Loading...
(Added by Ord. No. 171,261, Eff. 8/30/96.)
91.9604.1. Wall Panel Anchorage. (Amended by Ord. No. 181,758, Eff. 8/8/11.) Concrete and masonry walls shall be anchored to all floors and roofs which provide lateral support for the wall. The anchorage shall provide a positive direct connection between the wall and floor or roof construction capable of resisting a horizontal force equal to 30 percent of the tributary wall weight for all buildings, and 45 percent of the tributary wall weight for essential buildings, or a minimum force of 250 pounds per linear foot of wall, whichever is greater.
EXCEPTION: Using 75% of the design force as specified in Section 12.11 of ASCE 7 and completely complying with all the requirements as specified in Section 12.11 of ASCE 7 is considered equivalent to the requirements specified in this LAMC section and LAMC Subsection 91.9604.2. (Amended by Ord. No. 185,587, Eff. 7/16/18.)
The required anchorage shall be based on the tributary wall panel assuming simple supports at floors and roof.
EXCEPTION: An alternate design may be approved by the Superintendent of Building when justified by well established principles of mechanics.
91.9604.2. Special Requirements for Wall Anchors and Continuity Ties. (Amended by Ord. No. 186,488, Eff. 12/27/19.) The steel elements of the wall anchorage systems and continuity ties shall be designed by the allowable stress design method using a load factor of 1.7. The 1/3 stress increase permitted by CBC Section 1605.3.1.1 shall not be permitted for materials using allowable stress design methods.
The strength design shall be per Section 17.2.3 of ACI 318-14, unless modified by CBC Section 1905.1.8.
Wall anchors shall be provided to resist out-of-plane forces, independent of existing shear anchors.
EXCEPTION: Existing cast-in-place shear anchors may be used as wall anchors if the tie element can be readily attached to the anchors and if the engineer or architect can establish tension values for the existing anchors through the use of approved as-built plans or testing, and through analysis showing that the bolts are capable of resisting the total shear load while being acted upon by the maximum tension force due to seismic loading. Criteria for analysis and testing shall be determined by the Superintendent of Building.
Expansion anchors are not allowed without special approval of the Superintendent of Building. Attaching the edge of plywood sheathing to steel ledgers is not considered as complying with the positive anchoring requirements of the Code; and attaching the edge of steel decks to steel ledgers is not considered as providing the positive anchorage of this Code unless testing and analysis are performed, which establish shear values for the attachment perpendicular to the edge of the deck.
EXCEPTION: If continuously tied girders are present, then the maximum spacing of the continuity ties is the greater of the girder spacing or 24 feet (7315 mm).
In wood diaphragms, anchorage shall not be accomplished by use of toe nails or nails subject to withdrawal, nor shall wood ledgers, top plates or framing be used in cross-grain bending or cross-grain tension. The continuous ties required by LAMC Subsection 91.1613.5.3 and Section 12.11 of ASCE 7 shall be in addition to the diaphragm sheathing. (Amended by Ord. No. 185,587, Eff. 7/16/18.)
Lengths of development of anchor loads in wood diaphragms shall be based on existing field nailing of the sheathing unless existing edge nailing is positively identified on the original construction plans or at the site.
At reentrant corners, continuity collectors may be required for existing return walls not designed as shear walls, to develop into the diaphragm a force equal to the lesser of the rocking or shear capacity of the return wall, or the tributary shear but not exceeding the capacity of the diaphragm. Shear anchors for the return wall shall be commensurate with the collector force. If a truss or beam other than rafters or purlins is supported by the return wall or by a column integral with the return wall, an independent secondary column is required to support the roof or floor members whenever rocking or shear capacity of the return wall is governing.
91.9604.4. Anchorage at Pilasters. (Amended by Ord. No. 185,587, Eff. 7/16/18.) Anchorage of pilasters shall be designed for the tributary wall anchoring load per LAMC Subsection 91.9604.1, considering the wall as a two-way slab. The edge of the two-way slab shall be considered "fixed" when there is continuity at pilasters, and considered "pinned" at roof or floor levels. The pilasters or the walls immediately adjacent to the pilasters shall be anchored directly to the roof framing such that the existing vertical anchor bolts at the top of the pilasters are by-passed without causing tension or shear failure at the top of the pilasters.
EXCEPTION: If existing vertical anchor bolts at the top of the pilasters are used for the anchorage, then additional exterior confinement shall be provided.
The minimum anchorage at a floor or roof between the pilasters shall be that specified in LAMC Subsection 91.9604.1.
91.9604.5. Symmetry. Symmetry of connectors in the anchorage system is required. Eccentricity may be allowed when it can be shown that all components of forces are positively resisted and justified by calculations or tests.
