Skip to code content (skip section selection)
Compare to:
Los Angeles Overview
Los Angeles Charter and Administrative Code
Los Angeles Municipal Code
MUNICIPAL CODE
FOREWORD
CHAPTER I GENERAL PROVISIONS AND ZONING
CHAPTER 1A CITY OF LOS ANGELES ZONING CODE
CHAPTER II* LICENSES, PERMITS, BUSINESS REGULATIONS
CHAPTER III PUBLIC HEALTH CODE
CHAPTER IV PUBLIC WELFARE
CHAPTER V PUBLIC SAFETY AND PROTECTION
CHAPTER VI PUBLIC WORKS AND PROPERTY
CHAPTER VII TRANSPORTATION
CHAPTER VIII TRAFFIC
CHAPTER IX BUILDING REGULATIONS
ARTICLE 1 BUILDINGS [BUILDING CODE]
DIVISION 1 ADMINISTRATION
DIVISION 2 DEFINITIONS AND ABBREVIATIONS
DIVISION 3 USE OR OCCUPANCY
DIVISION 4 SPECIAL USE AND OCCUPANCY
DIVISION 5 GENERAL BUILDING HEIGHTS AND AREAS
DIVISION 6 TYPES OF CONSTRUCTION
DIVISION 7 FIRE-RESISTANT MATERIALS AND CONSTRUCTION
DIVISION 8 INTERIOR FINISHES
DIVISION 9 FIRE-PROTECTION SYSTEMS
DIVISION 10 MEANS OF EGRESS
DIVISION 11 ACCESSIBILITY
DIVISION 12 INTERIOR ENVIRONMENT
DIVISION 13 ENERGY CONSERVATION
DIVISION 14 EXTERIOR WALL COVERINGS
DIVISION 15 ROOFS AND ROOF STRUCTURES
DIVISION 16 STRUCTURAL DESIGN
DIVISION 17 STRUCTURAL TESTS AND SPECIAL INSPECTIONS
DIVISION 18 SOILS AND FOUNDATIONS
DIVISION 19 CONCRETE
DIVISION 20 ALUMINUM
DIVISION 21 MASONRY
DIVISION 22 STEEL
DIVISION 23 WOOD
DIVISION 24 GLASS AND GLAZING
DIVISION 25 GYPSUM BOARD AND PLASTER
DIVISION 26 PLASTIC
DIVISION 27 ELECTRICAL SYSTEMS
DIVISION 28 MECHANICAL SYSTEMS
DIVISION 29 PLUMBING SYSTEMS
DIVISION 30 ELEVATORS AND CONVEYING SYSTEMS
DIVISION 31 SPECIAL CONSTRUCTION
DIVISION 32 ENCROACHMENTS INTO THE PUBLIC RIGHT-OF-WAY
DIVISION 33 SAFEGUARDS DURING CONSTRUCTION
DIVISION 34 EXISTING STRUCTURES
DIVISION 35 REFERENCED STANDARDS
DIVISION 61 SPECIAL HAZARD AREAS
DIVISION 62 SIGNS
DIVISION 63 ADDITIONAL PROVISIONS FOR SPECIFIC USES
DIVISION 67 SECURITY PROVISIONS
DIVISION 70 GRADING, EXCAVATIONS AND FILLS
DIVISION 71 METHANE SEEPAGE REGULATIONS
DIVISION 72 FIRE DISTRICT REGULATIONS
DIVISION 81 EXISTING BUILDINGS AND STRUCTURES - GENERAL REQUIREMENTS
DIVISION 82 CHANGE OF OCCUPANCY, USE AND RATING CLASSIFICATION
DIVISION 83 RELOCATION PERMIT
DIVISION 85 ALTERNATIVE BUILDING STANDARDS FOR JOINT LIVING AND WORK QUARTERS
DIVISION 86 SPECIAL PROVISIONS FOR EXISTING BUILDINGS
DIVISION 88 EARTHQUAKE HAZARD REDUCTION IN EXISTING BUILDINGS
DIVISION 89 ABATEMENT OF BUILDINGS, STRUCTURES, PREMISES AND PORTIONS THEREOF WHICH CONSTITUTE A NUISANCE OR ARE HAZARDOUS, OR SUBSTANDARD
DIVISION 90 NUISANCE ABATEMENT AND DISCONTINUANCE OF LAND USE AND DISCRETIONARY ZONING APPROVALS; RELOCATION ASSISTANCE; ENFORCEMENT
DIVISION 91 EARTHQUAKE HAZARD REDUCTION IN EXISTING TILT-UP CONCRETE WALL BUILDINGS
DIVISION 92 VOLUNTARY - EARTHQUAKE HAZARD REDUCTION IN EXISTING WOOD FRAME RESIDENTIAL BUILDINGS WITH WEAK CRIPPLE WALLS AND UNBOLTED SILL PLATES
DIVISION 93 MANDATORY EARTHQUAKE HAZARD REDUCTION IN EXISTING WOOD-FRAME BUILDINGS WITH SOFT, WEAK OR OPEN-FRONT WALLS
DIVISION 94 VOLUNTARY - EARTHQUAKE HAZARD REDUCTION IN EXISTING HILLSIDE BUILDINGS
DIVISION 95 MANDATORY EARTHQUAKE HAZARD REDUCTION IN EXISTING NON-DUCTILE CONCRETE BUILDINGS
DIVISION 96 VOLUNTARY - EARTHQUAKE HAZARD REDUCTION IN EXISTING REINFORCED CONCRETE AND REINFORCED MASONRY WALL BUILDINGS WITH FLEXIBLE DIAPHRAGMS
DIVISION 97 EXISTING BUILDINGS ENERGY AND WATER EFFICIENCY PROGRAM
ARTICLE 1.2 EXISTING BUILDING CODE
ARTICLE 1.5 LOS ANGELES RESIDENTIAL CODE
ARTICLE 2 ELEVATOR CODE
ARTICLE 3 ELECTRICAL CODE
ARTICLE 4 PLUMBING CODE
ARTICLE 5 MECHANICAL CODE
ARTICLE 6 MISCELLANEOUS
ARTICLE 7 BOILERS, UNFIRED PRESSURE VESSELS AND OTHER EQUIPMENT
ARTICLE 8 GENERAL ADMINISTRATIVE PROVISIONS
ARTICLE 9 GREEN BUILDING CODE
CHAPTER X BUSINESS REGULATIONS
CHAPTER XI NOISE REGULATION
CHAPTER XII THE WATER CONSERVATION PLAN OF THE CITY OF LOS ANGELES
CHAPTER XIII THE EMERGENCY ENERGY CURTAILMENT PLAN OF THE CITY OF LOS ANGELES
CHAPTER XV RENT STABILIZATION ORDINANCE
CHAPTER XVI HOUSING REGULATIONS
CHAPTER XVII RULES AND REGULATIONS GOVERNING THE USE OF THE LOS ANGELES AIRPORTS
CHAPTER XVIII EMPLOYEE WAGES AND PROTECTIONS
CHAPTER XIX ENVIRONMENTAL PROTECTION
CHAPTER XX COVID-19 PROTECTION AND RECOVERY*
TABLES
Los Angeles Planning and Zoning
Chapter 1A City of Los Angeles Zoning Code
Table of Amending Legislation for Chapter 1A
Loading...
SEC. 91.9604. ANALYSIS AND DESIGN.
   (Added by Ord. No. 171,261, Eff. 8/30/96.)
 
