Skip to code content (skip section selection)
Compare to:
Chicago Overview
Prior Chicago Building Code
BUILDING CODE AND RELATED EXCERPTS OF THE MUNICIPAL CODE OF CHICAGO
DIVISION 1 - ADMINISTRATION
DIVISION 2 - DEFINITIONS
DIVISION 3 - USE AND OCCUPANCY CLASSIFICATIONS
DIVISION 4 - SPECIAL DETAILED REQUIREMENTS BASED ON USE AND OCCUPANCY
DIVISION 5 - GENERAL BUILDING HEIGHTS AND AREAS
DIVISION 6 - TYPES OF CONSTRUCTION
DIVISION 7 - FIRE-RESISTANCE-RATED CONSTRUCTION
DIVISION 8 - INTERIOR FINISHES (NA)
DIVISION 9 - FIRE PROTECTION SYSTEMS
CHAPTER 15-16 FIRE PROTECTION EQUIPMENT
ARTICLE I. FIRE PROTECTION (15-16-010 et seq.)
ARTICLE II. FIRE PROTECTION EQUIPMENT (15-16-170 et seq.)
PART 1. STANDARD SPRINKLER SYSTEMS (15-16-170 et seq.)
PART 2. STANDARD FIRE EXTINGUISHERS (15-16-620 et seq.)
PART 3. STANDARD INSIDE STANDPIPE SYSTEMS (15-16-710 et seq.)
15-16-710 Definition of system.
15-16-720 Where standpipe system required.
15-16-730 Other definitions.
15-16-740 Permit fees.
15-16-750 Installation certification.
15-16-760 Types of systems.
15-16-770 Sources of water supply.
15-16-780 Fire pumps.
15-16-790 Use for other services.
15-16-800 Fire pump requirements.
15-16-810 Pumps supplied from city main.
15-16-820 Fire pump auxiliary equipment.
15-16-830 Pressure-control devices.
15-16-840 Pump suction piping.
15-16-850 Requirements for auxiliary drive.
15-16-860 Piping arrangement.
15-16-870 Piping design.
15-16-880 Piping drains.
15-16-890 Risers.
15-16-900 Arrangement of risers.
15-16-910 Location of risers.
15-16-920 Size of risers.
15-16-930 Fire department hose connections.
15-16-940 Hose valve design.
15-16-950 Hand hose connections.
15-16-960 Hand hose valve design.
15-16-970 Equipment at hose outlets.
15-16-971 Identification of hose valves.
15-16-980 Pressure reducing devices.
15-16-990 Domestic use prohibited.
15-16-1000 Multiple systems.
15-16-1010 Express risers.
15-16-1020 Siamese connections required.
15-16-1030 Check valves for siamese.
15-16-1040 Arrangement of siamese connections.
15-16-1050 Valves.
15-16-1060 Reserved.
15-16-1070 Test manifold and wall hydrants.
15-16-1080 Gauges.
15-16-1090 Painting and identification of pipe.
15-16-1100 Protection against freezing.
15-16-1110 Dry pipe system.
15-16-1115 Manual dry pipe system.
15-16-1120 Buildings under construction.
15-16-1130 Buildings being demolished.
15-16-1140 Alarms.
15-16-1150 Test method.
15-16-1160 Annual test required.
15-16-1170 Inspection.
15-16-1180 Retroactivity.
15-16-1190 Existing buildings.
PART 4. STANDARD FIRE ALARM SYSTEMS (15-16-1200 et seq.)
PART 5. SPRINKLER SYSTEMS - ADDITIONAL PROVISIONS (15-16-1520 et seq.)
DIVISION 10 - MEANS OF EGRESS
DIVISION 11 - ACCESSIBILITY
DIVISION 12 - INTERIOR ENVIRONMENT
DIVISION 13 - ENERGY EFFICIENCY AND ENVIRONMENTAL PROTECTION
DIVISION 14 - EXTERIOR WALLS (NA)
DIVISION 15 - ROOF ASSEMBLIES AND ROOFTOP STRUCTURES (NA)
DIVISION 16 - STRUCTURAL DESIGN
DIVISION 17 - STRUCTURAL TESTS AND SPECIAL INSPECTIONS
DIVISION 18 - SOILS AND FOUNDATIONS
DIVISION 19 - CONCRETE
DIVISION 20 - ALUMINUM (NA)
DIVISION 21 - MASONRY
DIVISION 22 - STEEL
DIVISION 23 - WOOD
DIVISION 24 - GLASS AND GLAZING (NA)
DIVISION 25 - GYPSUM BOARD AND PLASTER (NA)
DIVISION 26 - PLASTIC (NA)
DIVISION 27 - ELECTRICAL
DIVISION 28 - MECHANICAL SYSTEMS
DIVISION 29 - PLUMBING SYSTEMS
DIVISION 30 - ELEVATORS AND CONVEYING SYSTEMS
DIVISION 31 - SPECIAL CONSTRUCTION (NA)
DIVISION 32 - ENCROACHMENTS INTO THE PUBLIC RIGHT-OF-WAY
DIVISION 33 - SAFEGUARDS DURING CONSTRUCTION
DIVISION 34 - EXISTING STRUCTURES
DIVISION 35 - REFERENCED STANDARDS

You are viewing an archived code

Loading...
