No portion of any projection from any building over any roadway shall be lower than an elevation of 14 feet (4267.2 mm) above the roadway surface. (Amended by Ord. No. 185,587, Eff. 7/16/18.)
Projections into the public right-of-way shall require the approval of the Department of Public Works.
(Amended by Ord. No. 185,587, Eff. 7/16/18.)
Section 3202 of the CBC is adopted by reference, except Section 3202.3.1 of the CBC is not adopted; and, in lieu, LAMC Subdivision 91.3202.3.1 is added.
91.3202.3.1. Awnings, Canopies, Marquees and Signs. Awnings, canopies, marquees and signs shall be constructed so as to support applicable loads as specified in Division 16, Article 1, Chapter IX of the LAMC. Awnings, canopies, marquees and signs with less than 15 feet (4572 mm) clearance above the sidewalk shall not extend into or occupy more than 2/3 the width of the sidewalk measured from the building. Stanchions or columns that support awnings, canopies, marquees and signs shall be located not less than 2 feet (609.6 mm) in from the curb line.
Prior to issuance of a building permit, plans and specifications and the type, design, arrangement and location of every marquee shall be approved by the City's Board of Cultural Affairs Commissioners and Board of Public Works.
(Amended by Ord. No. 185,587, Eff. 7/16/18.)
Section 3301 of the CBC is adopted by reference, except Section 3301.1 of the CBC is not adopted; and, in lieu, LAMC Subsection 91.3301.1 is added.
This section shall not be construed to waive the requirements of the General Safety Orders of the Department of Industrial Relations of the State of California, or the provisions of California Civil Code Section 832 concerning the rights of coterminous owners as to excavations.
See Division 70, Article 1, Chapter IX of the LAMC for all grading, excavation and fill requirements.
(Amended by Ord. No. 185,587, Eff. 7/16/18.)
Section 3304 of the CBC is adopted by reference, except Section 3304.1.4 of the CBC is not adopted; and, in lieu, LAMC Subdivision 91.3304.1.4 is added.
91.3304.1.4. Fill Supporting Foundations. (Amended by Ord. No. 186,488, Eff. 12/27/19.) Fill to be used to support the foundations of any building or structure shall comply with CBC Section 1804.6 and Division 70, Article 1, Chapter IX of the LAMC. Special inspections of compacted fill shall be in accordance with CBC Section 1705.6.
91.3305.1. Toilet Facilities Required. (Amended by Ord. No. 185,587, Eff. 7/16/18.) No person shall commence or proceed with the erection, construction, alteration, repair, raising, adding to, removal or demolition of any building or structure unless adequate, suitable, sanitary toilet facilities under the control of that person are provided for the use of any person employed or working upon the building or structure. The toilet facilities shall be located upon or within a reasonable distance of the lot, premises, or site upon which the work is being done. In no case shall the line of travel to any toilet facility exceed 500 feet (152.4 m).
91.3305.2. Toilet Standards. Every toilet shall be of the water-flush type and connected to a public sewer or a private sewage disposal system built in accordance with the provisions of the Plumbing Code. All toilet structures shall be completely enclosed on four sides and the top, and the door shall be self-closing; the toilet floor shall be smooth, and screened ventilation shall be provided for the toilet compartment. Where workers are employed during the night hours, the toilet building shall be provided with artificial light. In lieu of flush water closets, approved chemical toilets, which meet the requirements of Chapter III of the Los Angeles Municipal Code, may be provided.
Loading...