Each standpipe system supplied by a fire pump shall be provided with a discharge test manifold or wall hydrant having one two and one-half inch individually valved hose connection for each 250 gpm of rated pump capacity. The discharge test manifold shall be located on an outside wall in allocation which will permit the safe discharge and drainage of water.
(Prior code § 91-88; Amend Coun. J. 10-30-96, p. 31261, § 1)