Skip to code content (skip section selection)
Compare to:
Los Angeles Overview
Los Angeles Charter and Administrative Code
Los Angeles Municipal Code
MUNICIPAL CODE
FOREWORD
CHAPTER I GENERAL PROVISIONS AND ZONING
CHAPTER 1A CITY OF LOS ANGELES ZONING CODE
CHAPTER II* LICENSES, PERMITS, BUSINESS REGULATIONS
CHAPTER III PUBLIC HEALTH CODE
CHAPTER IV PUBLIC WELFARE
CHAPTER V PUBLIC SAFETY AND PROTECTION
CHAPTER VI PUBLIC WORKS AND PROPERTY
CHAPTER VII TRANSPORTATION
CHAPTER VIII TRAFFIC
CHAPTER IX BUILDING REGULATIONS
ARTICLE 1 BUILDINGS [BUILDING CODE]
DIVISION 1 ADMINISTRATION
DIVISION 2 DEFINITIONS AND ABBREVIATIONS
DIVISION 3 USE OR OCCUPANCY
DIVISION 4 SPECIAL USE AND OCCUPANCY
DIVISION 5 GENERAL BUILDING HEIGHTS AND AREAS
DIVISION 6 TYPES OF CONSTRUCTION
DIVISION 7 FIRE-RESISTANT MATERIALS AND CONSTRUCTION
DIVISION 8 INTERIOR FINISHES
DIVISION 9 FIRE-PROTECTION SYSTEMS
DIVISION 10 MEANS OF EGRESS
DIVISION 11 ACCESSIBILITY
DIVISION 12 INTERIOR ENVIRONMENT
DIVISION 13 ENERGY CONSERVATION
DIVISION 14 EXTERIOR WALL COVERINGS
DIVISION 15 ROOFS AND ROOF STRUCTURES
DIVISION 16 STRUCTURAL DESIGN
DIVISION 17 STRUCTURAL TESTS AND SPECIAL INSPECTIONS
DIVISION 18 SOILS AND FOUNDATIONS
DIVISION 19 CONCRETE
DIVISION 20 ALUMINUM
DIVISION 21 MASONRY
DIVISION 22 STEEL
DIVISION 23 WOOD
DIVISION 24 GLASS AND GLAZING
DIVISION 25 GYPSUM BOARD AND PLASTER
DIVISION 26 PLASTIC
DIVISION 27 ELECTRICAL SYSTEMS
DIVISION 28 MECHANICAL SYSTEMS
DIVISION 29 PLUMBING SYSTEMS
DIVISION 30 ELEVATORS AND CONVEYING SYSTEMS
DIVISION 31 SPECIAL CONSTRUCTION
DIVISION 32 ENCROACHMENTS INTO THE PUBLIC RIGHT-OF-WAY
DIVISION 33 SAFEGUARDS DURING CONSTRUCTION
DIVISION 34 EXISTING STRUCTURES
DIVISION 35 REFERENCED STANDARDS
DIVISION 61 SPECIAL HAZARD AREAS
DIVISION 62 SIGNS
DIVISION 63 ADDITIONAL PROVISIONS FOR SPECIFIC USES
DIVISION 67 SECURITY PROVISIONS
DIVISION 70 GRADING, EXCAVATIONS AND FILLS
DIVISION 71 METHANE SEEPAGE REGULATIONS
DIVISION 72 FIRE DISTRICT REGULATIONS
DIVISION 81 EXISTING BUILDINGS AND STRUCTURES - GENERAL REQUIREMENTS
DIVISION 82 CHANGE OF OCCUPANCY, USE AND RATING CLASSIFICATION
DIVISION 83 RELOCATION PERMIT
DIVISION 85 ALTERNATIVE BUILDING STANDARDS FOR JOINT LIVING AND WORK QUARTERS
