1. A fire protection system using antifreezes or other additives shall be protected by an approved reduced pressure principle backflow prevention assembly.
2. A dry type fire protection system shall be protected by an approved double check valve backflow prevention assembly.
3. Backflow prevention assemblies must be tested annually on a routine scheduled basis by the required licensed technician. The City of Ankeny fire marshal and water utility are both to be copied with test results.