The upper section of the drainage stack shall be vented as a separate stack with a vent stack connection installed in accordance with Section 18-29-903.4. The offset shall be considered the base of the stack.
The lower section of the drainage stack shall be vented by a yoke vent connecting between the offset and the next lower horizontal branch. The yoke vent connection shall be permitted to be a vertical extension of the drainage stack. The size of the yoke vent and connection shall be a minimum of the size required for the vent stack of the drainage stack.
The minimum required diameter of stack vents and vent stacks shall be determined from the developed length and the total of drainage fixture units connected thereto in accordance with Table 906.1, but in no case shall the diameter be less than one-half the diameter of the drain served, or less than 1 1/4 inches (32 mm).
Diameter of Soil or Waste Stack (inches) | Total Fixture Units Being Vented (dfu) | Maximum Developed Length of Vent (feet) a Diameter of Vent (inches) | ||||||||||
1 1/4 b | 1 1/2 b |
2 | 2 1/2 | 3 | 4 | 5 | 6 | 8 | 10 | 12 |
Diameter of Soil or Waste Stack (inches) | Total Fixture Units Being Vented (dfu) | Maximum Developed Length of Vent (feet) a Diameter of Vent (inches) | ||||||||||
1 1/4 b | 1 1/2 b |
2 | 2 1/2 | 3 | 4 | 5 | 6 | 8 | 10 | 12 | ||
1 1/4 1 1/2 1 1/2 | 2 8 10 | 30 50 30 | – 150 100 | – | – | – | – | – | – | – | – | – |
2 2 2 1/2 | 12 20 42 | – 30 26 | 75 50 30 | 200 150 100 | – – 300 | – | – | – | – | – | – | – |
3 3 3 | 10 21 53 | – | 42 32 27 | 150 110 94 | 360 270 230 | 1,040 810 680 | – | – | – | – | – | – |
3 4 4 | 102 43 140 | – | 25 – – | 86 35 27 | 210 85 65 | 620 250 200 | – 980 750 | – | – | – | – | – |
4 4 5 | 320 540 190 | – | – | 23 21 – | 55 50 28 | 170 150 82 | 640 580 320 | – – 990 | – | – | – | – |
5 5 5 | 490 940 1,400 | – | – | – | 21 18 16 | 63 53 49 | 250 210 190 | 760 670 590 | – | – | – | – |
6 6 6 | 500 1,100 2,000 | – | – | – | – | 33 26 22 | 130 100 84 | 400 310 260 | 1,000 780 660 | – | – | – |
6 8 8 | 2,900 1,800 3,400 | – | – | – | – | 20 – – | 77 31 24 | 240 95 73 | 600 240 190 | – 940 729 | – | – |
8 8 10 | 5,600 7,600 4,000 | – | – | – | – | – | 20 18 – | 62 56 31 | 160 140 78 | 610 560 310 | – – 960 | – |
10 10 10 | 7,200 11,000 15,000 | – | – | – | – | – | – | 24 20 18 | 60 51 46 | 240 200 180 | 740 630 571 | – |
12 12 12 | 7,300 13,000 20,000 | – | – | – | – | – | – | – | 31 24 20 | 120 94 79 | 380 300 250 | 940 720 610 |
12 15 15 | 26,000 15,000 25,000 | – | – | – | – | – | – | – | 18 – – | 72 40 31 | 230 130 96 | 500 310 240 |
15 15 | 38,000 50,000 | – | – | – | – | – | – | – | – | 26 24 | 81 74 | 200 180 |
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm.
a. The developed length shall be measured from the vent connection to the open air.
b. Not permitted for water closets.
(Amend Coun. J. 3-27-02, p. 82090, § 3; Amend Coun. J. 10-14-21, p. 37722, Art. IX, § 7)
The diameter of individual vents, branch vents, circuit vents and relief vents shall be not less than one-half the required diameter of the drain served. The required size of the drain shall be determined in accordance with Table 18-29-710B. Vent pipes shall be not less than 1 1/4 inches (32 mm) in diameter. Relief vents for soil and waste stacks in buildings having more than 10 branch intervals shall be sized in accordance with Section 18-29-914.2.
(Amend Coun. J. 10-14-21, p. 37722, Art. IX, § 7)
The developed length of individual, branch, circuit and relief vents shall be measured from the farthest point of vent connection to the drainage system to the point of connection to the vent stack, stack vent or termination outside of the building.
(Amend Coun. J. 10-14-21, p. 37722, Art. IX, § 7)
Where multiple branch vents are connected to a common branch vent, the common branch vent shall be sized in accordance with this section based on the size of the common horizontal drainage branch that is or would be required to serve the total drainage fixture unit load being vented.
(Amend Coun. J. 10-14-21, p. 37722, Art. IX, § 7)
Sump vent sizes shall be determined in accordance with Sections 18-29-916.5.1 and 18-29-916.5.2.
(Amend Coun. J. 10-14-21, p. 37722, Art. IX, § 7)
Drainage piping below sewer level shall be vented in the same manner as that of a gravity system. Building sump vent sizes for sumps with sewage pumps or sewage ejectors, other than pneumatic, shall be determined in accordance with Table 18-29-916.5.1.
Discharge Capacity of Pump (gpm) | Maximum Developed Length of Vent (feet) a | |||||
Diameter of vent (inches) | ||||||
1 1/4 | 1 1/2 | 2 | 2 1/2 | 3 | 4 |
Discharge Capacity of Pump (gpm) | Maximum Developed Length of Vent (feet) a | |||||
Diameter of vent (inches) | ||||||
1 1/4 | 1 1/2 | 2 | 2 1/2 | 3 | 4 | |
10 | No limit b |
No limit | No limit | No limit | No limit | No limit |
20 | 270 | No limit | No limit | No limit | No limit | No limit |
40 | 72 | 160 | No limit | No limit | No limit | No limit |
60 | 31 | 75 | 270 | No limit | No limit | No limit |
80 | 16 | 41 | 150 | 380 | No limit | No limit |
100 | 10
c | 25 | 97 | 250 | No limit | No limit |
150 | NP | 10
c | 44 | 110 | 370 | No limit |
200 | NP | NP | 20 | 60 | 210 | No limit |
250 | NP | NP | 10 | 36 | 132 | No limit |
300 | NP | NP | 10 c |
22 | 88 | 380 |
400 | NP | NP | NP | 10
c | 44 | 210 |
500 | NP | NP | NP | NP | 24 | 130 |
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 gallon per minute = 3.785 L/m.
NP = Not permitted.
a. Developed length plus an appropriate allowance for entrance losses and friction due to fittings, changes in direction and diameter. Allowances shall be obtained from NBS Monograph 31 or other engineered sources. An allowance of 50 percent of the developed length shall be assumed if a more precise value is not available.
b. Actual values greater than 500 feet.
c. Less than 10 feet.
(Amend Coun. J. 10-14-21, p. 37722, Art. IX, § 7)
The air pressure relief pipe from a pneumatic sewage ejector shall be connected to an independent vent stack terminating as required for vent extensions through the roof. The relief pipe shall be sized to relieve air pressure inside the ejector to atmospheric pressure but shall be not less than 1 1/2 inches (38 mm) in size.