15-16-860  Piping arrangement.
   The piping system shall consist of mains from the sources of supply, risers, branches and other piping to the hose outlets; it shall include the connection from the city main or other source to the suction of the pump. In addition to the source of supply inside of the building, there shall be one or more siamese connections at points outside of the building directly connected to the main for the use of the city fire department. The standpipe main from the source of supply shall be located in the lowest story of the building and shall be completely looped, without dead ends, when the building height exceeds 500 feet.
(Prior code §  91-67; Amend Coun. J. 10-30-96, p. 31261, § 1)
15-16-870  Piping design.
   All piping used in standpipe systems shall be of materials and pressure ratings as specified in Sections 2-2.1 to 2-2.4, both inclusive, of N.F.P.A. Standard 14, Standard for the Installation of Standpipe and Hose Systems, 1993 Edition. Pipe fittings used in standpipe systems shall meet the requirements of Sections 2-3.1 and 2-3.3 of the above referenced N.F.P.A. Standard 14.
(Prior code §  91-68; Amend Coun. J. 10-30-96, p. 31261, § 1)
15-16-880  Piping drains.
   All piping shall be provided with drains. Each riser shall be provided with a drain valve not less than two inches in size at the lowest point on the system side of the riser control valve. A valve used for a hose connection may be used to drain a standpipe riser when it is located at the low point of a riser. Drains shall discharge at a point where a floor drain or other adequate means exist to allow safe discharge and removal of water drained from the system.
   Drain valves shall be identified by a durable sign indicating the floors or zone served.
(Prior code §  91-69; Amend Coun. J. 10-30-96, p. 31261, § 1)
15-16-890  Risers.
   Connected to the standpipe main there shall be one or more independent standpipe risers to supply all the hose outlets in the building.
(Prior code §  91-70; Amend Coun. J. 10-30-96, p. 31261, § 1)
15-16-900  Arrangement of risers.
   The number of risers shall be determined by the floor area of the building; they shall be arranged so that all portions of the floor in all stories can be protected by fire hose not more than 100 feet long if the hose valve is located in a properly enclosed stairwell, and 75 feet if not; this length of hose shall extend to within 30 feet of the outside wall if the space is not divided into rooms or into the room farthest from the standpipe to which the hose is connected if the space is so divided. In spaces not subdivided by permanent partitions, allowance shall be made for future intervening furnishings and work station cubicles.
(Prior code §  91-71; Amend Coun. J. 10-30-96, p. 31261, § 1)