14B-9-901 General.
The provisions of Section 901 of IBC are adopted by reference with the following modifications:
1.   Add a new Section 901.1.1 to read:
"901.1.1 Modification of reference standards.
The fire code official shall be authorized to promulgate rules, not inconsistent with this code, which modify the following referenced standards for the design of fire protection systems for consistency with existing installations and the operations of the Chicago Fire Department: NFPA 10, NFPA 13, NFPA 13D, NFPA 13R, NFPA 14, NFPA 20, NFPA 25, NFPA 72 and NFPA 92. Where the fire code official has promulgated such rules and posted them on the city's public web site, references to such standards in the Chicago Construction Codes shall mean such standards as modified by the fire code official's rules.
1.1.   Revise Section 901.2 by replacing "reduction to the provisions" with "reduction under the provisions."
2.   Revise Section 901.3 to read:
"901.3 Modifications.
It is unlawful for any person to remove, modify or disable for more than 24 hours any automatic sprinkler system, automatic fire-extinguishing system, standpipe system or fire pump installed or maintained under the provisions of this code or the Chicago Fire Prevention Code without a permit from the fire code official. It is unlawful for any person to remove, modify or disable for more than 24 hours a fire alarm and detection system, smoke control system or carbon monoxide detection system without a permit from the building official. It is unlawful for any person to modify a fire command center without approval by the fire code official and a permit from the building official."
3.   Revise Section 901.4 by replacing "local fire department" with "Chicago Fire Department."
4.   Revise Section 901.5 to read:
"901.5 Acceptance tests.
Fire protection systems shall be tested in accordance with the requirements of this code and the Chicago Fire Prevention Code. Where required, the tests shall be conducted in the presence of the fire code official. Tests required by this code, the Chicago Fire Prevention Code and the standards listed in this code shall be conducted at the expense of the owner. It shall be unlawful to occupy portions of a structure until the required fire protection systems within that portion of the structure have been tested and accepted."
5.   Revise Section 901.6 and its subsections to read:
"901.6 Supervisory service.
Where required, fire protection systems shall be monitored by a supervising station in accordance with NFPA 72 or connected to a city fire alarm box in accordance with Section 919. A provider of supervising station services shall notify the fire code official no less than 48 hours before terminating services to a building.
901.6.1 Automatic sprinkler systems.
Automatic sprinkler systems shall be monitored by a supervising station.
Exceptions:
1.   A supervising station is not required for automatic sprinkler systems protecting Group R-5 occupancies.
2.   Limited area systems in accordance with Section 903.3.8.
901.6.3 Fire alarm systems.
Fire alarm systems required by the provisions of Section 907.2 of this code shall be monitored by a supervising station in accordance with Section 907.6.6 of this code.
Exceptions:
1.   Single- and multiple-station smoke alarms required by Section 907.2.10.
2.   Smoke detectors in Group I-3 occupancies.
3.   Supervisory service is not required for automatic sprinkler systems in Group R-5 occupancies.
901.6.4 Group H.
Supervision and monitoring of emergency alarm, detection and automatic fire-extinguishing systems in Group H occupancies shall be in accordance with the Chicago Fire Prevention Code."
(Amend Coun. J. 2-19-20, p. 14473, Art. II, § 28; Amend Coun. J. 10-7-20, p. 21791, Art. II, § 13)
14B-9-902 Fire pump and riser room size.
The provisions of Section 902 of IBC are adopted by reference with the following modification:
1.   Revise Section 902.1.2 by deleting "with an approved sign."
14B-9-903 Automatic sprinkler systems.
The provisions of Section 903 of IBC are adopted by reference with the following modifications:
1.   Add a new Section 903.1.2 to read:
"903.1.2 Where prohibited.
Automatic sprinkler systems shall not be installed in hazardous chemical rooms or in hazardous chemical storage buildings, where the chemical has the ability to react with water to produce substances or violent chemical reactions which increase the hazard. When the presence of water will not add to the hazard, an automatic sprinkler system shall be required in such hazardous chemical room or building."
2.   Revise Section 903.2 by deleting "Approved."
3.   Delete the exception to Section 903.2.
4.   Delete items 3 and 4 in Section 903.2.1.1.
5.   Revise the numbered items in Section 903.2.1.2 to read:
"1.   The fire area exceeds 12,000 square feet (1115 m2).
