Skip to code content (skip section selection)
Compare to:
Chicago Overview
Prior Chicago Building Code
BUILDING CODE AND RELATED EXCERPTS OF THE MUNICIPAL CODE OF CHICAGO
DIVISION 1 - ADMINISTRATION
DIVISION 2 - DEFINITIONS
DIVISION 3 - USE AND OCCUPANCY CLASSIFICATIONS
DIVISION 4 - SPECIAL DETAILED REQUIREMENTS BASED ON USE AND OCCUPANCY
DIVISION 5 - GENERAL BUILDING HEIGHTS AND AREAS
DIVISION 6 - TYPES OF CONSTRUCTION
DIVISION 7 - FIRE-RESISTANCE-RATED CONSTRUCTION
DIVISION 8 - INTERIOR FINISHES (NA)
DIVISION 9 - FIRE PROTECTION SYSTEMS
CHAPTER 15-16 FIRE PROTECTION EQUIPMENT
ARTICLE I. FIRE PROTECTION (15-16-010 et seq.)
ARTICLE II. FIRE PROTECTION EQUIPMENT (15-16-170 et seq.)
PART 1. STANDARD SPRINKLER SYSTEMS (15-16-170 et seq.)
PART 2. STANDARD FIRE EXTINGUISHERS (15-16-620 et seq.)
PART 3. STANDARD INSIDE STANDPIPE SYSTEMS (15-16-710 et seq.)
15-16-710 Definition of system.
15-16-720 Where standpipe system required.
15-16-730 Other definitions.
15-16-740 Permit fees.
15-16-750 Installation certification.
15-16-760 Types of systems.
15-16-770 Sources of water supply.
15-16-780 Fire pumps.
15-16-790 Use for other services.
15-16-800 Fire pump requirements.
15-16-810 Pumps supplied from city main.
15-16-820 Fire pump auxiliary equipment.
15-16-830 Pressure-control devices.
15-16-840 Pump suction piping.
15-16-850 Requirements for auxiliary drive.
15-16-860 Piping arrangement.
15-16-870 Piping design.
15-16-880 Piping drains.
15-16-890 Risers.
15-16-900 Arrangement of risers.
15-16-910 Location of risers.
15-16-920 Size of risers.
15-16-930 Fire department hose connections.
15-16-940 Hose valve design.
15-16-950 Hand hose connections.
15-16-960 Hand hose valve design.
15-16-970 Equipment at hose outlets.
15-16-971 Identification of hose valves.
15-16-980 Pressure reducing devices.
15-16-990 Domestic use prohibited.
15-16-1000 Multiple systems.
15-16-1010 Express risers.
15-16-1020 Siamese connections required.
15-16-1030 Check valves for siamese.
15-16-1040 Arrangement of siamese connections.
15-16-1050 Valves.
15-16-1060 Reserved.
15-16-1070 Test manifold and wall hydrants.
15-16-1080 Gauges.
15-16-1090 Painting and identification of pipe.
15-16-1100 Protection against freezing.
15-16-1110 Dry pipe system.
15-16-1115 Manual dry pipe system.
15-16-1120 Buildings under construction.
15-16-1130 Buildings being demolished.
15-16-1140 Alarms.
15-16-1150 Test method.
15-16-1160 Annual test required.
15-16-1170 Inspection.
15-16-1180 Retroactivity.
15-16-1190 Existing buildings.
PART 4. STANDARD FIRE ALARM SYSTEMS (15-16-1200 et seq.)
PART 5. SPRINKLER SYSTEMS - ADDITIONAL PROVISIONS (15-16-1520 et seq.)
DIVISION 10 - MEANS OF EGRESS
DIVISION 11 - ACCESSIBILITY
DIVISION 12 - INTERIOR ENVIRONMENT
DIVISION 13 - ENERGY EFFICIENCY AND ENVIRONMENTAL PROTECTION
DIVISION 14 - EXTERIOR WALLS (NA)
DIVISION 15 - ROOF ASSEMBLIES AND ROOFTOP STRUCTURES (NA)
DIVISION 16 - STRUCTURAL DESIGN
DIVISION 17 - STRUCTURAL TESTS AND SPECIAL INSPECTIONS
DIVISION 18 - SOILS AND FOUNDATIONS
DIVISION 19 - CONCRETE
DIVISION 20 - ALUMINUM (NA)
DIVISION 21 - MASONRY
DIVISION 22 - STEEL
DIVISION 23 - WOOD
DIVISION 24 - GLASS AND GLAZING (NA)
DIVISION 25 - GYPSUM BOARD AND PLASTER (NA)
DIVISION 26 - PLASTIC (NA)
DIVISION 27 - ELECTRICAL
DIVISION 28 - MECHANICAL SYSTEMS
DIVISION 29 - PLUMBING SYSTEMS
DIVISION 30 - ELEVATORS AND CONVEYING SYSTEMS
DIVISION 31 - SPECIAL CONSTRUCTION (NA)
DIVISION 32 - ENCROACHMENTS INTO THE PUBLIC RIGHT-OF-WAY
DIVISION 33 - SAFEGUARDS DURING CONSTRUCTION
DIVISION 34 - EXISTING STRUCTURES
DIVISION 35 - REFERENCED STANDARDS

You are viewing an archived code

Loading...