15-16-971  Identification of hose valves.
   Where the two and one-half inch valve is located in a cabinet, such cabinet shall bear the words “Fire Hose Valve” in letters not less than three inches high of a color which contrasts with the color of the cabinet.
(Added Coun. J. 10-30-96, p. 31261, § 1)
15-16-980  Pressure reducing devices.
   Where the pressure at nozzles is more than 65 pounds per square inch, the one and one-half inch hose valve shall be provided with a device or disc to limit the pressure to 90 pounds so that the nozzle can be safely handled by one person.
(Prior code §  91-79; Amend Coun. J. 10-30-96, p. 31261, § 1)
15-16-990  Domestic use prohibited.
   Connections for domestic supply shall not be taken from any part on the inside standpipe system.
(Prior code §  91-80; Amend Coun. J. 10-30-96, p. 31261, § 1)
15-16-1000  Multiple systems.
   An interior standpipe system required in a building, the top floor of which is more than 275 feet above grade, exclusive of space used for sprinkler, elevator, ventilation and other building machinery, shall be separated into two or more zones, each of which shall include a fire pump, pressure maintenance pump, and all other equipment and piping necessary for a complete inside standpipe installation. The lowest system shall serve the portion up to and including the story the floor of which is 275 feet or less above grade. Above 275 feet systems shall be provided to serve zones of not more than 20 stories each.
(Prior code §  91-81; Amend Coun. J. 10-30-96, p. 31261, § 1)
15-16-1010  Express risers.
   In a building having a top floor which is more than 275 feet above grade, individual zones, as required by this Code, shall be supplied by two or more separate risers from the zone fire pump located in the lowest story of the building, known as an express riser, except that the number of express risers shall not exceed the number of risers serving that zone; or by individual fire pumps located on the lowest floor of each zone taking suction under head from a tank automatically filled by two or more risers from the adjacent lower zone. Such a tank shall have a capacity sufficient to supply the largest pump in the zone at its rated capacity for at least 30 minutes but not less than 10,000 gallons.
(Prior code §  91-82; Amend Coun. J. 10-30-96, p. 31261, § 1)
15-16-1020  Siamese connections required.
   At least one siamese connection shall be provided on each street exposure to a limit of two street exposures, except that one siamese connection will be permitted in the case of two adjacent street exposures whose combined length is not greater than 250 feet. If any exposure is more than 250 feet long, there shall be two siamese connections for such exposure no closer than 200 feet apart. All siamese connections shall be located not less than 12 inches nor more than five feet above grade at the building line. Hose threads shall fit the couplings of the city fire department; they shall be provided with caps securely attached to the connection.
(Prior code §  91-83; Amend Coun. J. 10-30-96, p. 31261, § 1)
15-16-1030  Check valves for siamese.
   Each siamese connection shall be connected direct to the system through a four inch pipe with a straightway or silent type check valve in the connections; there shall be no other valves in the pipe connection. Each connection shall be drained between the check valve and the outside hose coupling.
(Prior code §  91-84; Amend Coun. J. 10-30-96, p. 31261, § 1)
15-16-1040  Arrangement of siamese connections.
   Where the inside standpipe system has a single riser, the siamese connection shall be connected on the system side of the gate valve in the riser. Where the system has two or more risers, the siamese connections shall be connected on the supply side of the gate valve so that with any riser shutoff the supply will be into the remaining risers. All piping shall be arranged to connect into the system by the most direct route as required by this code.
   At each siamese connection, there shall be provided a flat square metallic plate attached to the siamese connection or the building near the connection on which shall be placed the word “Standpipe” if there is a single system, or the words “Low Level Standpipe: Basement (Or Subbasement): to Floor” or “High Level Standpipe: Floor to Floor” or other suitable marking if there is more than one system.
   When a siamese connection serves both automatic sprinklers and a standpipe system the siamese connection shall be so identified.
(Prior code §  91-85; Amend Coun. J. 10-30-96, p. 31261, § 1)
15-16-1050  Valves.
   All parts of the system shall be provided with indicating valves so that any portion can be taken out of service for repairs or in an emergency without interfering with the operation of the remainder of the system. Each system shall be provided with a gate valve so located as to control all sources of water supply except siamese connections. All valves in connections to water supply and from main to risers shall be outside screw and yoke pattern or other indicating type.
   Check valves shall be installed in all sources of water supply including both suction and discharge side of the fire pump; they shall be straightway pattern or silent type installed in horizontal or vertical piping according to the valve's listing. A gate valve shall be installed on each side of each check valve unless otherwise noted.
   All valves shall be rated for pressures not less than the maximum pressure developed at the point in the system where the valve is installed including the shutoff pressure of the fire pump.
   All valves, including test and drain valves, shall have a durable sign attached indicating their function or area controlled.
   A diagram drawn to scale showing the city connection, fire pump, siamese connections, standpipe main, risers and all valves shall be permanently posted in a conspicuous location in the pump room.
   Gate valves controlling water supplies for main and risers shall be located where readily accessible. Valves shall not be located within concealed spaces.
   All valves in mains and risers shall be secured open.
(Prior code §  91-86; Amend Coun. J. 10-30-96, p. 31261, § 1)
Loading...