2702.2.5 Accessible means of egress elevators.
Standby power shall be provided for elevators that are part of an accessible means of egress in accordance with Section 1009.4.
2702.2.6 Horizontal sliding doors.
Standby power shall be provided for horizontal sliding doors in accordance with Section 1010.1.4.3.
2702.2.7 Semiconductor fabrication facilities.
Emergency power shall be provided for semiconductor fabrication facilities in accordance with Section 415.11.10.
2702.2.8 Membrane structures.
Standby power shall be provided for auxiliary inflation systems in accordance with Section 3102.8.2. Emergency power shall be provided for exit signs in tents and membrane structures.
2702.2.9 Hazardous materials.
Emergency or standby power shall be provided in occupancies with hazardous materials in accordance with the New York City Fire Code and Section 414.5.2 of this code.
2702.2.10 Highly toxic and toxic materials.
Emergency power shall be provided for occupancies with highly toxic or toxic materials in accordance with the New York City Fire Code.
2702.2.11 Organic peroxides.
Emergency or standby power shall be provided for occupancies with organic peroxides in accordance with the New York City Fire Code.
2702.2.12 Pyrophoric materials.
Emergency power shall be provided for occupancies with silane gas in accordance with the New York City Fire Code.
2702.2.13 Covered and open mall buildings.
Emergency power shall be provided for voice/alarm communication systems in covered and open mall buildings in accordance with Section 402.7.4.