Section 109.2 Schedule of Permit Fees, of the IFGC, is hereby amended by adding the following exception:
Section 109.2 Schedule of Permit Fees exception:
Persons performing work on exempt projects for the Federal Government, the State, the county or city may obtain permits for such work without paying permit fees described herein: provided, however, that nothing in this section shall be construed to exempt payment of permit fees by persons performing work under the direction of the City of Ankeny in connection with the abatement of property as prescribed by law.
Persons performing work on exempt projects for the Federal Government, the State, the county or city may obtain permits for such work without paying permit fees described herein: provided, however, that nothing in this section shall be construed to exempt payment of permit fees by persons performing work under the direction of the City of Ankeny in connection with the abatement of property as prescribed by law.
Section 113, Means of Appeal, of the IPMC, is hereby amended by deleting said section and inserting in lieu thereof the following:
Section 113 Board of Examiners and Appeals Pursuant to the Ankeny Municipal Code, there is hereby created the Ankeny Board of Examiners and Appeals. Appeals shall be in accordance thereof.
Section 115.4, Violation penalties, of the IFGC, is hereby amended by deleting said section and inserting in lieu thereof the following:
Section 115.4 Violation penalties Any person who violates a provision of this code or fails to comply with any of the requirements thereof or who erects, installs, alters or repairs Fuel Gas work in violation of the approved construction documents or directive of the Code Official, or of a permit issued under the provisions of this code, shall be subject to penalties as prescribed by law.
Section 310.2 CSST, of the IFGC, is hereby amended by deleting said section (not including subsections) and inserting in lieu of the following:
Section 310.2 Existing CSST - Bonding Required Where alterations, repairs or additions requiring a permit occur, CSST shall be bonded in accordance with 310.2.1 through 310.2.5 of the International Fuel Gas Code, unless deemed technically infeasible by the Code Official.
Section 310.3, Arc-resistant CSST, of the IFGC, is hereby amended by deleting said section and inserting in lieu thereof the following:
Section 310.3 Arc-resistant CSST Only Corrugated Stainless Steel Tubing (CSST) with an Arc Resistant Jacket or Covering System listed in accordance with ANSI LC-1 (Optional Section 5.16)/CSA 6.26-2016 shall be installed. Installation shall be in accordance with the terms of its approval, the conditions of listing, the manufactures instructions including electrical bonding requirements in Section 1211.2 and this code. CSST shall not be used for through wall penetrations from the point of delivery of the gas supply to the inside of the structure. CSST shall not be installed in locations where subject to physical damage unless protected in an approved manner.
Section 403. 9.1, Pipe joints, of the IFGC, is hereby amended by adding a new section as follows:
Section 403. 9.1.1 Welded Pipe Joints All joints of wrought iron or steel gas piping larger than two-inch (2") standard iron pipe size and providing gas pressure of two (2) PSIG or greater shall be welded steel. All welded joints shall comply with the State of Iowa requirements and work shall be performed by certified welders.