91.9604.1. Wall Panel Anchorage. (Amended by Ord. No. 181,758, Eff. 8/8/11.) Concrete and masonry walls shall be anchored to all floors and roofs which provide lateral support for the wall. The anchorage shall provide a positive direct connection between the wall and floor or roof construction capable of resisting a horizontal force equal to 30 percent of the tributary wall weight for all buildings, and 45 percent of the tributary wall weight for essential buildings, or a minimum force of 250 pounds per linear foot of wall, whichever is greater.
 
   EXCEPTION: Using 75% of the design force as specified in Section 12.11 of ASCE 7 and completely complying with all the requirements as specified in Section 12.11 of ASCE 7 is considered equivalent to the requirements specified in this LAMC section and LAMC Subsection 91.9604.2. (Amended by Ord. No. 185,587, Eff. 7/16/18.)
 
   The required anchorage shall be based on the tributary wall panel assuming simple supports at floors and roof.
 
   EXCEPTION: An alternate design may be approved by the Superintendent of Building when justified by well established principles of mechanics.
 
91.9604.2. Special Requirements for Wall Anchors and Continuity Ties. (Amended by Ord. No. 186,488, Eff. 12/27/19.) The steel elements of the wall anchorage systems and continuity ties shall be designed by the allowable stress design method using a load factor of 1.7. The 1/3 stress increase permitted by CBC Section 1605.3.1.1 shall not be permitted for materials using allowable stress design methods.
 
   The strength design shall be per Section 17.2.3 of ACI 318-14, unless modified by CBC Section 1905.1.8.
 
   Wall anchors shall be provided to resist out-of-plane forces, independent of existing shear anchors.
 
