2114.2.3 Vertical ties.
Each column, pier and wall shall be vertically tied continuously from its lowest to highest level. The vertical reinforcement shall be terminated in a horizontal tie or foundation or their equivalent. Where openings in bearing walls greater than 24 inches (610 mm) in height occur, ties shall be provided at each side of the opening that extend and are anchored in the masonry above and below the opening. Vertical ties shall be placed on both sides of control joints in bearing walls.
2114.2.3.1 Vertical ties reinforcing.
Vertical tie reinforcing shall not be less than the equivalent of one No. 4 bar, at a maximum spacing of 48 inches (1219 mm) on center. A minimum of four continuous No. 4 bars shall be provided per masonry column or pier.
2201.1 Scope.
The provisions of this chapter govern the quality, design, fabrication and erection of steel construction.
2201.2 Special inspection.
Steel shall be subject to the requirements of special inspection in accordance with Chapter 17.