DIVISION 86 SPECIAL PROVISIONS FOR EXISTING BUILDINGS
DIVISION 88 EARTHQUAKE HAZARD REDUCTION IN EXISTING BUILDINGS
DIVISION 89 ABATEMENT OF BUILDINGS, STRUCTURES, PREMISES AND PORTIONS THEREOF WHICH CONSTITUTE A NUISANCE OR ARE HAZARDOUS, OR SUBSTANDARD
DIVISION 90 NUISANCE ABATEMENT AND DISCONTINUANCE OF LAND USE AND DISCRETIONARY ZONING APPROVALS; RELOCATION ASSISTANCE; ENFORCEMENT
DIVISION 91 EARTHQUAKE HAZARD REDUCTION IN EXISTING TILT-UP CONCRETE WALL BUILDINGS
DIVISION 92 VOLUNTARY - EARTHQUAKE HAZARD REDUCTION IN EXISTING WOOD FRAME RESIDENTIAL BUILDINGS WITH WEAK CRIPPLE WALLS AND UNBOLTED SILL PLATES
DIVISION 93 MANDATORY EARTHQUAKE HAZARD REDUCTION IN EXISTING WOOD-FRAME BUILDINGS WITH SOFT, WEAK OR OPEN-FRONT WALLS
DIVISION 94 VOLUNTARY - EARTHQUAKE HAZARD REDUCTION IN EXISTING HILLSIDE BUILDINGS
DIVISION 95 MANDATORY EARTHQUAKE HAZARD REDUCTION IN EXISTING NON-DUCTILE CONCRETE BUILDINGS
DIVISION 96 VOLUNTARY - EARTHQUAKE HAZARD REDUCTION IN EXISTING REINFORCED CONCRETE AND REINFORCED MASONRY WALL BUILDINGS WITH FLEXIBLE DIAPHRAGMS
DIVISION 97 EXISTING BUILDINGS ENERGY AND WATER EFFICIENCY PROGRAM
ARTICLE 1.2 EXISTING BUILDING CODE
ARTICLE 1.5 LOS ANGELES RESIDENTIAL CODE
ARTICLE 2 ELEVATOR CODE
ARTICLE 3 ELECTRICAL CODE
ARTICLE 4 PLUMBING CODE
ARTICLE 5 MECHANICAL CODE
ARTICLE 6 MISCELLANEOUS
ARTICLE 7 BOILERS, UNFIRED PRESSURE VESSELS AND OTHER EQUIPMENT
ARTICLE 8 GENERAL ADMINISTRATIVE PROVISIONS
ARTICLE 9 GREEN BUILDING CODE
CHAPTER X BUSINESS REGULATIONS
CHAPTER XI NOISE REGULATION
CHAPTER XII THE WATER CONSERVATION PLAN OF THE CITY OF LOS ANGELES
CHAPTER XIII THE EMERGENCY ENERGY CURTAILMENT PLAN OF THE CITY OF LOS ANGELES
CHAPTER XV RENT STABILIZATION ORDINANCE
CHAPTER XVI HOUSING REGULATIONS
CHAPTER XVII RULES AND REGULATIONS GOVERNING THE USE OF THE LOS ANGELES AIRPORTS
CHAPTER XVIII EMPLOYEE WAGES AND PROTECTIONS
CHAPTER XIX ENVIRONMENTAL PROTECTION
CHAPTER XX COVID-19 PROTECTION AND RECOVERY*
TABLES
Los Angeles Planning and Zoning
Chapter 1A City of Los Angeles Zoning Code
Table of Amending Legislation for Chapter 1A
Loading...
SEC. 91.7103. GENERAL METHANE MITIGATION REQUIREMENTS.
 
