18-29-904.5 Location of vent terminal.
   An open vent terminal from a drainage system shall not be located directly beneath a door, openable window, overhead or other ventilating intake opening of the building or of an adjacent building, nor shall any such vent terminals be within 10 feet (3.05 m) horizontally of such an opening unless the vent terminal is at least 3 feet (914 mm) above the top of such opening.