801.23.2 Additional devices.
Appliances requiring a controlled chimney draft shall be permitted to be equipped with a listed barometric draft regulator or automatic damper installed and adjusted in accordance with the manufacturers' instructions. Automatic dampers shall be installed in accordance with Section 803.6.
801.23.3 Thermal safety (spill) switches.
Thermal safety (spill) switches shall be installed on barometric draft regulators and all other appurtenances that allow dilution air into chimneys or vents. Thermal safety (spill) switches shall be interlocked with all of the appliances connected to the same chimney or vent.
801.23.4 Location.
Barometric draft regulators shall be installed in the same room or enclosure as the appliance in such a manner as to prevent any difference in pressure between the regulator and the combustion air supply.
801.23.5 Positioning.
Barometric draft regulators shall be installed in the position for which they were designed with reference to the horizontal and vertical planes and shall be located so that the relief opening is not obstructed by any part of the appliance, adjacent construction or installation hardware.
801.24 Obstructions.
Devices or items that protrude into, impede or restrict the flow of vent gases shall not be installed in a vent connector, chimney, or vent.
801.25 Outdoor chimneys and vents.
Outdoor portions of chimneys or vents shall be provided with integral R-8 insulation or be provided with an R-8 insulation enclosure, where exposed to the outdoors for more than 5 feet (1524 mm).
802.1 General.
Vent systems shall be listed and labeled or field fabricated in accordance with NFPA 211. Type L vents shall be tested in accordance with UL 641.
802.2 Vent application.
The application of vents shall be in accordance with Table 802.2.
Vent Types | Appliance Types |
Type L oil vents | Oil-burning appliances listed and labeled for venting with Type L vents; gas appliances listed and labeled for venting with Type B vents. |