14E-3-368 Busways.
The provisions of Article 368 of NFPA 70 are adopted by reference with the following modifications:
1.   Revise section 368.12, by adding a new subsection (F) to read:
"(F)   Sprinklers. In rooms or areas where an automatic sprinkler system is installed which, when activated, would cause water to come into contact with the busway.
Exception: Busway that is listed as weatherproof or raintight shall be permitted in locations with sprinkler protection."
2.   Revise subsection 368.56, by deleting items 1, 2, 8, 9, 10, 12, 14, and 16.
(Amend Coun. J. 11-8-17, p. 59720, § 19)