(a) The provisions of this section shall not apply to buildings, each occupied by one (1) tenant and used for the manufacturing or processing of flammable liquid, provided such buildings are adequately isolated from other premises and do not present a conflagration hazard to the community.
(b) In applying the provisions of this section, each part of a building which is separated from all other parts by construction having a fire resistance rating commensurate to the fire load but of not less than one (1) hour may be deemed to be a separate building, and each such part may contain the maximum quantities hereinafter specified.
(c) Except as provided in subsections (a) and (b) hereof, or in Section 383.17, or as may be further limited or restricted by this Fire Prevention Code, the maximum quantity of flammable liquid stored or kept in containers in buildings and not stored or kept in rooms conforming to the provisions of Section 3129.43(c), or stored or kept in stationary or fixed tanks conforming to the applicable provisions of this chapter, shall be as follows: (Chapters 3125 to 3131 shall govern limits and restrictions applicable to occupancies other than high hazard occupancy.)
(1) Class I Liquid.
A. In buildings of Type IV, wood construction: in the Inner or Outer Fire District, none; in the Urban District, an aggregate of ten (10) gallons in sealed containers or safety cans of not more than one (1) gallon capacity each;
B. In buildings of Type I, fireproof, Type II, incombustible, or Type III, exterior protected construction: an aggregate of fifty (50) gallons in sealed containers or safety cans of not more than one (1) gallon capacity each.
(2) Class II Liquid.
A. In buildings of Type IV, wood construction: in the Inner or Outer Fire District, none; in the Urban District an aggregate of fifty (50) gallons in sealed containers or safety cans of not more than five (5) gallons capacity each;
B. In buildings of Type I, fireproof, Type II, incombustible or Type III, exterior protected construction: an aggregate of sixty (60) gallons in sealed containers or safety cans of not more than five (5) gallons capacity each or barrels or drums not exceeding sixty (60) gallons capacity each.
(3) Class III Liquid. In buildings of any type of construction; an aggregate of three thousand (3,000) gallons in sealed containers or safety cans not exceeding five (5) gallons capacity each or barrels or drums not exceeding sixty (60) gallons capacity each.
(4) Substitution of Liquids of Higher Flash Point. Class II or III liquid, in the same quantity, may be substituted for the permitted quantity of Class I liquid, and Class III liquid, in the same quantity, for the permitted quantity of Class II liquid. When substitutions are made, the maximum size of container may correspond to that permitted for storage of the class of liquid substituted.
(d) Flammable liquid in excess of the quantities given above or contained within containers exceeding the capacities specified above shall be stored either within rooms conforming to the provisions of Section 3129.43(c), or stored in aboveground or underground tanks as prescribed in this chapter, Chapters 385 and 3129, or stored in approved separate storage houses approved for such storage, or in drums or barrels stored outdoors in an approved isolated location.
(Ord. No. 991-49. Passed 6-27-49, eff. 6-27-49)
(a) Flammable liquid with flash point of ninety degrees Fahrenheit (90°F) or less shall not be stored or used in dwelling houses or row houses in quantities aggregating more than five (5) gallons, and all such liquid shall be in containers not exceeding one (1) gallon capacity. Containers shall be kept tightly sealed when not in actual use.
(b) Sections 385.73(h) to (m) and 3155.32 shall govern the storage and use of fuel oil and the installation of oil-fired appliances and equipment.
(Ord. No. 991-49. Passed 6-27-49, eff. 6-27-49)
The storing and handling of flammable liquids in garages and the application of flammable finishes shall be done in conformity with the applicable provisions of this chapter and Chapter 385.
(Ord. No. 991-49. Passed 6-27-49, eff. 6-27-49)
(a) No use or occupancy classified as high hazard occupancy shall be contained within any multiple dwelling, except that paint and oil stores, liquor stores and other retail stores of similar hazard may be permitted when separated from other occupancies in the building by approved occupancy separations, and when a permit for such use is issued by the Fire Chief and a certificate of occupancy therefor is issued by the Commissioner of Building.
(b) The provisions of this subsection apply to the storage of flammable liquid in parts of multiple dwellings classified as residential occupancy. The storage of flammable liquids in mercantile occupancies within such multiple dwellings shall be subject to the provisions of Section 383.17.
