If the supply is taken from a city main, the pumping unit shall be designed to develop its full capacity at its rated pressure; provided, however, that if it is the source of supply for an upper standpipe system in a building having multiple systems, it may take its suction from the discharge of the fire pump for the system immediately below, but all piping shall be arranged so that pressure from the higher pressure system cannot be delivered to the lower pressure system.
(Prior code § 91-62; Amend Coun. J. 10-30-96, p. 31261, § 1)