801.2.3 Support.
Chimneys and vents shall not be supported by the equipment they serve unless such equipment has been specifically designed for such loads.
801.2.4 Oil-fired appliances.
Oil-fired appliances shall be vented in accordance with this code and NFPA 31.
801.2.5 Gas fired appliances.
Gas fired appliances shall be vented in accordance with the New York City Fuel Gas Code.
801.3 Masonry chimneys.
Masonry chimneys shall be constructed in accordance with the New York City Building Code.
801.4 Positive flow.
Venting systems shall be designed and constructed so as to develop a positive flow adequate to convey all combustion products to the outside atmosphere.
801.5 Design.
Venting systems shall be designed in accordance with this chapter and comply with the requirements of the New York City Air Pollution Control Code.
801.6 Minimum size of chimney or vent.
Except as otherwise provided for in this chapter, the size of the chimney or vent, serving a single appliance, except engineered systems, shall have a minimum area equal to the area of the appliance connection.
801.7 Solid fuel-burning appliance flues.
The cross-sectional area of a flue serving a solid fuel-burning appliance shall be not greater than three times the cross-sectional area of the appliance flue collar or flue outlet.