(c) No flammable liquid, in excess of an aggregate of five (5) gallons shall be stored without a permit from the Division of Fire. Flammable liquid with a flash point of ninety degrees Fahrenheit (90°F) or less shall be in containers not exceeding one (1) gallon capacity. Containers of flammable liquid shall be kept tightly sealed when not in use.
(d) Flammable liquid, including paint, stored in excess of such aggregate of five (5) gallons, shall be stored and used in conformity with the provisions of this chapter. Except as otherwise provided for the storage of fuel oil, all storage of flammable liquids in excess of an aggregate of five (5) gallons shall be within rooms or spaces contained within incombustible walls or partitions having a fire resistance rating of not less than one and one-half (1-1/2) hours with openings protected with self-closing doors having a fire resistance rating of not less than one and one-half (1-1/2) hours. Ceilings of such rooms or spaces shall have a fire resistance rating of not less than one (1) hour.
(e) Except as provided in subsection (d) hereof, each such storage room or space shall conform to the provisions of Section 3129.43(c).
(f) Sections 385.73 and 3155.22 shall govern the storage and use of fuel oil and the installation of oil- fired appliances and equipment.
(g) All flammable liquid stored within any multiple dwelling shall be stored only in conformity with the provisions of subsections (b) to (f) hereof.
(Ord. No. 341-A-55. Passed 6-27-55, eff. 7-1-55)
(a) The provisions of this section apply to the storage of flammable liquids in parts of buildings classified as of business occupancy. The storage of flammable liquids in mercantile occupancies shall conform to the provisions of Section 383.17.
(b) No flammable liquid in excess of an aggregate of five (5) gallons shall be stored without a permit from the Division of Fire. Flammable liquid with a flash point of 90° F or less shall be in containers not exceeding one (1) gallon capacity. Containers of flammable liquid shall be kept tightly sealed when not in use.
(c) Flammable liquid, including paint, stored in excess of an aggregate of five (5) gallons, shall be stored and used in conformity with the provisions of this chapter, and Sections 381.05, 385.35, 391.29 and 3129.34 to 3129.50. Except as otherwise provided in the Fire Prevention and Building Codes for the storage of fuel oil, all storage of flammable liquids in excess of an aggregate of five (5) gallons shall be within rooms or spaces contained within incombustible walls or partitions having a fire resistance rating of not less than one and one-half (1-1/2) hours with openings protected with self-closing doors having a fire resistance rating of not less than one and one-half (1-1/2) hours. Ceilings of such rooms or spaces shall have a fire resistance rating of not less than one (1) hour.
(d) Except as provided in subsection (c) hereof, each such storage room or space shall conform to the provisions of Section 3129.43(c).
(e) Sections 385.73(a) to (g) and 3155.32 shall govern the storage and use of fuel oil and the installation of oil fired appliances.
(Ord. No. 991-49. Passed 6-27-49, eff. 6-27-49)
(b) Storage rooms and spaces for the storage of flammable liquid shall conform to the provisions of Section 3129.43(c). Except when lesser fire resistance rating is specifically approved by the Commissioner of Building for storage not exceeding a fire load of ten (10) pounds per square foot, such rooms or spaces shall be enclosed within incombustible walls or partitions having a fire resistance rating of not less than one and one-half (1-1/2) hours with openings protected with self-closing doors having a fire resistance rating of not less than one and one-half (1-1/2) hours, and ceilings of such rooms or spaces shall have a fire resistance rating of not less than one (1) hour.
(c) The storage and handling of flammable liquid at service stations shall conform to the applicable provisions of this chapter. Gasoline storage at service stations shall be in approved underground tanks.
(d) Sections 385.73(a) to (g) and 3155.32 shall govern the storage and use of fuel oil and the installation of oil-fired appliances.
(Ord. No. 991-49. Passed 6-27-49, eff. 6-27-49)
(a) No flammable liquid in excess of the quantities specified in Section 383.04(e) shall be stored in any building or part of a building of storage occupancy classification without a permit from the Fire Division. Sections 381.05, 385.35, 391.29 and 3129.34 to 3129.50 shall govern permits required for storing other hazardous substances.
(b) When issuing permits for the storage of flammable liquid and other hazardous substances, the Fire Chief may prescribe maximum quantities, maximum height at which such material may be stored and other conditions necessary for safety or efficient fire fighting.
(Ord. No. 991-49. Passed 6-27-49, eff. 6-27-49)