Skip to code content (skip section selection)
Compare to:
Chicago Overview
Prior Chicago Building Code
BUILDING CODE AND RELATED EXCERPTS OF THE MUNICIPAL CODE OF CHICAGO
DIVISION 1 - ADMINISTRATION
DIVISION 2 - DEFINITIONS
DIVISION 3 - USE AND OCCUPANCY CLASSIFICATIONS
DIVISION 4 - SPECIAL DETAILED REQUIREMENTS BASED ON USE AND OCCUPANCY
DIVISION 5 - GENERAL BUILDING HEIGHTS AND AREAS
DIVISION 6 - TYPES OF CONSTRUCTION
DIVISION 7 - FIRE-RESISTANCE-RATED CONSTRUCTION
DIVISION 8 - INTERIOR FINISHES (NA)
DIVISION 9 - FIRE PROTECTION SYSTEMS
CHAPTER 15-16 FIRE PROTECTION EQUIPMENT
ARTICLE I. FIRE PROTECTION (15-16-010 et seq.)
ARTICLE II. FIRE PROTECTION EQUIPMENT (15-16-170 et seq.)
PART 1. STANDARD SPRINKLER SYSTEMS (15-16-170 et seq.)
PART 2. STANDARD FIRE EXTINGUISHERS (15-16-620 et seq.)
PART 3. STANDARD INSIDE STANDPIPE SYSTEMS (15-16-710 et seq.)
15-16-710 Definition of system.
15-16-720 Where standpipe system required.
15-16-730 Other definitions.
15-16-740 Permit fees.
15-16-750 Installation certification.
15-16-760 Types of systems.
15-16-770 Sources of water supply.
15-16-780 Fire pumps.
15-16-790 Use for other services.
15-16-800 Fire pump requirements.
15-16-810 Pumps supplied from city main.
15-16-820 Fire pump auxiliary equipment.
15-16-830 Pressure-control devices.
15-16-840 Pump suction piping.
15-16-850 Requirements for auxiliary drive.
15-16-860 Piping arrangement.
15-16-870 Piping design.
15-16-880 Piping drains.
15-16-890 Risers.
15-16-900 Arrangement of risers.
15-16-910 Location of risers.
15-16-920 Size of risers.
15-16-930 Fire department hose connections.
15-16-940 Hose valve design.
15-16-950 Hand hose connections.
15-16-960 Hand hose valve design.
15-16-970 Equipment at hose outlets.
15-16-971 Identification of hose valves.
15-16-980 Pressure reducing devices.
15-16-990 Domestic use prohibited.
15-16-1000 Multiple systems.
15-16-1010 Express risers.
15-16-1020 Siamese connections required.
15-16-1030 Check valves for siamese.
15-16-1040 Arrangement of siamese connections.
15-16-1050 Valves.
15-16-1060 Reserved.
15-16-1070 Test manifold and wall hydrants.
15-16-1080 Gauges.
15-16-1090 Painting and identification of pipe.
15-16-1100 Protection against freezing.
15-16-1110 Dry pipe system.
15-16-1115 Manual dry pipe system.
15-16-1120 Buildings under construction.
15-16-1130 Buildings being demolished.
15-16-1140 Alarms.
15-16-1150 Test method.
15-16-1160 Annual test required.
15-16-1170 Inspection.
15-16-1180 Retroactivity.
15-16-1190 Existing buildings.
PART 4. STANDARD FIRE ALARM SYSTEMS (15-16-1200 et seq.)
PART 5. SPRINKLER SYSTEMS - ADDITIONAL PROVISIONS (15-16-1520 et seq.)
DIVISION 10 - MEANS OF EGRESS
DIVISION 11 - ACCESSIBILITY
DIVISION 12 - INTERIOR ENVIRONMENT
DIVISION 13 - ENERGY EFFICIENCY AND ENVIRONMENTAL PROTECTION
DIVISION 14 - EXTERIOR WALLS (NA)
DIVISION 15 - ROOF ASSEMBLIES AND ROOFTOP STRUCTURES (NA)
DIVISION 16 - STRUCTURAL DESIGN
DIVISION 17 - STRUCTURAL TESTS AND SPECIAL INSPECTIONS
DIVISION 18 - SOILS AND FOUNDATIONS
DIVISION 19 - CONCRETE
DIVISION 20 - ALUMINUM (NA)
DIVISION 21 - MASONRY
DIVISION 22 - STEEL
DIVISION 23 - WOOD
DIVISION 24 - GLASS AND GLAZING (NA)
DIVISION 25 - GYPSUM BOARD AND PLASTER (NA)
DIVISION 26 - PLASTIC (NA)
DIVISION 27 - ELECTRICAL
DIVISION 28 - MECHANICAL SYSTEMS
DIVISION 29 - PLUMBING SYSTEMS
DIVISION 30 - ELEVATORS AND CONVEYING SYSTEMS
DIVISION 31 - SPECIAL CONSTRUCTION (NA)
DIVISION 32 - ENCROACHMENTS INTO THE PUBLIC RIGHT-OF-WAY
DIVISION 33 - SAFEGUARDS DURING CONSTRUCTION
DIVISION 34 - EXISTING STRUCTURES
DIVISION 35 - REFERENCED STANDARDS

You are viewing an archived code

Loading...