2.   The fire area has an occupant load of 300 or more.
3.   The fire area has an occupant load of 100 or more and is located on a floor more than four feet (1219 mm) below the lowest level of exit discharge serving such occupancy."
6.   Delete item 3 in Section 903.2.1.3.
7.   Add a new item 4 in Section 903.2.1.3 to read:
"4.   The Group A-3 occupancy contains one or more exhibition areas exceeding 5,000 square feet (464 m 2 ) in aggregate."
8.   Delete item 3 in Section 903.2.1.4.
9.   Revise Section 903.2.1.6, including the exception, to read:
"903.2.1.6 Assembly occupancies on roofs.
Where an occupiable rooftop has an assembly occupancy with an occupant load of 300 or more, all floors between the occupiable rooftop and the level of exit discharge shall be equipped with an automatic sprinkler system in accordance with Section 903.3.1.1 or 903.3.1.2."
10.   Revise Section 903.2.1.7 by replacing "shall be provided" with "shall be provided throughout the building."
11.   Revise Section 903.2.2 to read:
"903.2.2 Group B.
An automatic sprinkler system shall be provided for Group B occupancies as provided in this section.
903.2.2.1 Ambulatory care facilities.
An automatic sprinkler system shall be installed throughout the entire floor containing an ambulatory care facility where either of the following conditions exist at any time:
1.   Four or more care recipients are incapable of self-preservation.
2.   One or more care recipients that are incapable of self-preservation are located at other than the level of exit discharge serving such a facility.
In buildings where ambulatory care is provided on levels other than the level of exit discharge, an automatic sprinkler system shall be installed throughout the entire floor as well as all floors between the level of ambulatory care and the nearest level of exit discharge, the level of exit discharge, and all floors below the level of exit discharge.
903.2.2.2 Telephone exchanges.
An automatic fire-extinguishing system shall be installed throughout buildings containing telephone exchanges."
12.   Revise Section 903.2.3 to read:
"903.2.3 Group E.
An automatic sprinkler system shall be provided for Group E occupancies as follows:
1.   Throughout all Group E fire areas and all connected Group A fire areas in buildings where the aggregate area of all Group E and connected Group A fire areas is 7,200 square feet (669 m2) or greater.
2.   Throughout buildings containing Group E occupancies owned by, operated by or constructed with funding from a governmental unit.
3.   Throughout buildings containing Group E-2 occupancies.
Exception: Where every room or space in a Group E-2 occupancy normally subject to client occupancy, other than toilet rooms, has not less than one door leading directly to an exit or directly to the outside of the building."
13.   Revise the title and first sentence of Section 903.2.4 to read:
"903.2.4 Group F.
An automatic sprinkler system shall be provided throughout all buildings containing a Group F occupancy where one of the following conditions exists:"
13.1   Revise item 4 in Section 903.2.4 to read:
"4.   A Group F-1 fire area used for the manufacture of upholstered furniture or mattresses exceeds 2,500 square feet (232 m 2 )."
14.   Revise Section 903.2.4.1 by replacing "fire areas" with "buildings."
15.   Add a new Section 903.2.4.2 to read:
"903.2.4.2 Electric generation plants.
An automatic fire-extinguishing system shall be provided throughout any structure that is owned or operated by any person whose primary business is the generation or transmission of electrical power and that houses one or more electrical generators, electrical transformers, or switching equipment for a service area beyond the building in which the equipment is located."
16.   Revise exception 2 to Section 903.2.6 to read:
"2.   An automatic sprinkler system is not required where Group I-4 day care facilities are at the level of exit discharge and where every room where care is provided has not fewer than one exterior exit door."
17.   Delete exception 3 to Section 903.2.6.
17.1.   Revise item 4 in Section 903.2.7 to read:
"4.   A Group M occupancy where the area used for the display and sale of upholstered furniture or mattresses exceeds 5,000 square feet (464 m 2 )."
18.   Add a new item 5 to Section 903.2.7 to read:
"5.   A Group M fire area is located in a basement."
19.   Add new exceptions to Section 903.2.8 to read:
"Exceptions:
1.   Buildings of Group R-5 occupancy.
2.   Buildings of Group R-2 occupancy, other than congregate living facilities, with not more than four stories above grade plane and containing not more than ten dwelling units where each fire area contains not more than two dwelling units and all required vertical exits are interior exit stairways."