   All new buildings and paved areas located in a Methane Zone or Methane Buffer Zone shall comply with these requirements and the Methane Mitigation Standards established by the Superintendent of Building. The Methane Mitigation Standards provide information describing the installation procedures, design parameters and test protocols for the methane gas mitigation system, which are not set forth in the provisions of this division.
 
   Boundaries of the Methane Zones and Methane Buffer Zones are shown on the "Methane and Methane Buffer Zones Map" designated as Map number A-20960, dated September 21, 2003, which is attached to Council File No. 01-1305 or the most recent version of the described map. (Amended by Ord. No. 185,587, Eff. 7/16/18.)
 
   Equipment and Systems. All devices, components and equipment installed in any methane detection system shall be approved by the Fire Department as set forth in Fire Prevention Bureau (F. P. B.) Requirement No. 71. (Added by Ord. No. 180,619, Eff. 5/12/09.)
 
 
SEC. 91.7104. GENERAL METHANE REQUIREMENTS.
 
91.7104.1. Site Testing. (Amended by Ord. No. 185,587, Eff. 7/16/18.) Site testing of subsurface geological formations shall be conducted in accordance with the Methane Mitigation Standards. The site testing shall be conducted under the supervision of a licensed Architect or registered Engineer or Geologist and shall be performed by a testing agency approved by the Department.
 
   The licensed Architect, registered Engineer or Geologist shall indicate in a report to the Department the testing procedure, the testing instruments used to measure the concentration and pressure of the methane gas. The measurements of the concentration and pressure of the methane gas shall be used to determine the Design Methane Concentration and the Design Methane Pressure. The Design Methane Concentration and the Design Methane Pressure shall determine the Site Design Level of LAMC Table 71.
 
   EXCEPTION: Site testing is not required for buildings designed to the requirements of Site Design Level V as described in LAMC Table 71, or for buildings designed using the exceptions set forth in LAMC Subdivisions 91.7104.3.2 or 91.7104.3.3.
 
91.7104.2. Methane Mitigation Systems. (Amended by Ord. No. 185,587, Eff. 7/16/18.) All buildings located in the Methane Zone and Methane Buffer Zone shall provide a methane mitigation system as required by LAMC Table 71 based on the appropriate Site Design Level. The Superintendent of Building may approve an equivalent methane mitigation system designed by an Architect, Engineer or Geologist.
 
   LAMC Table 71 prescribes the minimum methane mitigation systems, such as, the passive, active and miscellaneous systems, depending on the concentration and pressure of the methane present at the site. Each component of the passive, active and miscellaneous systems shall be constructed of an approved material and shall be installed in accordance with the Methane Mitigation Standards.
 
91.7104.2.1. Passive System. The passive system is a methane mitigation system installed beneath or near the building. The components of the passive system may consist of a de-watering system, the sub-slab vent system, and impervious membrane. The sub-slab vent system shall consist of Perforated Horizontal Pipes, Vent Risers, and Gravel Blankets for the purpose of collecting and conveying methane from the soil underneath the building to the atmosphere.
 
91.7104.2.1.1. De-watering System. The de-watering system is used to lower the ground water table to a level more than 12 inches below the bottom of the Perforated Horizontal Pipes. The de-watering system shall conduct ground water to an approved location.
 
91.7104.2.2. Active System. The components of the active system shall consist of one or more of the following, sub-slab system, gas detection system, mechanical ventilation, alarm system and control panel. All components shall be constructed of an approved material, installed in accordance with the Methane Mitigation Standards.
 
91.7104.2.3. Miscellaneous System. The components of the miscellaneous system may consist of Trench Dam, Cable or Conduit Seal Fitting, or Additional Vent Risers. The component of the miscellaneous system shall be a material approved by the Department and shall be installed in accordance with the Methane Mitigation Standards.
 
91.7104.3. Exceptions to LAMC Table 71. (Amended by Ord. No. 185,587, Eff. 7/16/18.) The provisions of this section are exceptions to the construction requirements of LAMC Table 71.
 
91.7104.3.1. (Repealed by Ord. No. 180,619, Eff. 5/12/09.)
 
91.7104.3.2. Buildings with Raised Floor Construction. If a Building with Raised Floor Construction has underfloor ventilation construction in accordance with the standards below, then the utilities shall be installed with Trench Dams and Cable or Conduit Seal Fittings and a four inch thick gravel blanket shall be installed under and around the elevator pits.
 
   Underfloor ventilation shall be provided by an approved mechanical ventilation system capable of exhausting underfloor air an equivalent of every 20 minutes, or by openings in the underfloor area complying with the following:
 
   A.   The top of the openings shall be located not more than 12 inches below the bottom of the floor joists.
 
   B.   The openings shall be distributed approximately equally and located to provide cross ventilation, for example, by locating the opening along the length of at least two opposite sides of the building.
 
   C.   The openings shall be the larger of:
 
   1.   Openings of not less than 1.5 square feet for each 25 linear feet or fraction of exterior wall; or
 
   2.   Openings shall be equal to 1 percent of underfloor area.
 
   D.   The openings may be covered with corrosion-resistant wire mesh with mesh openings of greater than ¼ inch and less than ½ inch in dimension.
 
