Skip to code content (skip section selection)
Compare to:
Chicago Overview
Municipal Code of Chicago
MUNICIPAL CODE OF CHICAGO
TITLE 1 GENERAL PROVISIONS
TITLE 2 CITY GOVERNMENT AND ADMINISTRATION
TITLE 3 REVENUE AND FINANCE
TITLE 4 BUSINESSES, OCCUPATIONS AND CONSUMER PROTECTION
TITLE 5 HOUSING AND ECONOMIC DEVELOPMENT
TITLE 6 HUMAN RIGHTS*
TITLE 7 HEALTH AND SAFETY
TITLE 8 OFFENSES AFFECTING PUBLIC PEACE, MORALS AND WELFARE
TITLE 9 VEHICLES, TRAFFIC AND RAIL TRANSPORTATION
TITLE 10 STREETS, PUBLIC WAYS, PARKS, AIRPORTS AND HARBORS
TITLE 11 UTILITIES AND ENVIRONMENTAL PROTECTION
TITLE 12 RESERVED
TITLE 13 BUILDINGS AND CONSTRUCTION
TITLE 14 RESERVED*
TITLE 14A ADMINISTRATIVE PROVISIONS OF THE CHICAGO CONSTRUCTION CODES*
TITLE 14B BUILDING CODE*
TITLE 14C CONVEYANCE DEVICE CODE*
TITLE 14E ELECTRICAL CODE*
TITLE 14F FIRE PREVENTION CODE*
TITLE 14G FUEL GAS CODE*
TITLE 14M MECHANICAL CODE*
TITLE 14N 2022 ENERGY TRANSFORMATION CODE*
TITLE 14P PLUMBING CODE*
TITLE 14R BUILDING REHABILITATION CODE*
TITLE 14X MINIMUM REQUIREMENTS FOR EXISTING BUILDINGS*
TITLE 15 FIRE PREVENTION
TITLE 16 LAND USE
TITLE 17 CHICAGO ZONING ORDINANCE
TITLE 18 BUILDING INFRASTRUCTURE
CHAPTER 18-11 RESERVED*
CHAPTER 18-13 RESERVED*
CHAPTER 18-14 BUILDING ENERGY USE BENCHMARKING
CHAPTER 18-27 RESERVED*
CHAPTER 18-28 MECHANICAL SYSTEMS*
CHAPTER 18-29 PLUMBING*
Article 1. Administration (18-29-101 et seq.)
Article 2. Definitions (18-29-201 et seq.)
Article 3. General Regulations (18-29-301 et seq.)
Article 4. Fixtures, Faucets and Fixture Fittings (18-29-401 et seq.)
Article 5. Water Heaters (18-29-501 et seq.)
Article 6. Water Supply and Distribution (18-29-601 et seq.)
Article 7. Sanitary Drainage (18-29-701 et seq.)
Article 8. Indirect/Special Waste (18-29-801 et seq.)
Article 9. Vents (18-29-901 et seq.)
18-29-901 General.
18-29-901.1 Scope.
18-29-901.2 Trap seal protection.
18-29-901.2.1 Venting required.
18-29-901.3 Chemical waste vent system.
18-29-901.4 Use limitations.
18-29-901.5 Tests.
18-29-901.6 Protection from freezing.
18-29-902 Materials.
18-29-902.1 Vents.
18-29-902.2 Sheet copper.
18-29-902.3 Sheet lead.
18-29-903 Vent Stacks and Stack Vents.
18-29-903.1 Main vent required.
18-29-903.2 Vent stack required.
18-29-903.3 Vent termination.
18-29-903.4 Vent connection at base.
18-29-903.5 Vent headers.
18-29-904 Vent Terminals.
18-29-904.1 Vent terminals required.
18-29-904.1.1 Roof extension unprotected.
18-29-904.1.2 Occupiable rooftop.
18-29-904.1.3 Reserved.
18-29-904.1.4 Sidewall vent terminal.
18-29-904.2 Frost closure.
18-29-904.3 Flashings.
18-29-904.4 Prohibited use.
18-29-904.5 Location of vent terminal.
18-29-904.6 Extension outside a structure.
18-29-905 Vent Connections and Grades.
18-29-905.1 Connection.
18-29-905.2 Grade.
18-29-905.3 Vent connection to drainage system.
18-29-905.4 Vertical rise of vent.
18-29-905.5 Height above fixtures.
18-29-905.6 Side inlet.
18-29-905.7 Vent for future fixtures.
18-29-906 Fixture Vents.
18-29-906.1 Distance of trap from vent.
18-29-906.2 Venting of fixture drains.
18-29-906.3 Crown vent.
18-29-907 Individual Vent.
18-29-907.1 Individual vent permitted.
18-29-908 Common Vent.
18-29-908.1 Individual vent as common vent.
18-29-908.2 Connection at the same level.
18-29-908.3 Connection of different levels.
18-29-909 Deliberately omitted.
18-29-910 Deliberately omitted.
18-29-911 Deliberately omitted.
18-29-912 Combination Drain and Vent System.
