public.
Upon evidence satisfactory to the Superintendent of Building of incompetence, of willful or negligent failure to observe or report violations of this Code, or of any other failure to perform properly and effectively the duties assumed by a Registered Deputy Inspector, the Superintendent of Building may revoke, suspend or refuse to renew any Certificate of Registration. But, prior to that action, the holder shall be given an opportunity to appear before the Superintendent of Building and be heard.
Except where there is a City employee inspecting buildings or structures being erected or repaired by the City, no Registered Deputy Inspector shall receive any compensation from the City. A Registered Deputy Inspector shall undertake and perform the duties of inspection solely on the request of the owner or the owner’s agent. The designation shall be deemed to indicate that the duties incident to the inspection are within the course and scope of the Registered Deputy Inspector’s employment by the owner or agent, and except where the Registered Deputy Inspector is in fact an employee of the City, the Registered Deputy Inspector shall not be deemed an employee of the City, a contractor, a subcontractor or a material vendor for any purpose.
The registered design professional in responsible charge and engineers of record involved in the design of the project are permitted to act as the supervising agency and their personnel are permitted to act as the deputy inspector for the work designed by them, provided they qualify as Registered Deputy Inspectors.
1. The Registered Deputy Inspector employed on any work must be present during the execution of all the work the Registered Deputy Inspector has undertaken to inspect. The Registered Deputy Inspector shall notify the Department of the commencement of inspection of a job and shall specify the type of inspection for which the Registered Deputy Inspector has been engaged. This notification shall be made no later than the last working day preceding the commencement of inspection. The Registered Deputy Inspector shall report to the job sufficiently in advance of construction to review the plans and to inspect all materials to be used or concealed within the work, shall inspect the construction, erection, placing or other use of the materials, and shall observe whether there is compliance with the Code as to all of the foregoing. During the execution of the work, the Registered Deputy Inspector shall not undertake or engage in any other task or occupation that will interfere with the proper performance of the Registered Deputy Inspector’s duties relating to the inspections. The Registered Deputy Inspector shall report, as directed, to the Superintendent of Building, noting all violations of this Code that have occurred and any other information as may be required. At the conclusion of the Registered Deputy Inspector’s duties on any project, which has been completed in accordance with this Code, the Registered Deputy Inspector shall submit a report to the Department setting forth the portion of the work inspected. The report shall be made on forms supplied by the Department and shall be filed with the Department. (Amended by Ord. No. 185,587, Eff. 7/16/18.)
2. Nothing here shall be deemed to authorize any Registered Deputy Inspector to approve any inspection required by this Code, other than the special inspection for which the Registered Deputy Inspector was hired and is of the type for which the Registered Deputy Inspector is registered. (Amended by Ord. No. 185,587, Eff. 7/16/18.)
3. Where, in the opinion of the Department, the magnitude or complexity of a job warrants it, additional Registered Deputy Inspectors may be required.
4. Where, in the opinion of the Department, the Registered Deputy Inspector is negligent in the performance of the Deputy Inspector’s duties, the job shall be stopped.
5. Nothing herein shall be deemed to authorize any Registered Deputy Inspector to approve the pouring of concrete, the placement of masonry, structural steel or fill prior to the approval of the regular building inspector.
1. New Application. Before accepting any application for registration as a Registered Deputy Inspector, the Department shall collect a new examination fee of $528. A separate application shall be submitted and a separate examination fee shall be collected for each additional type of registration desired. When the applicant passes the examination(s), a Certificate(s) of Registration for each type of examination passed shall be issued. If the applicant fails to pass an examination, the applicant may reapply and again pay the examination fees. No refund(s) will be given to the applicant after the Department has administered the examination(s).
2. Renewal Application. Before renewing a Certificate of Registration as a Registered Deputy Inspector, the Department shall collect a renewal Registration and examination fee in the amount of $482. A separate application shall be submitted and a separate examination fee shall be collected for each additional type of renewal registration desired. When the applicant passes the examination(s), a Certificate(s) of Registration for each type of examination passed shall be issued. If the applicant fails to pass the examination(s), the applicant may reapply; however, the applicant must again pay the renewal Registration and examination fees before the Department can issue the Certificate of Registration(s). No refund(s) will be given to applicant after the Department has administered the examination.
3. International Code Council (ICC) Certification(s). International Code Council (ICC) Certification(s) is required prior to taking the Department's new or renewal examination(s). In addition to ICC's certification, the Department's examination will be required for each type of registration and fees collected as specified in this Section.