91.7104.3.3. Buildings with Natural Ventilation. A building with natural ventilation is a building constructed with the following:
 
   A.   The Unobstructed Openings shall exchange outside air.
 
   B.   The size of the Unobstructed Opening shall be the larger of:
 
   1.   Opening equal to at least 25 percent of the total perimeter wall area of the lowest level of the building, or
 
   2.   Opening equal to at least 25 percent of the floor area of the lowest level of the building.
 
   C.   The Unobstructed Openings shall be evenly distributed and located within the upper portion of at least two opposite exterior walls of the lowest level of the building.
 
   Buildings with natural ventilation that are constructed as described above shall have the utilities constructed with Trench Dams and Cable or Conduit Seal Fittings. If there is an enclosed room or space less than 150 square feet (13.93 m2) within the building, then the enclosed room or space shall be constructed with vent openings that comply with the requirements of LAMC Subdivision 91.7104.3.4. (Amended by Ord. No. 185,587, Eff. 7/16/18.)
 
91.7104.3.4. Enclosed Room or Space within Building. (Amended by Ord. No. 185,587, Eff. 7/16/18.) Individual enclosed rooms or enclosed spaces with floor area less than 2,000 square feet (185.80 m2) may be exempt from providing the Active System as required by LAMC Table 71, provided the vent openings comply with all of the following:
 
   1.   Vent openings are Unobstructed Openings, except screens made with at least 1/4 inch mesh or wind driven turbines on the roof shall be permitted.
 
   2.   The aggregate size of vent openings shall be the larger of either five percent of the total floor area of the room or the area of enclosed space, or ten percent of the area of walls on the perimeter of the room or enclosed space.
 
   3.   The vent openings shall be located to prevent the accumulation of methane gases within the room or enclosed space.
 
   4.   The top of the vent opening shall be located not more than 12 inches below roof joists or ceiling joists if located in a wall of a building.
 
   5.   The vent openings shall be located on either two opposite walls or two adjacent walls of the room or enclosed space if located in a wall of a building.
 
   6.   The vent openings shall be located no more than 50 feet from any point within the room or enclosed space.
 
   7.   When using wind driven turbine, the area of the vent opening shall be calculated by the area of the opening at the attachment of the wind driven turbine at the roof.
 
   8.   When the vent opening is located in a wall of an adjoining room, then the adjoining room shall be constructed of either an Active System, or have Natural Ventilation as described in LAMC Subdivision 91.7104.3.3.
 
91.7104.3.5. Single Family Dwelling. (Amended by Ord. No. 185,587, Eff. 7/16/18.) Single Family Dwellings and buildings accessory to single family dwellings shall comply with all the Methane Mitigation requirements of LAMC Table 71, except that the following mitigation system may be substituted:
 
   A.   Single Station Gas Detectors with battery back-up may be installed in lieu of Alarm System and Gas Detection System; or
 
   B.   6 mil thick Visquene may be used in lieu of Impervious Membrane, when the Site Design Levels are I or II; or
 
   C.   Additional Vent Risers or Mechanical Ventilation may be omitted for buildings with width less than 50 feet and footprint less than 6,000 square feet in area; or
 
   D.   Vent Risers may be substituted in lieu of Mechanical Extraction System, provided the Vent Risers are designed at a rate twice that established by the Methane Mitigation Standards.
 
91.7104.3.6. Buildings Located in the Methane Buffer Zone. A building, located entirely or partially in the Methane Buffer Zone, shall be designed to the requirements of the Methane Buffer Zone. Buildings located in the Methane Buffer Zone shall not be required to provide any methane mitigation system, if the Design Methane Pressure is less than or equal to two inches of water pressure and is either of the following:
 
   A.   Areas which qualify as Site Design Level I or II; or
 
   B.   Areas which qualify as Site Design Level III and the utilities are installed with Trench Dams and Cable or Conduit Seal Fitting.
 
91.7104.3.7. De-watering System. A De-watering system is not required for either of the following:
      
   A.   If during the site testing, the groundwater level is deeper than 10 feet below the Perforated Horizontal Pipes, or
 
   B.   If the soil investigation or analysis, as approved by the Department, reveals the groundwater level is more than 12 inches below the bottom of the Perforated Horizontal Pipes.
 
