18-29-915.2 Upper section.
   The upper section of the drainage stack shall be vented as a separate stack with a vent stack connection installed in accordance with Section 18-29-903.4. The offset shall be considered the base of the stack.
18-29-915.3 Lower section.
   The lower section of the drainage stack shall be vented by a yoke vent connecting between the offset and the next lower horizontal branch. The yoke vent connection shall be permitted to be a vertical extension of the drainage stack. The size of the yoke vent and connection shall be a minimum of the size required for the vent stack of the drainage stack.
18-29-916 Vent Pipe Sizing.
18-29-916.1 Size of stack vents and vent stacks.
   The minimum required diameter of stack vents and vent stacks shall be determined from the developed length and the total of drainage fixture units connected thereto in accordance with Table 906.1, but in no case shall the diameter be less than one-half the diameter of the drain served, or less than 1 1/4 inches (32 mm).
Table 18-29-916.1
Size and Developed Length of Stack Vents and Vent Stacks
Diameter of Soil or Waste Stack
(inches)
Total Fixture Units Being Vented
(dfu)
Maximum Developed Length of Vent (feet) a
Diameter of Vent (inches)
1 1/4 b
1 1/2 b
2
2 1/2
3
4
5
6
8
10
12
Diameter of Soil or Waste Stack
(inches)
Total Fixture Units Being Vented
(dfu)
Maximum Developed Length of Vent (feet) a
Diameter of Vent (inches)
1 1/4 b
1 1/2 b
2
2 1/2
3
4
5
6
8
10
12
1 1/4
1 1/2
1 1/2
2
8
10
30
50
30

150
100
2
2
2 1/2
12
20
42

30
26
75
50
30
200
150
100


300
3
3
3
10
21
53
42
32
27
150
110
94
360
270
230
1,040
810
680
3
4
4
102
43
140
25

86
35
27
210
85
65
620
250
200

980
750
4
4
5
320
540
190
23
21
55
50
28
170
150
82
640
580
320


990
5
5
5
490
940
1,400
21
18
16
63
53
49
250
210
190
760
670
590
6
6
6
500
1,100
2,000
33
26
22
130
100
84
400
310
260
1,000
780
660
6
8
8
2,900
1,800
3,400
20

77
31
24
240
95
73
600
240
190

940
729
8
8
10
5,600
7,600
4,000
20
18
62
56
31
160
140
78
610
560
310


960
10
10
10
7,200
11,000
15,000
24
20
18
60
51
46
240
200
180
740
630
571
12
12
12
7,300
13,000
20,000
31
24
20
120
94
79
380
300
250
940
720
610
12
15
15
26,000
15,000
25,000
18

72
40
31
230
130
96
500
310
240
15
15
38,000
50,000
26
24
81
74
200
180
 
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm.
a.   The developed length shall be measured from the vent connection to the open air.
b.   Not permitted for water closets.
(Amend Coun. J. 3-27-02, p. 82090, § 3; Amend Coun. J. 10-14-21, p. 37722, Art. IX, § 7)
18-29-916.2 Vents other than stack vents or vent stacks.
   The diameter of individual vents, branch vents, circuit vents and relief vents shall be not less than one-half the required diameter of the drain served. The required size of the drain shall be determined in accordance with Table 18-29-710B. Vent pipes shall be not less than 1 1/4 inches (32 mm) in diameter. Relief vents for soil and waste stacks in buildings having more than 10 branch intervals shall be sized in accordance with Section 18-29-914.2.
(Amend Coun. J. 10-14-21, p. 37722, Art. IX, § 7)
18-29-916.3 Developed length.
   The developed length of individual, branch, circuit and relief vents shall be measured from the farthest point of vent connection to the drainage system to the point of connection to the vent stack, stack vent or termination outside of the building.
(Amend Coun. J. 10-14-21, p. 37722, Art. IX, § 7)
18-29-916.4 Multiple branch vents.
   Where multiple branch vents are connected to a common branch vent, the common branch vent shall be sized in accordance with this section based on the size of the common horizontal drainage branch that is or would be required to serve the total drainage fixture unit load being vented.
(Amend Coun. J. 10-14-21, p. 37722, Art. IX, § 7)
18-29-916.4.1 Reserved.
Editor's note – Coun. J. 10-14-21, p. 37722, Art. IX, § 7, repealed § 18-29-916.4.1, which pertained to multiple branch vents exceeding 40 feet.
18-29-916.5 Sump vents.
   Sump vent sizes shall be determined in accordance with Sections 18-29-916.5.1 and 18-29-916.5.2.
(Amend Coun. J. 10-14-21, p. 37722, Art. IX, § 7)
18-29-916.5.1 Sewage pumps and sewage ejectors other than pneumatic.
   Drainage piping below sewer level shall be vented in the same manner as that of a gravity system. Building sump vent sizes for sumps with sewage pumps or sewage ejectors, other than pneumatic, shall be determined in accordance with Table 18-29-916.5.1.
Table 18-29-916.5.1
Size and Length of Sump Vents
Discharge Capacity of Pump (gpm)
Maximum Developed Length of Vent (feet) a
Diameter of vent (inches)
1 1/4
1 1/2
2
2 1/2
3
4
Discharge Capacity of Pump (gpm)
Maximum Developed Length of Vent (feet) a
Diameter of vent (inches)
1 1/4
1 1/2
2
2 1/2
3
4
10
No limit b
No limit
No limit
No limit
No limit
No limit
20
270
No limit
No limit
No limit
No limit
No limit
40
72
160
No limit
No limit
No limit
No limit
60
31
75
270
No limit
No limit
No limit
80
16
41
150
380
No limit
No limit
100
10 c
25
97
250
No limit
No limit
150
NP
10 c
44
110
370
No limit
200
NP
NP
20
60
210
No limit
250
NP
NP
10
36
132
No limit
300
NP
NP
10 c
22
88
380
400
NP
NP
NP
10 c
44
210
500
NP
NP
NP
NP
24
130
 
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 gallon per minute = 3.785 L/m.
NP = Not permitted.
a.   Developed length plus an appropriate allowance for entrance losses and friction due to fittings, changes in direction and diameter. Allowances shall be obtained from NBS Monograph 31 or other engineered sources. An allowance of 50 percent of the developed length shall be assumed if a more precise value is not available.
b.   Actual values greater than 500 feet.
c.   Less than 10 feet.
(Amend Coun. J. 10-14-21, p. 37722, Art. IX, § 7)
18-29-916.5.2 Pneumatic sewage ejectors.
   The air pressure relief pipe from a pneumatic sewage ejector shall be connected to an independent vent stack terminating as required for vent extensions through the roof. The relief pipe shall be sized to relieve air pressure inside the ejector to atmospheric pressure but shall be not less than 1 1/2 inches (38 mm) in size.
(Amend Coun. J. 10-14-21, p. 37722, Art. IX, § 7)
18-29-917 Vents Not Required.