15-16-870  Piping design.
   All piping used in standpipe systems shall be of materials and pressure ratings as specified in Sections 2-2.1 to 2-2.4, both inclusive, of N.F.P.A. Standard 14, Standard for the Installation of Standpipe and Hose Systems, 1993 Edition. Pipe fittings used in standpipe systems shall meet the requirements of Sections 2-3.1 and 2-3.3 of the above referenced N.F.P.A. Standard 14.
(Prior code §  91-68; Amend Coun. J. 10-30-96, p. 31261, § 1)
15-16-880  Piping drains.
   All piping shall be provided with drains. Each riser shall be provided with a drain valve not less than two inches in size at the lowest point on the system side of the riser control valve. A valve used for a hose connection may be used to drain a standpipe riser when it is located at the low point of a riser. Drains shall discharge at a point where a floor drain or other adequate means exist to allow safe discharge and removal of water drained from the system.
   Drain valves shall be identified by a durable sign indicating the floors or zone served.
(Prior code §  91-69; Amend Coun. J. 10-30-96, p. 31261, § 1)
15-16-890  Risers.
   Connected to the standpipe main there shall be one or more independent standpipe risers to supply all the hose outlets in the building.
(Prior code §  91-70; Amend Coun. J. 10-30-96, p. 31261, § 1)
15-16-900  Arrangement of risers.
   The number of risers shall be determined by the floor area of the building; they shall be arranged so that all portions of the floor in all stories can be protected by fire hose not more than 100 feet long if the hose valve is located in a properly enclosed stairwell, and 75 feet if not; this length of hose shall extend to within 30 feet of the outside wall if the space is not divided into rooms or into the room farthest from the standpipe to which the hose is connected if the space is so divided. In spaces not subdivided by permanent partitions, allowance shall be made for future intervening furnishings and work station cubicles.
(Prior code §  91-71; Amend Coun. J. 10-30-96, p. 31261, § 1)
15-16-910  Location of risers.
   Risers shall be located in or adjacent to the stair enclosures except on the ground floor. Where the number of risers, as required in Section 15-16-900, is greater than the number of stair enclosures, additional risers may be located at other accessible locations as approved by the fire commissioner and adequately protected against mechanical injury.
(Prior code § 91-72; Amend Coun. J. 10-30-96, p. 31261, § 1; Amend Coun. J. 5-18-16, p. 24131, § 128)
15-16-920  Size of risers.
   Risers shall be not less than four inches in diameter for 13 or less stories; six inches for 15 additional stories and eight inches for all additional stories. Risers may be sized according to hydraulic calculation but in no case shall a riser be less than four inches in diameter. The flow rates used in hydraulic calculations shall be not less than required in Section 15-16-790. Main shall be of not less size than the largest riser.
(Prior code §  91-73; Amend Coun. J. 10-30-96, p. 31261, § 1)
15-16-930  Fire department hose connections.
   A two and one-half-inch fire department hose connection and valve shall be provided in each story on each required riser (except at street grade) and above the roof; the connections and valves shall be protected against mechanical damage. Additional fire department connections with valves shall be connected to the main if necessary to service basements or other stories with hose of the length prescribed in Section 15-16-900. All hose threads shall fit the couplings of the Chicago fire department.
(Prior code §  91-74; Amend Coun. J. 10-30-96, p. 31261, § 1)
15-16-940  Hose valve design.
   The two and one-half-inch hose valves for the use of the fire department, as hereinbefore prescribed, shall be of the gate or angle type and shall be located at such a height that the center line of the valve shall be not less than three feet nor more than six feet above the floor and so installed that the water will flow through the valve without kinking or bending the hose. Valve bodies shall be constructed of non-corrodible material and rated for not less than the pressure which exists in the standpipe. Hand wheels on all two and one-half-inch hose valves shall be of solid construction of malleable iron, cast iron, brass or bronze and shall be not less than five inches in diameter. Each two and one-half inch outlet shall be provided with a lugged cap to protect the threads of the valve, attached to the valve by a chain not less than six inches long.
(Prior code §  91-75; Amend Coun. J. 10-30-96, p. 31261, § 1)
15-16-950  Hand hose connections.
   A one and one-half-inch hose connection and valve shall be provided adjacent to each fire department hose valve, except at the connection above the roof if this is exposed to freezing. All hose threads shall fit the couplings of the Chicago fire department.
(Prior code §  91-76; Amend Coun. J. 10-30-96, p. 31261, § 1)
Loading...