5704.3.7.5.1 Fire extinguishing systems.
Liquid storage rooms shall be protected throughout by sprinkler systems installed in accordance with FC Chapter 9, FC Tables 5704.3.6.3(4) through 5704.3.6.3(8) and FC Table 5704.3.7.5.1 and the construction codes, including the Building Code. In-rack sprinklers shall additionally comply with the requirements of NFPA 13, as modified by FC Appendix B, and the construction codes, including the Building Code. Foam fire extinguishing systems and aqueous film-forming foam (AFFF) fire extinguishing systems shall not be used except when approved by the commissioner and the Commissioner of Buildings. Protection criteria developed from fire modeling or full-scale fire testing conducted at an approved testing laboratory are allowed in lieu of the protection as required in FC Tables 5704.3.6.3(2) through 5704.3.6.3(8) and FC Table 5704.3.7.5.1 and the construction codes, including the Building Code when approved by the commissioner and the Commissioner of Buildings.
Package Type | Class Liquid | Ceiling Sprinkler Design and Demand | Storage Height (feet) | Hose Demand (gpm) c | Duration AFFF Supply (minimum) | Duration Water Supply (hours) | ||||
Density (gpm/ft2) |
Area (square feet) | Temperature rating | Maximum spacing | Orifice size (inch) | ||||||
Cartoned | IB, IC, II and III | 0.40 | 2,000 | 286°F | 100 ft2 / head | 0.531 | 11 | 500 | 15 | 2 |
Uncartoned | IB, IC, II and III | 0.30 | 2,000 | 286°F | 100 ft2 / head | 0.5 or 0.531 | 12 | 500 | 15 | 2 |
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 square foot = 0.0929 m2, 1 gallon per minute = 3.785 L/m, 1 gallon per minute per square foot = 40.75 L/min/m2, °C. = (°F-32)/1.8.
a. System shall be a closed-head wet system with approved devices for proportioning aqueous film-forming foam.
b. Ceiling heights shall not exceed 30 feet.
c. Hose stream demand includes 1 1/2-inch inside hand hose, when required.
5704.3.7.5.2 Portable fire extinguishers.
A minimum of one portable fire extinguisher complying with the requirements of FC 906 and having a rating of not less than 20-B shall be located not less than 10 feet (3048 mm) or more than 50 feet (15 240 mm) from any Class I or II liquid storage area located outside of a liquid storage room. A minimum of one portable fire extinguisher having a rating of not less than 20-B shall be located outside of, but not more than 10 feet (3048 mm) from, the door opening into a liquid storage room.
5704.3.8 Liquid warehouses.
Buildings used for storage of flammable or combustible liquids in quantities exceeding those set forth in FC 5704.3.4 for control areas and FC 5704.3.7 for liquid storage rooms shall comply with the requirements of FC 5704.3.8.1 through 5704.3.8.5 and shall be constructed and separated as required by the construction codes, including the Building Code.
5704.3.8.1 Quantities and storage arrangement.
Except as may be limited by the commissioner at a particular premises in the interest of public safety, any amount of flammable and combustible liquids may be stored in a liquid warehouse as defined in NFPA 30. The arrangement of such storage shall be in accordance with FC Table 5704.3.6.3(2) or 5704.3.6.3(3).
5704.3.8.1.1 Mixed storage.
Mixed storage shall be in accordance with FC 5704.3.7.2.1.