The provisions of Article 340 of NFPA 70 are adopted by reference with the following modification:
1. Revise section 340.10 to read:
"Uses Permitted. Listed Type UF cable shall be permitted as follows:
(1) For use underground, including direct burial in the earth. For underground requirements, see 300.5.
(2) As single-conductor cables. Where installed as single-conductor cables, all conductors of the feeder grounded conductor or branch circuit, including the grounded conductor and equipment grounding conductor, if any, shall be installed in accordance with 300.3.
(3) For solar photovoltaic systems in accordance with 690.31.
(4) As single-conductor cables as the non-heating leads for heating cables as provided in 424.43.
Informational Note: See 310.15(A)(3) for temperature limitation of conductors."