EXCEPTIONS:
If the ICC does not have an examination for a Department registration, the applicant will be required to take the Department examination only.
The ICC Certification may not be required when the Department registration is utilized by the Department of Public Works for City business only.
91.1704.2.3. Statement of Special Inspections. The permit applicant shall submit a statement of special inspections in accordance with LAMC Subsection 91.106.3.3. The statement of special inspections shall be prepared by the registered design professional in responsible charge as a condition for permit issuance. This statement shall be in accordance with LAMC Subsection 91.1704.3.
EXCEPTION:
1. A statement of special inspections is not required for portions of structures designed and constructed in accordance with the cold-formed steel light-frame construction provisions of CBC Section 2211.1.2 or the conventional light-frame construction provisions of LAMC Section 91.2308.
91.1704.2.4. Report Requirement. In addition to all the requirements of LAMC Subsection 91.1704.2.1.1, Registered Deputy Inspectors shall keep records of inspections and tests. The Registered Deputy Inspectors shall furnish inspection reports and tests to the Superintendent of Building, and to the registered design professional in responsible charge. Reports shall indicate that work inspected was or was not completed in conformance to approved construction documents. Discrepancies shall be brought to the immediate attention of the contractor for correction. If they are not corrected, the discrepancies shall be brought to the attention of the Superintendent of Building and to the registered design professional in responsible charge prior to the completion of that phase of the work. A final report documenting required special inspections and tests, and correction of any discrepancies noted in the inspections or tests, shall be submitted at a point in time agreed upon prior to the start of the work by the owner or owner's authorized agent to the Superintendent of Building.
91.1704.2.5. Special Inspection of Fabricated Items. Where fabrication of structural, load-bearing or lateral load resisting members or assemblies is being conducted on the premises of a fabricator's shop, deputy inspections of the fabricated items shall be performed during fabrication, when approved by the Superintendent of Building, except where the fabricator has been approved to perform work without special inspection in accordance with LAMC Subsection 1704.2.5.1.
91.1704.2.5.1. Fabricator Approval. Pursuant to LAMC Section 96.200 et seq., special inspections required by LAMC Section 91.1705 are not required where the work is done on the premises of a fabricator approved to perform such work without special inspection. Approval shall be based upon review of the fabricator’s written fabrication procedures and quality control manuals that provide a basis for control of materials and work quality, with periodic auditing of fabrication and quality control practices by an approved agency or the Superintendent of Building. At completion of fabrication, the approved fabricator shall submit a certificate of compliance to the owner or owner’s authorized agent for submittal to the Superintendent of Building as specified in CBC Section 1704.5 stating that the work was performed in accordance with the approved construction documents.
91.1704.6. Structural Observations. Where required by the provisions of LAMC Subsection 91.1704.6.1, the owner shall employ the registered design professional in responsible charge for the structural design, or another registered design professional designated by the registered design professional in responsible charge of the structural design to perform structural observations as defined in CBC Section 202. The structural observer shall visually observe representative locations of structural systems, details and load paths for general conformance to the approved construction documents.
Prior to the commencement of observations, the structural observer shall submit to the Superintendent of Building a written statement identifying the frequency and extent of proposed structural observations.
The owner or owner's representative shall coordinate and call a preconstruction meeting between the engineer or architect responsible for the structural design, structural observer, contractor, affected subcontractors and deputy inspectors. The structural observer shall preside over the meeting. The purpose of the meeting shall be to identify the major structural elements and connections that affect the vertical and lateral load systems of the structure and to review scheduling of the required observations. A record of the meeting shall be included in the first report submitted to the Superintendent of Building.
Observed deficiencies shall be reported, in writing, to the owner's representative, Registered Deputy Inspector, contractor and the Superintendent of Building. Upon the form prescribed by the Superintendent of Building, the structural observer shall submit to the Superintendent of Building a written statement at each significant construction stage stating that the site visits have been made and identify any reported deficiencies which, to the best of the structural observer's knowledge, have not been resolved. A final report by the structural observer, which states that all observed deficiencies have been resolved, is required before acceptance of the work by the Superintendent of Building.
1. The structure is classified as Risk Category III or IV.
2. The structure is a high-rise building.
3. A lateral design is required for the structure or portion thereof.
EXCEPTION: One-story wood framed Group R-3 and U occupancies less than 2,000 square feet in area, provided the adjacent grade is not steeper than I unit vertical in 10 units horizontal (10% slope), assigned to Seismic Design Category D.
