14E-3-368 Busways.
The provisions of Article 368 of NFPA 70 are adopted by reference with the following modifications:
1.   Revise section 368.12, by adding a new subsection (F) to read:
"(F)   Sprinklers. In rooms or areas where an automatic sprinkler system is installed which, when activated, would cause water to come into contact with the busway.
Exception: Busway that is listed as weatherproof or raintight shall be permitted in locations with sprinkler protection."
2.   Revise subsection 368.56, by deleting items 1, 2, 8, 9, 10, 12, 14, and 16.
(Amend Coun. J. 11-8-17, p. 59720, § 19)
14E-3-370 Cablebus.
The provisions of Article 370 of NFPA 70 are adopted by reference without modification.
14E-3-372 Cellular concrete floor raceways.
The provisions of Article 372 of NFPA 70 are not adopted.
14E-3-374 Cellular metal floor raceways.
The provisions of Article 374 of NFPA 70 are adopted by reference without modification.
14E-3-376 Metal wireways.
The provisions of Article 376 of NFPA 70 are adopted by reference with the following modification:
1.   Revise section 376.12 by inserting new items (3) and (4) to read:
"(3)   For service entrance conductors
(4)   Above suspended ceilings"
14E-3-378 Nonmetallic wireways.
The provisions of Article 378 of NFPA 70 are not adopted.
14E-3-380 Multi-outlet assembly.
The provisions of Article 380 of NFPA 70 are adopted by reference with the following modification:
1.   Revise section 380.12 item (3) to read:
"(3)   Where the voltage is 300 volts or more between conductors"
14E-3-382 Nonmetallic extensions.
The provisions of Article 382 of NFPA 70 are not adopted.