The provisions of Section 913 of IBC are adopted by reference with the following modifications:
1. Revise exception 1 to Section 913.2.1 to read:
"1. In buildings less than 55 feet (16.8 m) in building height, separation by 1-hour fire barriers constructed in accordance with Section 707 or 1-hour horizontal assemblies constructed in accordance with Section 711, or both, shall be permitted in buildings equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1 or 903.3.1.2."
2. Delete item 4 in Section 913.4.