The provisions of Article 360 of NFPA 70 are adopted by reference with the following modifications:
1. Revise subsections 360.10(1) through (4) to read:
"(1) Branch circuits not exceeding 20 amperes and 300 volts to ground
(2) As permitted in 300.22(C)
(3) Connection between a junction box and a single luminaire
(4) Connection between a junction box and speakers or similar equipment requiring flexibility"
2. Insert new subsection 360.12(7) to read:
"(7) Other than as specifically permitted in 360.10"
The provisions of Article 366 of NFPA 70 are adopted by reference with the following modifications:
1. Revise the title of Article 366 to read "Metallic Auxiliary Gutters."
2. Revise section 366.1 to read:
"Scope. This article covers the use, installation, and construction requirements of metal auxiliary gutters and associated fittings."
3. Revise section 366.2 by deleting the definition of "Nonmetallic Auxiliary Gutter."
4. Delete section 366.6.
5. Delete subsection 366.10(B).
6. Delete subsection 366.22(B).
7. Delete subsection 366.23(B).
8. Delete subsection 366.30(B).
9. Delete section 366.120.
The provisions of Article 368 of NFPA 70 are adopted by reference with the following modifications:
1. Revise section 368.12, by adding a new subsection (F) to read:
"(F) Sprinklers. In rooms or areas where an automatic sprinkler system is installed which, when activated, would cause water to come into contact with the busway.
Exception: Busway that is listed as weatherproof or raintight shall be permitted in locations with sprinkler protection."
2. Revise subsection 368.56, by deleting items 1, 2, 8, 9, 10, 12, 14, and 16.
(Amend Coun. J. 11-8-17, p. 59720, § 19)