4. Such observation is required by the registered design professional responsible for the structural design.
5. Such observation is specifically required by the building official.
(Amended by Ord. No. 187,719, Eff. 1/23/23.)
Section 1705 of the CBC is adopted by reference, except CBC Sections 1705.3, 1705.3.2, 1705.6, 1705.7, 1705.8, 1705.12.1, 1705.12.1.1, 1705.13.1, 1705.13.4, 1705.16.2, and 1705.17 are not adopted; and, in lieu, LAMC Subsections 91.1705.1.2, 91.1705.1.3, 91.1705.1.4, 91.1705.1.5, 91.1705.1.6, 91.1705.1.7, 91.1705.1.8, 91.1705.1.9, 91.1705.1.10, 91.1705.1.11, 91.1705.1.12, 91.1705.1.13, 91.1705.2.4, 91.1705.3, 91.1705.3.1.1, 91.1705.3.2, 91.1705.6, 91.1705.6.2, 91.1705.7, 91.1705.8, 91.1705.13.1, 91.1705.13.1.1.1, 91.1705.14.1, 91.1705.18.2; and 91.1705.19 are added.
91.1705.1.2. Certifications by Engineer or Geologist. If the grading or foundation earthwork has required continuous inspection, the responsible engineering geologist or soils engineer shall certify by signature to the Department that, to the best of the geologist’s or engineer’s knowledge, the field work was completed in conformity with the technical design data.
91.1705.1.3. Department's Responsibility. The employment of a Registered Deputy Inspector for any work does not deprive the Department of the right to make periodic or called inspections of all or portions of the work. On any work requiring continuous inspection by a Registered Deputy Inspector, the called inspections required by Section 91.108 of this Code may be delegated to the Registered Deputy Inspector by the Superintendent of Building.
91.1705.1.4. Structural, Termite and Fungus Damage. Every building raised from its foundation shall be inspected. If there is any superficial evidence of structural damage, termites or fungus growth, the permittee shall remove and renew the damaged or infested members before reseating the building or moving it from its existing site or into the City.
91.1705.1.5. Emergencies or Catastrophes. In the event of an emergency or of a major catastrophe in the City, the Department may deputize Emergency Building Inspectors for the Department. The inspectors shall receive no compensation from the City, and they shall be appointed for the periods of time the Department deems advisable.
91.1705.1.6. Special Activity Inspection. (Amended by Ord. No. 185,587, Eff. 7/16/18.) In addition to the construction or work inspected as described in LAMC Sections 91.108 and 91.1704 through 91.1705, there are other construction activities that are sufficiently important to the structural stability of the structure, the occupants of and the fire and life safety of the structure that inspection by a specially qualified inspector is necessary in order to ensure compliance with the Code requirements. These special activity inspections may occur during off-site fabrication or during on-site construction.
Inspections by Department Approved Special Activity Inspectors will be required in accordance with regulations promulgated by the Superintendent of Building where:
1. The structure is more than five stories or 60 feet (18,288 mm) in height.
2. The structure exceeds 50,000 square feet (4645 m
2
) of ground area or 200,000 square feet (18 580 m
2
) of total floor area.
3. Nondestructive structural testing methods are utilized.
4. The quality identification markings of the materials used are not inspectable after installation.
5. The manner of use of materials precludes full inspection after installation.
EXCEPTION: The Department may waive continuous or periodic inspection required by this Section where minor quantities are involved and no unusual hazards exist.
In addition to the projects included in the above categories, the Superintendent of Building may require Special Activity inspections if the Superintendent of Building determines that these inspections are needed to ensure compliance with the provisions of this Code and the work involves:
6. Unique, novel or innovative construction;
7. Highly complex or intricate construction;
8. Unique, novel or innovative grading, earth support or foundation procedures; or
9. New methods of construction not yet provided for in the rules and regulations.
Special Activity inspection authority will be determined on a case-by-case basis and will require Registered Deputy Inspector registration. The Superintendent of Building shall adopt rules and regulations implementing the provisions of this Section. These regulations may establish and set the requirements for different types of Department Approved Special Activity Inspectors.
