2702.1.2.3 Multiple generators.
Multiple generators supplying emergency power system loads only, or supplying emergency power system equipment in combination with optional standby power loads as a common system may be located in the same room. Such generators may also share a common room, fuel supply and other common equipment and systems.
2702.1.3 Capacity.
The emergency and standby power systems shall have capacity and ratings that supply all equipment required to be operational at the same time.
2702.1.4 Protection of fire pumps.
Where electrically powered fire pumps are connected to the emergency power system, overcurrent protection and feeder conductors shall be provided in accordance with the New York City Electrical Code. Automatic transfer switches shall be located in the same room as the fire pump as an integral part of the pump controller.
2702.1.5 Special inspection.
The installation of a required emergency or standby power system shall be subject to special inspection in accordance with Section 1705.
2702.1.6 Registration.
Fuel-burning equipment for an emergency or standby power system shall be registered with the Department of Environmental Protection in accordance with the requirements of Section 24-109 of the Administrative Code.