14B-9-915 Carbon monoxide detection.
The provisions of Section 915 of IBC are adopted by reference with the following modifications:
1.   Revise Section 915.1 by replacing "Chapter 11 of the International Fire Code" with "the Chicago Minimum Requirements for Existing Buildings."
2.   Revise Section 915.1.1 by replacing "through 915.1.6" with "through 915.1.5."
3.   Revise the exception to Section 915.1.3 by replacing "an approved location" with "a location that is monitored at all times when the building is occupied."
4.   Revise exception 2.1 to Section 915.1.4 by replacing "an approved" with "a."
5.   Revise exception 4 to Section 915.1.5 by replacing "an approved" with "a."
6.   Delete Section 915.1.6.
7.   Revise Section 915.2.3 to read:
"915.2.3 Group E and I-4 occupancies.
Carbon monoxide detectors shall be installed in classrooms in Group E and I-4 occupancies. Carbon monoxide alarm signals shall be automatically transmitted to an on-site location that is staffed by school personnel.
Exception: Carbon monoxide alarm signals shall not be required to be automatically transmitted to an on- site location that is staffed by school personnel in Group E or I-4 occupancies with an occupant load of 30 or less."
(Amend Coun. J. 2-19-20, p. 14473, Art. II, § 36)