91.9604.6. Minimum Roof Member Size. (Amended by Ord. No. 185,587, Eff. 7/16/18.) Wood members used to develop anchorage forces to the diaphragm shall be of minimum three-inch nominal width for new construction and replacement. All such members must be designed for gravity and earthquake forces as part of the wall anchorage system. For existing structural members, the allowable stresses shall be without the 1/3 stress increase per LAMC Subsection 91.9604.2.
91.9604.7. Combination of Anchor Types. To repair and retrofit existing buildings, a combination of different anchor types of different behavior or stiffness shall not be permitted. The capacity of the new and existing connectors cannot be added.
91.9604.8. Prohibited Anchors. Usage of connectors that were bent or stretched from the intended use shall be prohibited.
91.9604.9. Crack and Damage Repairs, Evaluation of Existing Structural Alterations. The engineer or architect shall report any observed structural conditions and structural damage that have imminent life safety effects on the buildings and recommend repairs. This includes alterations such as openings cut in existing wall panels without a building permit. Evaluations and repairs shall be reviewed and approved by the Department.
91.9604.10. Miscellaneous. (Amended by Ord. No. 185,587, Eff. 7/16/18.) Existing mezzanines relying on the concrete or masonry walls for vertical or lateral support shall be anchored to the walls for the tributary mezzanine load. Walls depending on the mezzanine for lateral support shall be anchored per LAMC Subsections 91.9604.1, 91.9604.2 and 91.9604.3.
EXCEPTION: Existing mezzanines that have independent lateral and vertical support need not be anchored to the concrete or masonry walls.
Existing interior masonry or concrete walls not designed as shear walls, which extend to the floor above or to the roof diaphragm shall also be anchored for out-of-plane forces per LAMC Subsections 91.9604.1, 91.9604.2 and 91.9604.3. In the in-plane direction, the walls may be isolated or shall be developed into the diaphragm for a lateral force equal to the lesser of the rocking or shear capacity of the wall, or the tributary shear but not exceeding the diaphragm capacity.
91.9604.11. Historical Buildings. (Amended by Ord. No. 185,587, Eff. 7/16/18.) Qualified historical buildings shall be permitted to use alternate building standards or deviations from this division in order to preserve their original or restored architectural elements and features. See LAMC Section 91.2.1200 for these alternatives.
(Amended by Ord. No. 185,587, Eff. 7/16/18.)
All materials permitted by this Code, including their appropriate allowable stresses and those existing configurations of materials specified in Division 88, Article 1, Chapter IX of the LAMC, may be utilized to meet the requirements of this division.
(Added by Ord. No. 171,261, Eff. 8/30/96.)
91.9606.1. General. In addition to the seismic analysis required elsewhere in this division, the licensed engineer or architect responsible for the seismic analysis of the building shall record the information required by this section on the approved plans.
91.9606.2. Information Required. The plans shall accurately reflect the results of the engineering investigation and design and show all pertinent dimensions and sizes for plan review and construction. The following shall be provided:
1. Floor plans and roof plans shall show the existing framing construction, diaphragm construction, proposed wall anchors, cross-ties and collectors. Existing nailing, anchors, ties and collectors shall also be shown on the plans if these are part of the design, and these structural elements need to be verified in the field.
2. At elevations where there is alterations or damage, the details shall show the roof and floor heights, dimensions of openings, location and extent of existing damage, and proposed repair.
3. Typical concrete or masonry wall sections with wall thickness, height, and location of anchors shall be provided.
4. Details shall include the existing and new anchors and the method of development of anchor forces into the diaphragm framing; existing and new cross-ties, existing and new or improved support of the roof and floor girders at pilasters or walls.
91.9606.3. Engineer’s or Architect’s Statement. (Amended by Ord. No. 185,587, Eff. 7/16/18.) The responsible engineer or architect shall state on the approved plans, the following:
1. "I am responsible for this building's seismic strengthening design of the tilt-up concrete wall anchorage system in compliance with the minimum seismic resistance standards of Division 96, Article 1, Chapter IX of the LAMC."
or when applicable:
2. "The Registered Deputy Inspector, required as a condition of the use of structural design stresses requiring continuous inspection, will be responsible to me as required by LAMC Section 91.1704."
(Division 97 Added by Ord. No. 184,674, Eff. 1/29/17.)
Section
91.9701 Title.
91.9702 Purpose.
91.9703 Scope.
91.9704 Definitions.
91.9705 Benchmarking and Self-Reporting of Energy and Water Consumption Information.
91.9706 Energy and Water Audits and Retro-Commissioning.
91.9707 Record Maintenance.
91.9708 Schedule for Compliance.
91.9709 Noncompliance Fee.
91.9710 Submittal Fees.
91.9711 Building and Safety Development Surcharge.
91.9712 Severability.
(Added by Ord. No. 184,674, Eff. 1/29/17.)
It is the purpose of this division to reduce energy and water consumption in buildings, including existing buildings, in the City of Los Angeles. These efficiency improvements will lower the use of energy, water, and greenhouse gas emissions citywide.
Loading...