91.7104.3.8. Buildings Located in the First Phase Playa Vista Project. The First Phase Playa Vista project, as approved by the City on September 21, 1993 and December 8, 1995, shall comply with the methane mitigation program as required by the Department pursuant to the Methane Prevention, Detection and Monitoring Program approved by the Department on January 31, 2001, in lieu of the requirements of this division.
 
91.7104.4. Paved Areas. Paved areas that are over 5,000 square feet in area and within 15 feet of the exterior wall of a commercial, industrial, institutional or residential building, shall be vented in accordance with the Methane Mitigation Standards.
 
   EXCEPTION: Paved areas located in the Methane Buffer Zone and which qualify for Site Design Levels I, II or III.
 
 
SEC. 91.7105. EXISTING BUILDINGS.
 
   Additions, alterations, repairs, changes of use or changes of occupancy to existing buildings shall comply with the methane mitigation requirements of LAMC Subsections 91.7104.1 and 91.7104.2, when required by Divisions 81 or 82 of Article 1, Chapter IX of the LAMC. (Amended by Ord. No. 184,692, Eff. 12/30/16.)
 
   Approved methane mitigation systems in existing buildings shall be maintained in accordance with LAMC Section 91.7106. (Amended by Ord. No. 185,587, Eff. 7/16/18.)
 
 
SEC. 91.7106. TESTING, MAINTENANCE AND SERVICE OF GAS-DETECTION AND MECHANICAL VENTILATION SYSTEMS.
   (Amended by Ord. No. 185,587, Eff. 7/16/18.)
 
   The installation instructions for the gas detection and mechanical ventilation systems, which are required by LAMC Table 71, shall be approved and enforced by the Fire Department. All gas detection and mechanical ventilation systems shall be maintained and serviced in proper working condition and meet all requirements of the State of California and City Electrical and Mechanical Codes.
 
   A.   Fire Department. The Fire Department shall enforce the following:
 
   1.   The maintenance and service procedures for each gas detection and mechanical ventilation systems, which are required in LAMC Table 71, shall be performed by the building owner in accordance with the manufacturers written instructions.
 
   2.   The annual and maintenance testing shall be performed as set forth by the Fire Department in accordance with the Fire Prevention Bureau (F.P.B.) Requirement No. 71 and Fire Chief's Regulation 4, Section 4J.
 
   3.   The testing of the gas detection and mechanical ventilation systems shall be performed by a person with a valid Certificate of Fitness for Gas Detection Systems as set forth in LAMC Section 57.117.
 
   B.   Notification Placard. A permanent notification placard shall be posted and maintained at the front entrance of a building that is constructed with Impervious Membrane, except in residential buildings. The placard shall indicate the presence of the Impervious Membrane.
 
 
SEC. 91.7107. EMERGENCY PROCEDURES.
 
   With the exception of single-family dwellings, all buildings required by this division to have a gas detection system or sub-slab vent system shall, subject to Fire Department approval, have established emergency procedures that include, but are not limited to, the following: (Amended by Ord. No. 180,619, Eff. 5/12/09.)
 
   A.   Assignment of a responsible person as safety director to work with the Fire Department in the establishment, implementation and maintenance of an emergency plan.
 
   B.   Conspicuous posting of the Fire Department’s telephone number in areas designated by the Fire Department.
 
   C.   Conspicuous posting of emergency plan procedures approved by the Fire Department.
 
 
SEC. 91.7108. APPLICATION OF METHANE SEEPAGE REGULATIONS TO LOCATIONS OR AREAS OUTSIDE THE METHANE ZONE AND METHANE BUFFER ZONE BOUNDARIES.
   (Amended by Ord. No. 185,587, Eff. 7/16/18.)
 
   Upon a determination by the Department that a hazard may exist from methane intrusion at a geographical location or in an area outside the boundaries established in LAMC Section 91.7103, the Department and the Fire Department may enforce any or all of the requirements of Division 71, Article 1, Chapter IX of the LAMC as required to preclude potential fire or explosion from methane concentration.
 
 