Skip to code content (skip section selection)
Compare to:
Chicago Overview
Prior Chicago Building Code
BUILDING CODE AND RELATED EXCERPTS OF THE MUNICIPAL CODE OF CHICAGO
DIVISION 1 - ADMINISTRATION
DIVISION 2 - DEFINITIONS
DIVISION 3 - USE AND OCCUPANCY CLASSIFICATIONS
DIVISION 4 - SPECIAL DETAILED REQUIREMENTS BASED ON USE AND OCCUPANCY
DIVISION 5 - GENERAL BUILDING HEIGHTS AND AREAS
DIVISION 6 - TYPES OF CONSTRUCTION
DIVISION 7 - FIRE-RESISTANCE-RATED CONSTRUCTION
DIVISION 8 - INTERIOR FINISHES (NA)
DIVISION 9 - FIRE PROTECTION SYSTEMS
CHAPTER 15-16 FIRE PROTECTION EQUIPMENT
ARTICLE I. FIRE PROTECTION (15-16-010 et seq.)
ARTICLE II. FIRE PROTECTION EQUIPMENT (15-16-170 et seq.)
PART 1. STANDARD SPRINKLER SYSTEMS (15-16-170 et seq.)
PART 2. STANDARD FIRE EXTINGUISHERS (15-16-620 et seq.)
PART 3. STANDARD INSIDE STANDPIPE SYSTEMS (15-16-710 et seq.)
15-16-710 Definition of system.
15-16-720 Where standpipe system required.
15-16-730 Other definitions.
15-16-740 Permit fees.
15-16-750 Installation certification.
15-16-760 Types of systems.
15-16-770 Sources of water supply.
15-16-780 Fire pumps.
15-16-790 Use for other services.
15-16-800 Fire pump requirements.
15-16-810 Pumps supplied from city main.
15-16-820 Fire pump auxiliary equipment.
15-16-830 Pressure-control devices.
15-16-840 Pump suction piping.
15-16-850 Requirements for auxiliary drive.
15-16-860 Piping arrangement.
15-16-870 Piping design.
15-16-880 Piping drains.
15-16-890 Risers.
15-16-900 Arrangement of risers.
15-16-910 Location of risers.
15-16-920 Size of risers.
15-16-930 Fire department hose connections.
15-16-940 Hose valve design.
15-16-950 Hand hose connections.
15-16-960 Hand hose valve design.
15-16-970 Equipment at hose outlets.
15-16-971 Identification of hose valves.
15-16-980 Pressure reducing devices.
15-16-990 Domestic use prohibited.
15-16-1000 Multiple systems.
15-16-1010 Express risers.
15-16-1020 Siamese connections required.
15-16-1030 Check valves for siamese.
15-16-1040 Arrangement of siamese connections.
15-16-1050 Valves.
15-16-1060 Reserved.
15-16-1070 Test manifold and wall hydrants.
15-16-1080 Gauges.
15-16-1090 Painting and identification of pipe.
15-16-1100 Protection against freezing.
15-16-1110 Dry pipe system.
15-16-1115 Manual dry pipe system.
15-16-1120 Buildings under construction.
15-16-1130 Buildings being demolished.
15-16-1140 Alarms.
15-16-1150 Test method.
15-16-1160 Annual test required.
15-16-1170 Inspection.
15-16-1180 Retroactivity.
15-16-1190 Existing buildings.
PART 4. STANDARD FIRE ALARM SYSTEMS (15-16-1200 et seq.)
PART 5. SPRINKLER SYSTEMS - ADDITIONAL PROVISIONS (15-16-1520 et seq.)
DIVISION 10 - MEANS OF EGRESS
DIVISION 11 - ACCESSIBILITY
DIVISION 12 - INTERIOR ENVIRONMENT
DIVISION 13 - ENERGY EFFICIENCY AND ENVIRONMENTAL PROTECTION
DIVISION 14 - EXTERIOR WALLS (NA)
DIVISION 15 - ROOF ASSEMBLIES AND ROOFTOP STRUCTURES (NA)
DIVISION 16 - STRUCTURAL DESIGN
DIVISION 17 - STRUCTURAL TESTS AND SPECIAL INSPECTIONS
DIVISION 18 - SOILS AND FOUNDATIONS
DIVISION 19 - CONCRETE
DIVISION 20 - ALUMINUM (NA)
DIVISION 21 - MASONRY
DIVISION 22 - STEEL
DIVISION 23 - WOOD
DIVISION 24 - GLASS AND GLAZING (NA)
DIVISION 25 - GYPSUM BOARD AND PLASTER (NA)
DIVISION 26 - PLASTIC (NA)
DIVISION 27 - ELECTRICAL
DIVISION 28 - MECHANICAL SYSTEMS
DIVISION 29 - PLUMBING SYSTEMS
DIVISION 30 - ELEVATORS AND CONVEYING SYSTEMS
DIVISION 31 - SPECIAL CONSTRUCTION (NA)
DIVISION 32 - ENCROACHMENTS INTO THE PUBLIC RIGHT-OF-WAY
DIVISION 33 - SAFEGUARDS DURING CONSTRUCTION
DIVISION 34 - EXISTING STRUCTURES
DIVISION 35 - REFERENCED STANDARDS

You are viewing an archived code

Loading...
