Where the rooftop is to be used as a promenade, restaurant, bar, sunbathing deck, observation deck or for similar purposes (occupiable rooftop), open vent pipes shall terminate not less than 7 feet (2134 mm) above the highest walking surface located within 10 feet (3048 mm) horizontally.
(Added Coun. J. 10-14-21, p. 37722, Art. IX, § 3)
Vent terminals extending through the wall shall terminate not less than 10 feet (3048 mm) from the nearest abutting lot line and 10 feet (3048 mm) above the highest adjacent grade within 10 feet (3048 mm) horizontally of the vent terminal. Vent terminals shall not terminate under the overhang of a structure with soffit vents. Sidewall vent terminals shall be protected to prevent birds and rodents from entering and blocking the vent opening.
(Added Coun. J. 10-14-21, p. 37722, Art. IX, § 3; Amend Coun. J. 12-14-22, p. 58278, Art. VI, § 18)
An open vent terminal from a drainage system shall not be located directly beneath a door, openable window, overhead or other ventilating intake opening of the building or of an adjacent building, nor shall any such vent terminals be within 10 feet (3.05 m) horizontally of such an opening unless the vent terminal is at least 3 feet (914 mm) above the top of such opening.
(Amend Coun. J. 10-14-21, p. 37722, Art. IX, § 3)