At least one siamese connection shall be provided on each street exposure to a limit of two street exposures, except that one siamese connection will be permitted in the case of two adjacent street exposures whose combined length is not greater than 250 feet. If any exposure is more than 250 feet long, there shall be two siamese connections for such exposure no closer than 200 feet apart. All siamese connections shall be located not less than 12 inches nor more than five feet above grade at the building line. Hose threads shall fit the couplings of the city fire department; they shall be provided with caps securely attached to the connection.
(Prior code § 91-83; Amend Coun. J. 10-30-96, p. 31261, § 1)