15-16-1170  Inspection.
   It shall be the duty of the fire commissioner to cause an inspection to be made of all standpipe systems at least once every year by an independent contractor licensed under the Illinois Fire Sprinkler Contractor Licensing Act. Such inspections shall be schedule with, and may be overseen by or in the presence of, the fire commissioner. If such inspection discloses any violations of, or variation from, the requirements of this Code pertaining to standpipes or standpipe systems, or any defective conditions which would handicap the operation of the standpipe system, notice shall be sent to the owner or agent in control of the building containing such standpipe system to remove or correct such defective conditions within such time as shall be set forth in said notice. It shall be the duty of the building owner to pay the comptroller an inspection fee of $50.00 for each standpipe, other than a manual dry standpipe, inspected in connection with such annual inspection.
(Prior code § 91-98; Amend Coun. J. 12-15-92, p. 27387; Amend Coun. J. 10-30-96, p. 31261, § 1; Amend Coun. J. 11-16-11, p. 13798, Art. I, § 11; Amend Coun. J. 5-18-16, p. 24131, § 131; Amend Coun. J. 1-23-19, p. 94952, Art. II, § 4)
15-16-1180  Retroactivity.
   The provisions of Sections 15-16-710 to 15-16-1180, both inclusive, shall apply to existing buildings including pre-ordinance buildings and buildings hereafter constructed but no existing building shall be required to make any alteration in its standard inside standpipe system, if originally installed in accordance with approved plans and permits, by reason of amendments to this code adopted after passage of this ordinance.
(Prior code §  91-99; Amend Coun. J. 10-30-96, p. 31261, § 1)
15-16-1190  Existing buildings.
   Existing buildings which require standpipes under Section 15-16-090(d) only, shall use the following design requirements to comply with this code:
   1.   Such building is equipped with one four-inch inside standpipe riser where the ground area of the building does not exceed 20,000 square feet and an additional four-inch inside standpipe riser where the ground area of the building is over 20,000 square feet.
   2.   Each such standpipe riser is equipped, in the basement and on each floor level, with a one and one- half inch connection with 75 feet of hose attached, and also a two and one-half inch valve and connection provided with standard Chicago fire department thread.
   3.   In such buildings, equipped throughout with an approved system of automatic sprinklers, sprinkler risers, which are not less than four inches in diameter, may be used in lieu of inside standpipe risers.
   4.   Such building is equipped with a siamese pumper connection.
   5.   The standpipe or sprinkler risers are maintained wet at all times.
   6.   The piping, fittings and equipment used in connection with such risers shall be capable of withstanding the water pressure required for fire extinguishment.
   7.   The location and equipment of such risers are approved by the fire commissioner.
(Prior code § 91-100; Amend Coun. J. 10-30-96, p. 31261, § 1; Amend Coun. J. 5-18-16, p. 24131, § 132)
PART 4.  STANDARD FIRE ALARM SYSTEMS (15-16-1200 et seq.)
15-16-1200  Definition of system.
   The words “standard fire alarm system” where used in this Code, are hereby defined to mean a manually operated fire alarm system equipped with automatic detectors, if required, as hereinafter defined. Such system shall be installed in a building for the purpose of notifying the occupants and/or employees of said building of conditions due to fire or other causes which necessitate that the building be vacated immediately by the occupants. All equipment and devices used in the installation of such a system shall be tested by and bear the label of approval of a nationally recognized testing laboratory acceptable to the fire commissioner and the bureau of electrical inspection. The workmanship, equipment and quality of installation shall conform to the requirements of Title 14E.
(Prior code § 91-101; Amend Coun. J. 5-18-16, p. 24131, § 133; Amend Coun. J. 9-6-17, p. 55278, Art. II, § 50)
Loading...