SEC. 91.2600. BASIC PROVISIONS.
 
   Chapter 26 of the CBC is hereby adopted by reference.
 
 
 
DIVISION 27
ELECTRICAL SYSTEMS
 
(Division Amended by Ord. No. 181,758, Eff. 8/8/11.)
 
 
Section
91.2700   Basic Provisions.
 
 
SEC. 91.2700. BASIC PROVISIONS.
   (Amended by Ord. No. 187,719, Eff. 1/23/23.)
 
   Chapter 27 of the CBC is hereby adopted by reference, except that Los Angeles Municipal Code Subsections 91.2702.2.11.1, 91.2702.2.16.1, and 91.2702.2.19.1 are added.
 
91.2702.2.11.1. Fuel Supply. An on-premises fuel supply, sufficient for not less than 6-hour full-load operation of the emergency and standby power source(s), shall be provided. This fuel supply shall not be less than 8-hour when the load also includes fire pump(s).
 
91.2702.2.16.1. Fuel Supply. An on-premises fuel supply, sufficient for not less than 6-hour full-load operation of the emergency and standby power source(s), shall be provided. This fuel supply shall not be less than 8-hour when the load also includes fire pump(s).
 
91.2702.2.19.1. Fuel Supply. An on-premises fuel supply, sufficient for not less than 6-hour full-load operation of the emergency and standby power source(s), shall be provided. This fuel supply shall not be less than 8-hour when the load also includes fire pump(s).
 
 
 