   EXCEPTION: Existing cast-in-place shear anchors may be used as wall anchors if the tie element can be readily attached to the anchors and if the engineer or architect can establish tension values for the existing anchors through the use of approved as-built plans or testing, and through analysis showing that the bolts are capable of resisting the total shear load while being acted upon by the maximum tension force due to seismic loading. Criteria for analysis and testing shall be determined by the Superintendent of Building.
 
   Expansion anchors are not allowed without special approval of the Superintendent of Building. Attaching the edge of plywood sheathing to steel ledgers is not considered as complying with the positive anchoring requirements of the Code; and attaching the edge of steel decks to steel ledgers is not considered as providing the positive anchorage of this Code unless testing and analysis are performed, which establish shear values for the attachment perpendicular to the edge of the deck.
 
91.9604.3. Development of Anchor Loads into the Diaphragm. (Amended by Ord. No. 182,850, Eff. 1/3/14.) Development of anchor loads into roof and floor diaphragms shall comply with Section 12.11 of ASCE 7.
 
   EXCEPTION: If continuously tied girders are present, then the maximum spacing of the continuity ties is the greater of the girder spacing or 24 feet (7315 mm).
 
   In wood diaphragms, anchorage shall not be accomplished by use of toe nails or nails subject to withdrawal, nor shall wood ledgers, top plates or framing be used in cross-grain bending or cross-grain tension. The continuous ties required by LAMC Subsection 91.1613.5.3 and Section 12.11 of ASCE 7 shall be in addition to the diaphragm sheathing. (Amended by Ord. No. 185,587, Eff. 7/16/18.)
 
   Lengths of development of anchor loads in wood diaphragms shall be based on existing field nailing of the sheathing unless existing edge nailing is positively identified on the original construction plans or at the site.
 
   At reentrant corners, continuity collectors may be required for existing return walls not designed as shear walls, to develop into the diaphragm a force equal to the lesser of the rocking or shear capacity of the return wall, or the tributary shear but not exceeding the capacity of the diaphragm. Shear anchors for the return wall shall be commensurate with the collector force. If a truss or beam other than rafters or purlins is supported by the return wall or by a column integral with the return wall, an independent secondary column is required to support the roof or floor members whenever rocking or shear capacity of the return wall is governing.
 
91.9604.4. Anchorage at Pilasters. (Amended by Ord. No. 185,587, Eff. 7/16/18.) Anchorage of pilasters shall be designed for the tributary wall anchoring load per LAMC Subsection 91.9604.1, considering the wall as a two-way slab. The edge of the two-way slab shall be considered "fixed" when there is continuity at pilasters, and considered "pinned" at roof or floor levels. The pilasters or the walls immediately adjacent to the pilasters shall be anchored directly to the roof framing such that the existing vertical anchor bolts at the top of the pilasters are by-passed without causing tension or shear failure at the top of the pilasters.
 
   EXCEPTION: If existing vertical anchor bolts at the top of the pilasters are used for the anchorage, then additional exterior confinement shall be provided.
 
   The minimum anchorage at a floor or roof between the pilasters shall be that specified in LAMC Subsection 91.9604.1.
 
91.9604.5. Symmetry. Symmetry of connectors in the anchorage system is required. Eccentricity may be allowed when it can be shown that all components of forces are positively resisted and justified by calculations or tests.
 
91.9604.6. Minimum Roof Member Size. (Amended by Ord. No. 185,587, Eff. 7/16/18.) Wood members used to develop anchorage forces to the diaphragm shall be of minimum three-inch nominal width for new construction and replacement. All such members must be designed for gravity and earthquake forces as part of the wall anchorage system. For existing structural members, the allowable stresses shall be without the 1/3 stress increase per LAMC Subsection 91.9604.2.
 
91.9604.7. Combination of Anchor Types. To repair and retrofit existing buildings, a combination of different anchor types of different behavior or stiffness shall not be permitted. The capacity of the new and existing connectors cannot be added.
 
91.9604.8. Prohibited Anchors. Usage of connectors that were bent or stretched from the intended use shall be prohibited.
 
91.9604.9. Crack and Damage Repairs, Evaluation of Existing Structural Alterations. The engineer or architect shall report any observed structural conditions and structural damage that have imminent life safety effects on the buildings and recommend repairs. This includes alterations such as openings cut in existing wall panels without a building permit. Evaluations and repairs shall be reviewed and approved by the Department.
 