91.1705.1.8. Registration. The procedures and conditions of registration as a Special Activity Inspector shall be the same as applicable to a Registered Deputy Inspector under LAMC Subsection 91.1704.2.1, except that the extent and duration of special inspection authority shall be as specified in the rules and regulations adopted by the Superintendent of Building.
91.1705.1.9. Duties. Except as otherwise indicated by regulations promulgated by the Superintendent of Building, the duties and responsibilities for a Special Activity Inspector shall be the same as specified for a Registered Duty Inspector under LAMC Subsection 91.1704.2.1.1
91.1705.1.10. Fees. The procedures for the examination, registration and renewal of authority as a Special Activity Inspector shall be the same as specified for a Registered Deputy Inspectors under LAMC Subsection 91.1704.2.1.2.
91.1705.1.11. Renewal Process. LAMC Subsection 91.1704.2.1.2 applies to the application, examination and renewal process for registration as a Special Activity Inspector.
91.1705.1.13. The Superintendent of Building shall suspend or revoke any certificate upon evidence of failure of the person so certified to conduct welding operations in compliance with any of the conditions upon which it is based, or where quality of work or workmanship is not equivalent to that required by the Code, or for any of the reasons set forth in Article 8, Chapter IX of the Los Angeles Municipal Code. Any action shall be in accordance with the provisions of Article 8, Chapter IX of the Los Angeles Municipal Code.
91.1705.2.4. Cold-formed Steel Trusses Spanning 60 Feet or Greater. Where a cold-formed steel truss clear span is 60 feet (18 288 mm) or greater, the deputy inspector shall verify that the temporary installation restraint/bracing and the permanent individual truss member restraint/bracing are installed in accordance with the approved truss submittal package. (Amended by Ord. No. 185,198, Eff. 11/22/17.)
EXCEPTION: Special inspections and tests shall not be required for:
1. Isolated spread concrete footings of buildings three stories or less above grade plane that are fully supported on earth or rock, where the structural design of the footing is based on a specified compressive strength, f'c, no greater than 2,500 pounds per square inch (psi) (17.2 MPa).
2. Continuous concrete footings supporting walls of buildings three stories or less above grade plane that are fully supported on earth or rock where:
2.1. The footings support walls of light-frame construction;
2.2. The footings are designed in accordance with LAMC Table 1809.7; or
2.3. The structural design of the footing is based on a specified compressive strength, f'c, not more than 2,500 pounds per square inch (psi) (17.2 MPa), regardless of the compressive strength specified in the approved construction documents or used in the footing construction.
3. Nonstructural concrete slabs supported directly on the ground, including prestressed slabs on grade, where the effective prestress in the concrete is less than 150 psi (1.03 MPa).
4. Concrete foundation walls constructed in accordance with CBC Table 1807.1.6.2.
5. Concrete patios, driveways and sidewalks on grade.
91.1705.3.1.1. Structural Inspection – Concrete. During the construction of all buildings over 160 feet (48.768 m) in height with concrete special moment-resisting space frames, a structural inspector under the supervision of the engineer responsible for the structural design shall be present to inspect the materials and work quality for conformance with approved plans, specifications and change orders involved in construction of the ductile frames and shear walls. This inspection may be made by one or more structural inspectors, provided that at least one structural inspector is present during the placement of all concrete and reinforcement in the structural frame and shear walls.
The number of structural inspectors to be provided for each structure shall be determined by the engineer responsible for the structural design, provided that more than one structural inspector shall be provided where the magnitude of a structure prevents a single inspector from adequately performing the inspection.
The owner shall provide each structural inspector. Each structural inspector shall be paid by the owner directly or through the person responsible for the structural design. Each structural inspector shall be responsible to the person who prepared the structural design.
Prior to the issuance of the Certificate of Occupancy, each structural inspector shall submit a report in writing to the engineer and the Department certifying that the portions of the structural frame inspected by the inspector were constructed in accordance with the approved plans, specifications, change orders and Division 19, Article 1, Chapter IX of the LAMC.
91.1705.3.2. Material Tests. In the absence of sufficient data or documentation providing evidence of conformance to quality standards for materials in Chapters 19 and 20 of ACI 318, the Superintendent of Building shall require testing of materials in accordance with the appropriate standards and criteria for the material in Chapters 19 and 20 of ACI 318. Weldability of reinforcement, except that which conforms to ASTM A706, shall be determined in accordance with the requirements of Section 26.6.4 of ACI 318.