20.   Revise Section 903.2.8.1 to read:
"903.2.8.1 Group R-3 and R-5.
An automatic sprinkler system installed in accordance with Section 903.3.1.3 shall be permitted in Group R-3 and R-5 occupancies."
20.1.   Revise items 4 and 5 in Section 903.2.9 to read:
"4.   A Group S-1 fire area used for the storage of commercial motor vehicles where the fire area exceeds 5,000 square feet (464 m 2 ).
5.   A Group S-1 occupancy where the area used for the storage of upholstered furniture or mattresses exceeds 2,500 square feet (232 m 2 )."
20.2.   In Section 903.2.10.1, reset the following term in italic type: "commercial motor vehicle."
21.   Revise Section 903.2.10 to read:
"903.2.10 Group S-2 parking garages.
An automatic sprinkler system shall be provided throughout buildings containing parking garages in accordance with Section 406.6 where any of the following conditions exists:
1.   Where the floor area of the parking garage exceeds 12,000 square feet (1115 m2).
2.   Where the parking garage has a storage capacity of more than 20 vehicles and is located beneath other occupancies.
3.   Where the parking garage is in a basement."
22.   Revise the title of Section 903.2.10.1 to "Commercial-vehicle parking garages."
22.1.   In Section 903.2.10.1, reset the following term in italic type: "commercial motor vehicle."
22.2.   Revise Section 903.2.11 by replacing "903.2.11.6" with "903.2.11.8."
23.   Revise Section 903.2.11.1.2 by deleting "approved."
24.   Revise Section 903.2.11.1.3 by deleting "approved."
25.   Revise Section 903.2.11.3 to read:
"903.2.11.3 Buildings more than 70 feet in height.
An automatic sprinkler system shall be installed throughout buildings that are more than 70 feet (21.3 m) in building height.
Exception: Parking facilities, in accordance with Section 906.9."
26.   Renumber existing Section and Table 903.2.11.6 to 903.2.11.8 and delete the following rows in the table: covered and open mall buildings, Group H-5 HPM exhaust ducts, flammable finishes, drying rooms, children’s play structures, buildings containing laboratory suites, unlimited area buildings, smoke-protected assembly seating, and the last row.
27.   Add a new Section 903.2.11.6 to read:
"903.2.11.6 Shops and storerooms.
An automatic sprinkler system shall be installed in all rooms and spaces used as paint shops, wastepaper baling or storage, and other storage uses having a similar degree of combustibility.
Exceptions:
1.   Shops and storerooms located in a Group R-5 occupancy.
2.   Shops and storerooms not exceeding 1,000 square feet (93 m2) in a building not exceeding one story above grade plane."
28.   Add a new Section 903.2.11.7 to read:
"903.2.11.7 Telecommunications equipment areas.
Every fire area within an existing structure containing a telecommunication equipment area that exceeds 150 square feet (13.93 m2) must be equipped with an automatic fire-extinguishing system."
29.   Revise Section 903.2.12 by deleting "Chapter 33 of."
30.   Revise Section 903.3.1.1.1 to read:
"903.3.1.1.1 Exempt locations.
Automatic sprinklers shall not be required in the following rooms or areas where such rooms or areas are protected with an automatic fire detection system in accordance with Section 907.2 that will respond to visible or invisible particles of combustion. Sprinklers shall not be omitted from a room merely because it is damp, of fire-resistance-rated construction or contains electrical equipment.
1.   A room where the application of water, or flame and water, constitutes a serious life or fire hazard.
2.   A room or space where sprinklers are considered undesirable because of the nature of the contents, where approved by the fire code official.
3.   Generator, transformer and switchboard rooms separated from the remainder of the building by walls and floor/ceiling or roof/ceiling assemblies having a fire-resistance rating of not less than 2 hours.
4.   [Reserved.]
5.   Elevator machine rooms, elevator shafts and machinery spaces. (Automatic sprinklers shall be provided in elevator pits.)"
31.   Delete Section 903.3.1.1.2.
32.   Revise Section 903.3.1.2 to read:
"903.3.1.2 NFPA 13R sprinkler systems.
Automatic sprinkler systems installed in Group R-5; Group R-3; and Group R-4, Condition 1 shall be permitted to be installed throughout in accordance with NFPA 13D, provided the building shall not exceed 45 feet (13.7 m) in building height."