91.9604.10. Miscellaneous. (Amended by Ord. No. 185,587, Eff. 7/16/18.) Existing mezzanines relying on the concrete or masonry walls for vertical or lateral support shall be anchored to the walls for the tributary mezzanine load. Walls depending on the mezzanine for lateral support shall be anchored per LAMC Subsections 91.9604.1, 91.9604.2 and 91.9604.3.
 
   EXCEPTION: Existing mezzanines that have independent lateral and vertical support need not be anchored to the concrete or masonry walls.
 
   Existing interior masonry or concrete walls not designed as shear walls, which extend to the floor above or to the roof diaphragm shall also be anchored for out-of-plane forces per LAMC Subsections 91.9604.1, 91.9604.2 and 91.9604.3. In the in-plane direction, the walls may be isolated or shall be developed into the diaphragm for a lateral force equal to the lesser of the rocking or shear capacity of the wall, or the tributary shear but not exceeding the diaphragm capacity.
 
91.9604.11. Historical Buildings. (Amended by Ord. No. 185,587, Eff. 7/16/18.) Qualified historical buildings shall be permitted to use alternate building standards or deviations from this division in order to preserve their original or restored architectural elements and features. See LAMC Section 91.2.1200 for these alternatives.
 
 
SEC. 91.9605. MATERIALS OF CONSTRUCTION.
   (Amended by Ord. No. 185,587, Eff. 7/16/18.)
 
   All materials permitted by this Code, including their appropriate allowable stresses and those existing configurations of materials specified in Division 88, Article 1, Chapter IX of the LAMC, may be utilized to meet the requirements of this division.
 
 
SEC. 91.9606. INFORMATION REQUIRED ON PLANS.
   (Added by Ord. No. 171,261, Eff. 8/30/96.)
 
91.9606.1. General. In addition to the seismic analysis required elsewhere in this division, the licensed engineer or architect responsible for the seismic analysis of the building shall record the information required by this section on the approved plans.
 
91.9606.2. Information Required. The plans shall accurately reflect the results of the engineering investigation and design and show all pertinent dimensions and sizes for plan review and construction. The following shall be provided:
 
   1.   Floor plans and roof plans shall show the existing framing construction, diaphragm construction, proposed wall anchors, cross-ties and collectors. Existing nailing, anchors, ties and collectors shall also be shown on the plans if these are part of the design, and these structural elements need to be verified in the field.
 
   2.   At elevations where there is alterations or damage, the details shall show the roof and floor heights, dimensions of openings, location and extent of existing damage, and proposed repair.
 
   3.   Typical concrete or masonry wall sections with wall thickness, height, and location of anchors shall be provided.
 
   4.   Details shall include the existing and new anchors and the method of development of anchor forces into the diaphragm framing; existing and new cross-ties, existing and new or improved support of the roof and floor girders at pilasters or walls.
 
91.9606.3. Engineer’s or Architect’s Statement. (Amended by Ord. No. 185,587, Eff. 7/16/18.) The responsible engineer or architect shall state on the approved plans, the following:
 
   1.   "I am responsible for this building's seismic strengthening design of the tilt-up concrete wall anchorage system in compliance with the minimum seismic resistance standards of Division 96, Article 1, Chapter IX of the LAMC."
 
or when applicable:
 
   2.   "The Registered Deputy Inspector, required as a condition of the use of structural design stresses requiring continuous inspection, will be responsible to me as required by LAMC Section 91.1704."
 
 
 
DIVISION 97
EXISTING BUILDINGS ENERGY AND WATER EFFICIENCY PROGRAM
 
(Division 97 Added by Ord. No. 184,674, Eff. 1/29/17.)
 
 
Section
91.9701   Title.
91.9702   Purpose.
91.9703   Scope.
91.9704   Definitions.
91.9705   Benchmarking and Self-Reporting of Energy and Water Consumption Information.
91.9706   Energy and Water Audits and Retro-Commissioning.
91.9707   Record Maintenance.
91.9708   Schedule for Compliance.
91.9709   Noncompliance Fee.
91.9710   Submittal Fees.
91.9711   Building and Safety Development Surcharge.
91.9712   Severability.
 
 
SEC. 91.9701. TITLE.
   (Added by Ord. No. 184,674, Eff. 1/29/17.)
 
   This division shall be known as the City of Los Angeles Existing Buildings Energy and Water Efficiency (EBEWE) Program.
 
 
SEC. 91.9702. PURPOSE.
   (Added by Ord. No. 184,674, Eff. 1/29/17.)
 
   It is the purpose of this division to reduce energy and water consumption in buildings, including existing buildings, in the City of Los Angeles. These efficiency improvements will lower the use of energy, water, and greenhouse gas emissions citywide.
 
 
Loading...