§ 383.14 Storage in Assembly Occupancy
   (a)   No flammable liquid in excess of an aggregate of five (5) gallons shall be stored in any building of assembly occupancy classification without a permit from the Division of Fire. No flammable liquid in any quantity shall be kept or stored in any location where deemed hazardous by the Fire Chief. No flammable liquid shall be contained within the fuel tank of any motor vehicle placed on exhibition in a place of public assembly.
   (b)   No flammable gas of any kind whether natural gas, manufactured gas or compressed gas, shall be stored or used in any part of a building of assembly occupancy classification accessible to the public, or in any room or space of assembly occupancy, except for the preparation of food in kitchens where adequate approved and independent means of natural or mechanical ventilation are provided, or for heating by means of properly vented approved appliances, or for special necessary purposes when approved by the Commissioner of Building.
   (c)   Bowling pin finishing or refinishing operations shall be performed only in separate rooms used only for that purpose conforming to the provisions of Section 3129.43(c), except that the fire resistance rating of walls and partitions shall be not less than one and one-half (1-1/2) hours, and of floors and ceiling construction not less than one (1) hour.
   (d)   No flammable liquid shall be used for refinishing within any building or part of a building of assembly occupancy classification at a time when any part of the building is in use by the public, and no such building shall again be used by the public until all flammable vapor and dust have been removed.
   (e)   Sections 385.73(a) to (g) and 3155.32 shall govern the storage and use of fuel oil and the installation of oil-fired appliances.
(Ord. No. 991-49. Passed 6-27-49, eff. 6-27-49)