Skip to code content (skip section selection)
Compare to:
Chicago Overview
Prior Chicago Building Code
BUILDING CODE AND RELATED EXCERPTS OF THE MUNICIPAL CODE OF CHICAGO
DIVISION 1 - ADMINISTRATION
DIVISION 2 - DEFINITIONS
DIVISION 3 - USE AND OCCUPANCY CLASSIFICATIONS
DIVISION 4 - SPECIAL DETAILED REQUIREMENTS BASED ON USE AND OCCUPANCY
DIVISION 5 - GENERAL BUILDING HEIGHTS AND AREAS
DIVISION 6 - TYPES OF CONSTRUCTION
DIVISION 7 - FIRE-RESISTANCE-RATED CONSTRUCTION
DIVISION 8 - INTERIOR FINISHES (NA)
DIVISION 9 - FIRE PROTECTION SYSTEMS
CHAPTER 15-16 FIRE PROTECTION EQUIPMENT
ARTICLE I. FIRE PROTECTION (15-16-010 et seq.)
ARTICLE II. FIRE PROTECTION EQUIPMENT (15-16-170 et seq.)
PART 1. STANDARD SPRINKLER SYSTEMS (15-16-170 et seq.)
PART 2. STANDARD FIRE EXTINGUISHERS (15-16-620 et seq.)
PART 3. STANDARD INSIDE STANDPIPE SYSTEMS (15-16-710 et seq.)
15-16-710 Definition of system.
15-16-720 Where standpipe system required.
15-16-730 Other definitions.
15-16-740 Permit fees.
15-16-750 Installation certification.
15-16-760 Types of systems.
15-16-770 Sources of water supply.
15-16-780 Fire pumps.
15-16-790 Use for other services.
15-16-800 Fire pump requirements.
15-16-810 Pumps supplied from city main.
15-16-820 Fire pump auxiliary equipment.
15-16-830 Pressure-control devices.
15-16-840 Pump suction piping.
15-16-850 Requirements for auxiliary drive.
15-16-860 Piping arrangement.
15-16-870 Piping design.
15-16-880 Piping drains.
15-16-890 Risers.
15-16-900 Arrangement of risers.
15-16-910 Location of risers.
15-16-920 Size of risers.
15-16-930 Fire department hose connections.
15-16-940 Hose valve design.
15-16-950 Hand hose connections.
15-16-960 Hand hose valve design.
15-16-970 Equipment at hose outlets.
15-16-971 Identification of hose valves.
15-16-980 Pressure reducing devices.
15-16-990 Domestic use prohibited.
15-16-1000 Multiple systems.
15-16-1010 Express risers.
15-16-1020 Siamese connections required.
15-16-1030 Check valves for siamese.
15-16-1040 Arrangement of siamese connections.
15-16-1050 Valves.
15-16-1060 Reserved.
15-16-1070 Test manifold and wall hydrants.
15-16-1080 Gauges.
15-16-1090 Painting and identification of pipe.
15-16-1100 Protection against freezing.
15-16-1110 Dry pipe system.
15-16-1115 Manual dry pipe system.
15-16-1120 Buildings under construction.
15-16-1130 Buildings being demolished.
15-16-1140 Alarms.
15-16-1150 Test method.
15-16-1160 Annual test required.
15-16-1170 Inspection.
15-16-1180 Retroactivity.
15-16-1190 Existing buildings.
PART 4. STANDARD FIRE ALARM SYSTEMS (15-16-1200 et seq.)
PART 5. SPRINKLER SYSTEMS - ADDITIONAL PROVISIONS (15-16-1520 et seq.)
DIVISION 10 - MEANS OF EGRESS
DIVISION 11 - ACCESSIBILITY
DIVISION 12 - INTERIOR ENVIRONMENT
DIVISION 13 - ENERGY EFFICIENCY AND ENVIRONMENTAL PROTECTION
DIVISION 14 - EXTERIOR WALLS (NA)
DIVISION 15 - ROOF ASSEMBLIES AND ROOFTOP STRUCTURES (NA)
DIVISION 16 - STRUCTURAL DESIGN
DIVISION 17 - STRUCTURAL TESTS AND SPECIAL INSPECTIONS
DIVISION 18 - SOILS AND FOUNDATIONS
DIVISION 19 - CONCRETE
DIVISION 20 - ALUMINUM (NA)
DIVISION 21 - MASONRY
DIVISION 22 - STEEL
DIVISION 23 - WOOD
DIVISION 24 - GLASS AND GLAZING (NA)
DIVISION 25 - GYPSUM BOARD AND PLASTER (NA)
DIVISION 26 - PLASTIC (NA)
DIVISION 27 - ELECTRICAL
DIVISION 28 - MECHANICAL SYSTEMS
DIVISION 29 - PLUMBING SYSTEMS
DIVISION 30 - ELEVATORS AND CONVEYING SYSTEMS
DIVISION 31 - SPECIAL CONSTRUCTION (NA)
DIVISION 32 - ENCROACHMENTS INTO THE PUBLIC RIGHT-OF-WAY
DIVISION 33 - SAFEGUARDS DURING CONSTRUCTION
DIVISION 34 - EXISTING STRUCTURES
DIVISION 35 - REFERENCED STANDARDS

You are viewing an archived code

Loading...
