Loading...
The waste piping and trap in a combination waste and an end vented (both ends) system shall be a minimum of 4 inch (100 mm) diameter. The waste piping and trap shall be at least two pipe increments larger than the pipe size required and at least two pipe increments larger than any fixture/appurtenance discharge tailpiece.
A branch more than 15 feet (4.57 m) in length shall be separately vented. The minimum area of any vent installed in a combination waste and vent system shall be one-half the diameter of the drain pipe served, but not less than the minimum indicated in Table 18-29-916.1.
Loading...