18-29-908.1 Individual vent as common vent.
   An individual vent is permitted to vent two traps or trapped fixtures as a common vent. The traps or trapped fixtures being common vented shall be located on the same floor level.
18-29-908.2 Connection at the same level.
   Where the fixture drains being common vented connect at the same level, the vent connection shall be at the interconnection of the fixture drains.
18-29-908.3 Connection of different levels.
   Connections at different levels shall not be permitted.
18-29-909 Deliberately omitted.
18-29-910 Deliberately omitted.
18-29-911 Deliberately omitted.
18-29-912 Combination Drain and Vent System.
18-29-912.1 Type of fixtures.
   A combination drain and vent system shall not serve fixtures other than floor drains receiving only clear water wastes. Appurtenances receiving large quantities or surges of water shall not be discharged to a combination waste and vent.