18-29-916.1 Size of stack vents and vent stacks.
   The minimum required diameter of stack vents and vent stacks shall be determined from the developed length and the total of drainage fixture units connected thereto in accordance with Table 906.1, but in no case shall the diameter be less than one-half the diameter of the drain served, or less than 1 1/4 inches (32 mm).
Table 18-29-916.1
Size and Developed Length of Stack Vents and Vent Stacks
Diameter of Soil or Waste Stack
(inches)
Total Fixture Units Being Vented
(dfu)
Maximum Developed Length of Vent (feet) a
Diameter of Vent (inches)
1 1/4 b
1 1/2 b
2
2 1/2
3
4
5
6
8
10
12
Diameter of Soil or Waste Stack
(inches)
Total Fixture Units Being Vented
(dfu)
Maximum Developed Length of Vent (feet) a
Diameter of Vent (inches)
1 1/4 b
1 1/2 b
2
2 1/2
3
4
5
6
8
10
12
1 1/4
1 1/2
1 1/2
2
8
10
30
50
30

150
100
2
2
2 1/2
12
20
42

30
26
75
50
30
200
150
100


300
3
3
3
10
21
53
42
32
27
150
110
94
360
270
230
1,040
810
680
3
4
4
102
43
140
25

86
35
27
210
85
65
620
250
200

980
750
4
4
5
320
540
190
23
21
55
50
28
170
150
82
640
580
320


990
5
5
5
490
940
1,400
21
18
16
63
53
49
250
210
190
760
670
590
6
6
6
500
1,100
2,000
33
26
22
130
100
84
400
310
260
1,000
780
660
6
8
8
2,900
1,800
3,400
20

77
31
24
240
95
73
600
240
190

940
729
8
8
10
5,600
7,600
4,000
20
18
62
56
31
160
140
78
610
560
310


960
10
10
10
7,200
11,000
15,000
24
20
18
60
51
46
240
200
180
740
630
571
12
12
12
7,300
13,000
20,000
31
24
20
120
94
79
380
300
250
940
720
610
12
15
15
26,000
15,000
25,000
18

72
40
31
230
130
96
500
310
240
15
15
38,000
50,000
26
24
81
74
200
180
 
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm.
a.   The developed length shall be measured from the vent connection to the open air.
b.   Not permitted for water closets.
(Amend Coun. J. 3-27-02, p. 82090, § 3; Amend Coun. J. 10-14-21, p. 37722, Art. IX, § 7)