18-29-912.1 Type of fixtures.
18-29-912.2 Waste piping and trap.
18-29-912.2.1 Branches.
18-29-912.2.2 Sinks, lavatories, and other fixtures.
18-29-912.2.3 Long mains.
18-29-912.2.4 Floor drains.
18-29-912.3 Size.
18-29-913 Island Fixture Venting.
18-29-913.1 Limitation.
18-29-913.2 Vent connection.
18-29-913.3 Vent installation below the fixture flood level rim.
18-29-914 Relief Vents - Stacks of More Than 10 Branch Intervals.
18-29-914.1 Where required.
18-29-914.2 Size and connection.
18-29-915 Vents for Stack Offsets.
18-29-915.1 Vent for horizontal offset of drainage stack.
18-29-915.2 Upper section.
18-29-915.3 Lower section.
18-29-916 Vent Pipe Sizing.
18-29-916.1 Size of stack vents and vent stacks.
18-29-916.2 Vents other than stack vents or vent stacks.
18-29-916.3 Developed length.
18-29-916.4 Multiple branch vents.
18-29-916.4.1 Reserved.
18-29-916.5 Sump vents.
18-29-916.5.1 Sewage pumps and sewage ejectors other than pneumatic.
18-29-916.5.2 Pneumatic sewage ejectors.
18-29-917 Vents Not Required.
18-29-917.1 Not required.
18-29-918 Deliberately omitted.
Article 10. Traps, Separators and Interceptors (18-29-1001 et seq.)
Article 11. Storm Drainage (18-29-1101 et seq.)
Article 12. Swimming Pools and Other Swimming Facilities* (18-29-1201 et seq.)
Article 13. Referenced Standards
Appendix A Procedures for Calculating the Minimum Sizing of the Water Supply System
CHAPTER 18-30 RESERVED*
CHAPTER 18-31 RESERVED*
CHAPTER 18-32 RESERVED*
CHAPTER 18-36 REFERENCE STANDARDS*
APPENDIX TO THE MUNICIPAL CODE OF CHICAGO (RESERVED)*
TABLES
Chicago Zoning Ordinance and Land Use Ordinance
Loading...
18-29-916.5.1 Sewage pumps and sewage ejectors other than pneumatic.
   Drainage piping below sewer level shall be vented in the same manner as that of a gravity system. Building sump vent sizes for sumps with sewage pumps or sewage ejectors, other than pneumatic, shall be determined in accordance with Table 18-29-916.5.1.
Table 18-29-916.5.1
Size and Length of Sump Vents
Discharge Capacity of Pump (gpm)
Maximum Developed Length of Vent (feet) a
Diameter of vent (inches)
1 1/4
1 1/2
2
2 1/2
3
4
Discharge Capacity of Pump (gpm)
Maximum Developed Length of Vent (feet) a
Diameter of vent (inches)
1 1/4
1 1/2
2
2 1/2
3
4
10
No limit b
No limit
No limit
No limit
No limit
No limit
20
270
No limit
No limit
No limit
No limit
No limit
40
72
160
No limit
No limit
No limit
No limit
60
31
75
270
No limit
No limit
No limit
80
16
41
150
380
No limit
No limit
100
10 c
25
97
250
No limit
No limit
150
NP
10 c
44
110
370
No limit
200
NP
NP
20
60
210
No limit
250
NP
NP
10
36
132
No limit
300
NP
NP
10 c
22
88
380
400
NP
NP
NP
10 c
44
210
500
NP
NP
NP
NP
24
130
 
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 gallon per minute = 3.785 L/m.
NP = Not permitted.
a.   Developed length plus an appropriate allowance for entrance losses and friction due to fittings, changes in direction and diameter. Allowances shall be obtained from NBS Monograph 31 or other engineered sources. An allowance of 50 percent of the developed length shall be assumed if a more precise value is not available.
b.   Actual values greater than 500 feet.
c.   Less than 10 feet.
(Amend Coun. J. 10-14-21, p. 37722, Art. IX, § 7)
18-29-916.5.2 Pneumatic sewage ejectors.
   The air pressure relief pipe from a pneumatic sewage ejector shall be connected to an independent vent stack terminating as required for vent extensions through the roof. The relief pipe shall be sized to relieve air pressure inside the ejector to atmospheric pressure but shall be not less than 1 1/2 inches (38 mm) in size.
(Amend Coun. J. 10-14-21, p. 37722, Art. IX, § 7)
18-29-917 Vents Not Required.
18-29-917.1 Not required.
   No vent will be required on a downspout trap, a subsoil catch basin trap draining by gravity to the house drain or sewer, or a basement floor drain which branches into the house drain at a distance of more than 5 feet from any soil or waste stack. Other floor drains below grade shall be vented at the end of the waste line or individually vented.
18-29-918 Deliberately omitted.
Article 10. Traps, Separators and Interceptors (18-29-1001 et seq.)
18-29-1001 General.
18-29-1001.1 Scope.
   This article shall govern the material and installation of traps, interceptors and separators.
18-29-1002 Trap Requirements.