33.   Delete Section 903.3.1.2.1.
34.   Delete item 3 (and subitems) in Section 903.3.1.2.3.
35.   Revise Section 903.3.1.3 to read:
"903.3.1.3 NFPA 13D sprinkler systems.
Automatic sprinkler systems installed in Group R-5; Group R-3; Group R-4, Condition 1; and townhouses shall be permitted to be installed throughout in accordance with NFPA 13D, provided the building shall not exceed 45 feet (13.7 m) in building height."
36.   Revise the last sentence of Section 903.3.5 to read:
"For connections to the public waterworks systems, the water supply test used for design of fire protection systems shall be acceptable to the fire code official and not less than one year old."
37.   Revise Section 903.3.8.4 by deleting "approved."
37.1   Insert a new Section 903.3.9 to read:
"903.3.9 Concealed sprinkler heads.
Where concealed sprinkler heads are used, cover plates shall have a brass, chrome or other unpainted metallic finish."
38.   Revise exception 1 to Section 903.4 by replacing "one- and two-family dwellings" with "Group R-5 occupancies."
39.   Revise Section 903.4 by adding a sentence, following the exceptions, to read:
"All valves in supply pipes to automatic sprinkler systems shall be secured open."
40.   Revise Section 903.4.1, excluding the exceptions, to read:
"903.4.1 Monitoring.
Alarm, supervisory and trouble signals shall be distinctly different and shall be automatically transmitted to a supervising station."
41.   Revise Section 903.4.2 to read:
"903.4.2 Alarms.
An electric bell, located on the exterior of the building above a fire department connection, shall be connected to each automatic sprinkler system. The bell shall be activated by water flow equivalent to the flow of a single sprinkler of the smallest orifice size installed in the system. Where a fire alarm system is installed, actuation of the automatic sprinkler system shall actuate the building fire alarm system.
A sign shall be placed at a conspicuous location near the bell and shall state: "SPRINKLER ALARM-WHEN BELL RINGS CALL FIRE OR POLICE DEPARTMENT."
42.   Revise Section 903.4.3 by deleting "Approved."
(Amend Coun. J. 2-19-20, p. 14473, Art. II, § 29; Amend Coun. J. 10-7-20, p. 21791, Art. II, § 14; Amend Coun. J. 6-25-21, p. 32180, Art. II, § 13)
14B-9-904 Alternative automatic fire-extinguishing systems.
The provisions of Section 904 of IBC are adopted by reference with the following modifications:
1.   Revise Section 904.2 to read:
"904.2 Where permitted.
Automatic fire-extinguishing systems installed as an alternative to the required automatic sprinkler systems of Section 903 shall be approved by the fire code official. As a condition of approval, the fire code official may require signs indicating the type of alternative automatic fire-extinguishing system be installed in prominent locations at each building entrance."
2.   Revise Section 904.2.2 to read:
"904.2.2 Commercial hood and duct systems.
Each required commercial kitchen exhaust hood and duct system required by the Chicago Fire Prevention Code or Chicago Mechanical Code to have a Type I hood shall be protected with an automatic fire-extinguishing system installed in accordance with this code."
3.   Revise Section 904.11.1.4 by replacing "an approved" with "a."
4.   Revise the exception to Section 904.12 by deleting "Section 304.1 of."
5.   Revise Section 904.13 by deleting item 3.
6.   Revise Section 904.13.1.1 by deleting "approved."
(Amend Coun. J. 2-19-20, p. 14473, Art. II, § 30)
14B-9-905 Standpipe systems.
The provisions of Section 905 of IBC are adopted by reference with the following modifications:
1.   Add new Sections 905.2.1, 905.2.2, 905.2.3 and 905.2.4 to read:
"905.2.1 Water supply.
Where wet standpipes are installed in buildings that are 80 feet (24.4 m) or less in building height and the building is protected throughout with an automatic sprinkler system in accordance with Section 903.3.1.1 or 903.3.1.2, the water supply for the building may be designed to provide 100 pounds per square inch (689 kPa) pressure with 500 gallons per minute (31.6 L/s) flowing from the two hydraulically most remote outlets in the standpipe system. The standpipe system shall be designed for full standpipe flow in accordance with NFPA 14.