91.1705.6. Soils. Special inspections defined per LAMC Subsections 91.7008.2 and 91.7011.3 and tests for existing site soil conditions, fill placement and load-bearing requirements shall be as required by this section and LAMC Table 1705.6. The approved geotechnical report, and the construction documents prepared by the registered design professionals shall be used to determine compliance. During fill placement, the special inspector shall determine that proper materials and procedures are used in accordance with the provisions of the approved geotechnical report, as specified in CBC Section 1803.6.
EXCEPTION: Special inspection is not required during placement of controlled fill having a total depth of 12 inches (305 mm) or less and where the fill is not used for graded slopes or for support of footings or foundations.
1.1. A contiguous grading area exceeding 60,000 square feet (5574 m
2
).
1.2. An excavated or filled slope steeper than 2 horizontal in 1 vertical (50% slope). (Amended by Ord. No. 185,587, Eff. 7/16/18.)
1.3. An excavated slope exceeding 40 feet (12,192 mm) in height and the top of which is within 20 feet (6096 mm) of a property line coterminous with improved private property or a public way.
1.4. Foundation excavations below a 1 horizontal in 1 vertical plane inward and down from the property line.
EXCEPTION: The Department may waive continuous inspection where minor areas or heights are involved and no unusual hazards exist. (Amended by Ord. No. 185,587, Eff. 7/16/18.)
VERIFICATION AND INSPECTION TASK | CONTINUOUS DURING TASK LISTED | PERIODICALLY DURING TASK LISTED |
1. Verify materials below shallow foundations are adequate to achieve the design bearing capacity. | – | X |
2. Verify excavations are extended to proper depth and have reached proper material. | – | X |
3. Perform classification and testing of compacted fill materials. | – | X |
4. Verify use of proper materials, densities and lift thicknesses during placement and compaction of compacted fill. | X
a | – |
5. Prior to placement of compacted fill, observe subgrade and verify that site has been prepared properly. | – | X |
a. Frequency of special inspections to be determined by the registered design professional responsible for the project. |
91.1705.7. Driven Deep Foundations and Connecting Grade Beams. Special inspections and tests shall be performed during installation and testing of the driven deep foundation elements as specified by CBC Table 1705.7. The approved geotechnical report, required by CBC Section 1803.6 and the construction documents prepared by the registered design professionals shall be used to determine compliance. Special inspections for connecting grade beams shall be in accordance with LAMC Section 91.1705.3.
91.1705.8. Cast-in-Place Deep Foundations and Connecting Grade Beams. Special inspections and tests shall be performed during installation and testing of cast-in-place deep foundation elements as specified by CBC Table 1705.8. The approved geotechnical report, required by CBC Section 1803.6 and the construction documents prepared by the registered design professionals shall be used to determine compliance. Special inspections for connecting grade beams shall be in accordance with LAMC Section 91.1705.3.
91.1705.13.1. Structural Steel. Special inspection for seismic resistance shall be in accordance with CBC Section 1705.13.1.1 or 1705.13.1.2, as applicable and during the fabrication and erection of buildings over 160 feet (48,768 mm) in height with structural steel moment resisting frames. A registered deputy inspector shall be present during the performance of all structural welding or the installation of all high-strength bolts whether in a fabricator's shop or at the job site.
EXCEPTIONS:
1. Single-pass fillet welds not exceeding 5/16-inch (7.9 mm) in size.
2. Floor and roof deck welding.
91.1705.13.1.1.1. Certification. For buildings exceeding 160 feet (48,768 mm) in height, the engineer responsible for the structural design and the general contractor responsible for the construction, or their competent authorized representatives, shall make periodic inspections of the work at the site to verify general compliance with the approved plans, specifications and change orders. The engineer and general contractor shall submit a statement in writing to the Department stating that they know from personal knowledge that the materials installed and the structural work performed is in compliance with the approved plans, specifications and change orders.
The phrase "personal knowledge" as used above in reference to the engineer and general contractor means the knowledge resulting from the general observation by the engineer and the general supervision by the contractor of the work, as required by both in the superintendence of the building's construction, and as distinguished from the continuous personal superintendence of the special inspector and/or deputy inspector who are continuously at the site during the progress of the work. The exercise of reasonable diligence to obtain the facts is required and anyone who intentionally remains unaware may be charged with knowledge. The interpretation of personal knowledge as it applies to the special inspector and/or deputy inspector is that the inspector(s) must have actual personal knowledge that the requirements of the plans and specifications are being carried out, which is obtained by the inspector's continuous observation of the work of construction at the site in all stages of its progress.