15-16-690  Licensing of servicemen.
   Every fire extinguisher serviceman shall be licensed in accordance with the provisions of Chapter 15-4.
(Prior code §  91-52)
15-16-700  Violation – Penalty.
   Any person who violates any provisions of Sections 15-16-620 to 15-16-690 shall be fined not more than $200.00 for each offense.
(Prior code §  91-52.1)
PART 3.  STANDARD INSIDE STANDPIPE SYSTEMS (15-16-710 et seq.)
15-16-710  Definition of system.
   A standard inside standpipe system, for the purposes of this code, is hereby defined as a system of piping installed in a building with hose outlets located in such a manner that water can be discharged in streams through hose attached to such hose outlets, for the purpose of extinguishing a fire and so protecting the building and its contents, with pumps, tanks and other equipment necessary to provide an adequate supply of water to the hose outlets. Every inside standpipe system required by this code shall comply with all the requirements hereinafter enumerated for such a system. Fire pumps, air compressors, valves, hose and all other equipment installed in connection with a standard inside standpipe system, except for pressure maintenance pumps, shall be of a make, type and design which has been tested and listed by and which bears the label of a product testing laboratory which regularly tests fire protection equipment and conducts periodic inspection of the production of listed equipment or materials.
(Prior code §  91-53; Amend Coun. J. 10-30-96, p. 31261, § 1)
15-16-720  Where standpipe system required.
   Standard inside standpipe systems complying with the requirements of Sections 15-16-710 to 15-16-1190 shall be provided in all buildings exceeding 80 feet in height with the exceptions listed in Section 15-16-090(d) of this code.
(Prior code §  91-53.1; Amend Coun. J. 10-30-96, p. 31261, § 1)
15-16-730  Other definitions.
   For the purpose of Part 3 of Article II of this chapter, other additional terms used hereinafter are hereby defined as follows:
   “Fire pump.” A device used for supplying water to an inside standpipe system at the pressure required by the system.
   “Pressure maintenance pump.” A small centrifugal pump under automatic control used to maintain pressure on the system to avoid frequent operation of the fire pump.
   “Siamese connections.” A two or other multiple inlet fitting installed on the outside of a building and connected to the standpipe main of an inside standpipe system for the use of the fire department only, to supply water to the system.
   Water supply piping in an inside standpipe system. The sections of the piping are:
      (1)   Pump suction. The pipe which conveys the water from the city main or other source of supply to the fire pump.
      (2)   Standpipe main. The pipe which conveys the water from the fire pump to the standpipe risers.
      (3)   Standpipe risers, or standpipe. A vertical pipe which extends upward through a building and conveys the water from the standpipe main to the hose outlets
   “Zone.” A portion of a standpipe system which supplies water to a number of consecutive stories in a building.
(Prior code §  91-54; Amend Coun. J. 10-30-96, p. 31261, § 1)
15-16-740  Permit fees.
   Before the installation or alteration of an inside standpipe system required by the provisions of this Code, a plan, setting forth all essential details of the inside standpipe system, shall be submitted to the Fire Commissioner. Such plan shall include hydraulic calculations. Upon finding that the plan conforms to the requirements of the Code and after payment of standpipe permit fees hereinafter specified, said plan shall be approved by the Fire Commissioner.
   The fees charged in connection with an inside standpipe system shall be as follows:
   If the plan does not conform to the requirements of the Code and a revised plan is submitted, the fee for each revised plan submission shall be $200.00. For the approval of the standpipe plan and the initial inspection of the inside standpipe system required by the provisions of this code, a fee of $300.00 shall be charged for the first standpipe riser and $100.00 for each additional standpipe riser. For the test of a fire pump used in connection with an inside standpipe system, a fee of $31.50 for each unit of pumping capacity of 50 gallons per minute or fraction thereof shall be charged with a minimum permit fee of $315.00.
(Prior code § 91-55; Amend Coun. J. 12-15-92, p. 27387; Amend Coun. J. 10-30-96, p. 31261, § 1; Amend Coun. J. 5-18-16, p. 24131, § 126; Amend Coun. J. 11-14-18, p. 90376, Art. V, § 5)
15-16-750  Installation certification.
   After completing a standpipe system installation, the contractor shall submit to the fire commissioner a written certification that the system has been installed in accordance with the plans approved by the fire commissioner.
(Prior code § 91-56; Amend Coun. J. 10-30-96, p. 31261, § 1; Amend Coun. J. 5-18-16, p. 24131, § 127)
15-16-760  Types of systems.
   Inside standpipe systems may be:
   (a)   Wet, in which the pipes are kept filled with water.
   (b)   Dry, in which a portion of the piping nearest the hose outlets normally is kept filled with air under pressure and so arranged that the operation of an outlet will automatically admit water to the system. Dry systems shall be used only when a wet system is impractical on account of a deficiency of heat in the area in which piping is located.
   (c)   Manual dry, in which a permanent water supply is not attached to the system, and which requires water from a Fire Department pumper to be pumped into the system through the Fire Department connection in order to meet the system demand. Manual dry systems shall be used only as provided in Section 15-16-090(a)(5).
(Prior code § 91-57; Amend Coun. J. 10-30-96, p. 31261, § 1; Amend Coun. J. 1-23-19, p. 94952, Art. II, § 2)
Loading...