2309.4 Canopies.
Dispensing equipment need not be separated from canopies of Type I or II construction that are constructed in a manner that prevents the accumulation of hydrogen gas and in accordance with Chapter 4 of the Building Code.
2309.5 Weather protection.
Generation, compression, storage or dispensing equipment shall be allowed under weather protection in accordance with the requirements of Chapter 4 of the Building Code and FC 5004.13. The weather protection shall be constructed in a manner that prevents the accumulation of hydrogen gas.
2309.6 Overpressure protection.
Dispensing systems shall be equipped with an overpressure protection device set at 140 percent of the service pressure of the fueling nozzle it supplies.
2309.7 Safety precautions.
Safety precautions at hydrogen motor fuel-dispensing and generating facilities shall be in accordance with this section.
2309.7.1 Protection from vehicles.
Guard posts or other approved means shall be provided to protect hydrogen storage systems and use areas subject to vehicular damage in accordance with FC 312.
2309.7.2 Vehicle fueling pad.
The motor vehicle shall be fueled on noncoated concrete or other approved paving material having a resistance not exceeding 1 megohm as determined by the methodology specified in EN 1081.