905.2.2 Multiple systems required.
In buildings where the floor level of the highest story is more than 275 feet (83.8 m) above grade plane, two or more separate standpipe systems shall be provided. The lowest standpipe system shall serve the portion up to and including the story which is 275 feet (83.8 m) or less above grade plane. Above 275 feet (83.8 m) additional standpipe systems shall be provided to serve zones of not more than 20 stories each.
905.2.3 Express risers.
In buildings where the floor level of the highest story is more than 275 feet (83.8 m) above grade plane, individual standpipe systems, as required by Section 905.2.1, shall be supplied by two or more separate risers from the zone fire pump located in the lowest story of the building, except that the number of express risers shall not exceed the number of risers serving that zone; or by individual fire pumps located on the lowest story of each zone taking suction under head from a tank automatically filled by two or more risers from the adjacent lower zone. Such a tank shall have a capacity sufficient to supply the largest pump in the zone at its rated capacity for at least 30 minutes but not less than 10,000 gallons (37,854 L).
905.2.4 Pressure reducing devices.
Where the pressure at nozzles is more than 65 pounds per square inch (448 kN/m2), the 1 1/2-inch hose valve shall be provided with a device or disk to limit the force of the hose stream to 90 pounds (0.4 kN) so that the nozzle can be safely handled by one person."
2.   Revise the exception to Section 905.3 to read:
"Exception: Standpipe systems are not required in Group R-2, R-3, R-4 and R-5 occupancies not more than four stories above grade plane."
3.   Revise Section 905.3.1 to read:
"905.3.1 Height.
Class III standpipe systems shall be installed throughout buildings which exceed 55 feet in building height or where four or more stories are above grade plane or two or more stories are basements.
Exceptions:
1.   Class I standpipes are allowed in buildings equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1 or 903.3.1.2.
2.   [Reserved.]
3.   [Reserved.]
4.   Class I manual dry standpipes are allowed in parking garages and parking facilities that are subject to freezing temperatures, provided that the hose connections are located as required for Class II standpipes in accordance with Section 905.5."
4.   Revise exception 2 to Section 905.3.2 by deleting "automatic dry and semiautomatic dry standpipes or."
5.   Delete Section 905.3.3.
6.   Revise Section 905.3.4.1 by deleting "approved."
7.   Revise Section 905.3.6 to read:
"905.3.6 Helistops and heliports.
Buildings with a rooftop helistop or heliport shall be equipped with a Class I or III standpipe system extended to the roof level on which the helistop or heliport is located."
8.   Revise Section 905.3.7 by deleting "Chapter 36 of."
9.   Revise Section 905.3.8 to read:
"905.3.8 Rooftop gardens, landscaped roofs, and occupiable rooftops.
Buildings or structures that have vegetative roofs, rooftop gardens, landscaped roofs or occupiable rooftops and that are equipped with a standpipe system shall have the standpipe system extended to the roof level on which the vegetative roof, rooftop garden, landscaped roof or occupiable rooftop is located."
10.   Revise Section 905.4 to read:
"905.4 Location of Class I standpipe hose connections.
Class I standpipe hose connections shall be provided in all of the following locations:
1.   In every required interior exit stairway, a hose connection shall be provided for each story above and below grade plane. Hose connections shall be located at the floor landing.
2.   [Reserved.]
3.   In every exit passageway, at the entrance from the exit passageway to other areas of a building.
4.   [Reserved.]
5.   Where the roof has a slope less than four units vertical in 12 units horizontal (33.3-percent slope), a hose connection shall be located to serve the roof or at the highest landing of an interior exit stairway with access to the roof provided in accordance with Section 1011.12.
6.   Where the most remote portion of a nonsprinklered floor or story is more than 150 feet (45 720 mm) from a hose connection or the most remote portion of a sprinklered floor or story is more than 200 feet (60 960 mm) from a hose connection, the fire code official is authorized to require that additional hose connections be provided in approved locations."
11.   Revise the exception to Section 905.4.1 to delete "approved."
12.   Revise Section 905.5.3 by replacing "approved" with "permitted."
13.   Revise Section 905.7.1 by deleting "in an approved manner."
14.   Revise Section 905.9 by adding the following after the last sentence:
"All valves in supply pipes to standpipe systems shall be secured open."
(Amend Coun. J. 2-19-20, p. 14473, Art. II, § 31; Amend Coun. J. 10-7-20, p. 21791, Art. II, § 15))