15-16-760  Types of systems.
   Inside standpipe systems may be:
   (a)   Wet, in which the pipes are kept filled with water.
   (b)   Dry, in which a portion of the piping nearest the hose outlets normally is kept filled with air under pressure and so arranged that the operation of an outlet will automatically admit water to the system. Dry systems shall be used only when a wet system is impractical on account of a deficiency of heat in the area in which piping is located.
   (c)   Manual dry, in which a permanent water supply is not attached to the system, and which requires water from a Fire Department pumper to be pumped into the system through the Fire Department connection in order to meet the system demand. Manual dry systems shall be used only as provided in Section 15-16-090(a)(5).
(Prior code § 91-57; Amend Coun. J. 10-30-96, p. 31261, § 1; Amend Coun. J. 1-23-19, p. 94952, Art. II, § 2)
15-16-770  Sources of water supply.
   The water supply for inside standpipe systems shall be taken from a source sufficient to provide a minimum pressure of 65 pounds per square inch with 500 gallons per minute flowing at the highest hose outlet. The total water supply capacity shall be not less than 500 gallons per minute for the first standpipe and 250 gallons per minute for each additional standpipe riser, but no standpipe system need have a capacity greater than 1,500 gallons per minute. The water supply shall be capable of providing the required flow for not less than one-half hour.
(Prior code §  91-58; Amend Coun. J. 10-30-96, p. 31261, § 1)
15-16-780  Fire pumps.
   Where fire pumps are used to meet the water supply requirements, the minimum capacity of such pumps shall be 500 gallons per minute at a pressure of not less than 100 pounds per square inch. However, no one pump need have a capacity of more than 1,500 gallons per minute.
(Prior code §  91-59; Amend Coun. J. 10-30-96, p. 31261, § 1)
15-16-790  Use for other services.
   An inside standpipe system and a sprinkler system may be connected to the same water supply; provided, however, the water supply is of sufficient capacity for the automatic sprinkler system plus one-half of the standpipe demand. It shall provide sufficient pressure for the more severe demands.
   An individual riser used to supply both hose connections and automatic sprinklers shall be calculated to deliver the sprinkler demand as determined in Sections 15-16-270 or 15-16-600 plus 250 gallons per minute for a hose stream but not less than 500 gallons per minute.
(Prior code §  91-60; Amend Coun. J. 10-30-96, p. 31261, § 1)
15-16-800  Fire pump requirements.
   Pumps shall be of a centrifugal type. Pumps and auxiliary equipment, including controllers, required to form complete pumping units shall be of a type designed and developed for fire protection service and listed by a product testing laboratory which regularly tests fire protection equipment and conducts periodic inspection of the production of listed equipment. Pumps and controllers shall be plainly marked to show the manufacturer, model designation, pump capacity and pressure, and controller electrical rating.
   Where pumps or controllers are provided to service more than one area or zone, pumps and controllers shall be identified as to the area or zone served by permanent signs.
   Each pump shall be installed in accordance with N.F.P.A. Standard 20, Standard for the Installation of Centrifugal Fire Pumps, 1993 Edition except as herein modified.
(Prior code §  91-61; Amend Coun. J. 10-30-96, p. 31261, § 1)
15-16-810  Pumps supplied from city main.
   If the supply is taken from a city main, the pumping unit shall be designed to develop its full capacity at its rated pressure; provided, however, that if it is the source of supply for an upper standpipe system in a building having multiple systems, it may take its suction from the discharge of the fire pump for the system immediately below, but all piping shall be arranged so that pressure from the higher pressure system cannot be delivered to the lower pressure system.
(Prior code §  91-62; Amend Coun. J. 10-30-96, p. 31261, § 1)
15-16-820  Fire pump auxiliary equipment.
   Pumps shall be designed for automatic starting and stopping. Control shall be by means of a pressure- activated switch having independent high and low calibrated adjustments in the control circuit. The switch shall be responsive to water pressure in the fire protection system. Each controller shall have its own individual pressure sensing line. The pressure sensing line connection for each pump shall be made between that pump's discharge check valve and discharge control valve. There shall be no shutoff valve in the pressure sensing line.
   A time delay device set for one minute for each 10 horsepower of motor rating to a maximum of seven minutes continuous operation after each start shall be provided. A separate automatically controlled pressure maintenance pump shall be provided.
(Prior code §  91-63; Amend Coun. J. 10-30-96, p. 31261, § 1)
15-16-830  Pressure-control devices.
   All pressure-controlling and pressure-limiting devices installed in connection with a fire pump shall be designed for operation over a minimum range of zero to 300 pounds per square inch.
(Prior code §  91-64)
15-16-840  Pump suction piping.
   The suction pipe size to a fire pump shall be six inches for 500 and 750 gallons per minute pumps and eight inches for 1,000 and 1,500 gallons per minute pumps. This pipe shall be directly connected to the city main or suction source free from any meter (except a detector meter installed in a bypass around a check valve). The city connection shall be increased two inches if used for both domestic consumption and fire protection demands when the domestic service exceeds two inches in diameter.
(Prior code §  91-65; Amend Coun. J. 10-30-96, p. 31261, § 1)
Loading...