The provisions of Article 348 of NFPA 70 are adopted by reference with the following modifications:
1. Revise section 348.10 to read:
"Uses Permitted. FMC shall be permitted to be used:
(1) For the connection of motors or recessed luminaires
(2) In lengths not exceeding 7.62 m (25 ft) between junction boxes for branch circuits in concealed work fished into existing walls, partitions, floors, or hard surface ceilings where other work does not require or include removal of the existing finished surface
(3) For required flexibility at the termination of conduit runs."
2. Insert new subsections 348.12(8) and (9) to read:
"(8) In lengths exceeding 1.83 m (6 ft) except where fished in existing construction
(9) Where exposed below the first floor except 1.83 m (6 ft) of any run shall be permitted to extend below the basement ceiling to connect to a cabinet, outlet box or junction box."