EXCEPTION: Special inspections of structural steel in structures assigned to Seismic Design Category C that are not specifically detailed for seismic resistance, with a response modification coefficient, R, of 3 or less, excluding cantilever column systems.
91.1705.14.1. Structural Steel. Testing for structural steel shall be in accordance with the quality assurance requirements of AISC 341 and the additional requirements in this Section. Nondestructive testing shall be performed by an approved agency and the written report, including the test results, shall be submitted for evaluation by the Superintendent of Building. The acceptance criteria for nondestructive testing shall be as required in AWS D1.1 as specified by the registered design professional.
Base metal thicker than 1.5 inches (38 mm), where subject to through-thickness weld shrinkage strains, shall be ultrasonically tested for discontinuities behind and adjacent to those welds after joint completion. Any material discontinuities shall be accepted or rejected on the basis of ASTM A 435 or ASTM A 898 (Level 1 criteria) and criteria as established by the registered design professional(s) in responsible charge, and the construction documents.
(Added by Ord. No. 182,850, Eff. 1/3/14.)
Section 1706 of the CBC is adopted by reference, except Section 1706.1 of the CBC is not adopted; and, in lieu, LAMC Subsection 91.1706.1 is added. (Amended by Ord. No. 185,587, Eff. 7/16/18.)
91.1706.1. Conformance to Standards. The design strengths and permissible stresses of any structural material that are identified by a manufacturer's designation as to manufacture and grade by mill tests, or the strength and stress grade is otherwise confirmed to the satisfaction of the Superintendent of Building shall conform to the specifications and methods of design of accepted engineering practice or the approved rules in the absence of applicable standards.
(Amended by Ord. No. 184,692, Eff. 12/30/16.)
91.1710.1. General. (Amended by Ord. No. 185,587, Eff. 7/16/18.) A certified security bar installer may certify to the Department that any bars, grilles, grates, security roll-down shutters, or similar devices installed on required emergency escape windows or doors meet the requirements of LAMC Subsection 91.6304.3.
The Department may allow the use of a certified installer if:
1. The certified installer obtains a Certificate of Registration in accordance with the provisions of this section.
2. The certified installer files with the Department a Certificate of Compliance for each dwelling unit for which certification is being made. The Certificate of Compliance shall be on a form provided by the Department and shall be signed by the property owner and the certified installer.
3. The Certificate of Compliance processing fee is paid in accordance with LAMC Subsection 91.107.7.
4. The certified installer files the Certificate of Compliance with the Department within 15 days after completion of the installation.
91.1710.4.1. Examination Required. Before any person shall be issued a Certificate of Registration, the applicant, who must be an officer in the case of a firm, partnership or corporation, shall have successfully passed the examination required for the issuance of the certificate within ninety (90) days preceding the date of the issuance.
The results of every examination shall be subject to the approval of the Superintendent.
Each examiner shall serve at the pleasure of the Superintendent of Building and shall serve for a period of one year unless reappointed by the Superintendent of Building.
91.1710.4.4. Scope of Examination. (Amended by Ord. No. 185,587, Eff. 7/16/18.) The examination shall, in the judgment of the Board of Examiners, fairly determine the ability of the applicant to properly perform the work, which the applicant would be authorized to do by the certificate requested, and may include the following:
1. A written test.
2. Practical tests as may be required.
3. An oral interview as may be required.
4. Other tests as may be required by the Board of Examiners.
91.1710.4.8. Failure to Pass. Every applicant who fails to pass an examination shall not be eligible for another examination until four (4) weeks after taking the previous examination. Any applicant who fails to pass on the third try shall not be eligible again until six (6) months after taking the previous examination.
91.1710.5.2. Renewal of Certificates. (Amended by Ord. No. 185,587, Eff. 7/16/18.) Expired certificates may be renewed at any time within twelve (12) months following the date of expiration. However, after the first month, the renewal fee shall be increased by 10% for each subsequent month. After a certificate has been expired for one year, it may not be renewed; however, an applicant may apply for a new certificate at that time.
91.1710.7. Revocation of Certificate. (Amended by Ord. No. 185,587, Eff. 7/16/18.) Any certificate may be suspended or revoked in accordance with the provisions of Article 8, Chapter IX of the LAMC.
Loading...