3006.1.2.10 Control panel.
A fire-fighter's smoke control panel complying with Section 909.16 shall be provided.
3006.1.2.11 System response time.
Hoistway pressurization systems shall comply with the requirements for smoke control system response time in Section 909.17.
3007.1 General.
Where required by Section 403.6.1, every floor of the building shall be served by a fire service access elevator complying with Sections 3007.1 through 3007.8. Except as modified in this section, the fire service access elevator shall be installed in accordance with this chapter and ASME A17.1/CSA B44 as modified by Appendix K, Chapter K1.
3007.2 Automatic sprinkler system.
The building shall be equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1, except as otherwise permitted by Section 903.3.1.1.1 and as prohibited by Section 3007.2.1.