Loading...
2309.1.5.3 Emergency procedures.
A sign setting forth emergency procedures that reads as follows shall be posted in the dispensing area, or other location designated in this section:
IN CASE OF FIRE, LEAK OR EMERGENCY:
ACTIVATE EMERGENCY SHUTDOWN
DIRECT VEHICLE OCCUPANTS TO EXIT VEHICLES
AND LEAVE AREA IMMEDIATELY
KEEP ALL PERSONS AWAY FROM THE AREA
NOTIFY THE FIRE DEPARTMENT (CALL 911)
(FACILITY ADDRESS)
(indicate address, with cross-street reference).
ACTIVATE EMERGENCY SHUTDOWN
DIRECT VEHICLE OCCUPANTS TO EXIT VEHICLES
AND LEAVE AREA IMMEDIATELY
KEEP ALL PERSONS AWAY FROM THE AREA
NOTIFY THE FIRE DEPARTMENT (CALL 911)
(FACILITY ADDRESS)
(indicate address, with cross-street reference).
2309.1.5.4 Canopy top hydrogen storage.
An approved sign having 2-inch (51-mm) block letters shall be conspicuously posted at approved locations on the exterior of any canopy structure when gaseous hydrogen compression and storage equipment is located on top of such canopy reading "CANOPY TOP HYDROGEN STORAGE."
2309.1.6 Emergency telephone.
A telephone not requiring a coin to operate or another approved, clearly identified means to notify the department, shall be provided on the site in an approved location.
2309.2 Equipment.
Equipment used for the generation, compression, storage or dispensing of hydrogen shall be designed for hydrogen motor fuel in accordance with this section.